TeSys LC1D6500 contactor, 4 poles, screw clamp terminals or lugs, without cover, 80A
TeSys model d contactor
TeSys LC1D6500 contactor, 4 poles, screw clamp terminals or lugs, without cover, 80A
TeSys model d contactor

TeSys D Contactor, 4P(2 NO + 2 NC), AC-1, <= 440V, 80A, 48VAC, 50/60 Hz Coil

Catalogue Number: LC1D65008E7
TeSys LC1D6500 contactor, 4 poles, screw clamp terminals or lugs, without cover, 80A
TeSys model d contactor
TeSys LC1D6500 contactor, 4 poles, screw clamp terminals or lugs, without cover, 80A
TeSys model d contactor
Retail
$2,378.28
RRP (Inc. GST)

Specifications

hide show
Range of product
TeSys D
Range
TeSys
Product name
TeSys D
Product or component type
contactor
Device short name
LC1D
Contactor application
resistive load
Utilisation category
AC-1
Poles description
4P
Pole contact composition
2 NO + 2 NC
[Ue] rated operational voltage
  • power circuit: <= 690 V AC 25...400 Hz
  • power circuit: <= 300 V DC
    • [Ie] rated operational current
      80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
      Control circuit type
      AC at 50/60 Hz
      [Uc] control circuit voltage
      48 V AC 50/60 Hz
      [Uimp] rated impulse withstand voltage
      6 kV conforming to IEC 60947
      Overvoltage category
      III
      [Ith] conventional free air thermal current
      80 A (at 60 °C) for power circuit
      Irms rated making capacity
      1000 A at 440 V for power circuit conforming to IEC 60947
      Rated breaking capacity
      1000 A at 440 V for power circuit conforming to IEC 60947
      [Icw] rated short-time withstand current
    • 520 A 40 °C - 10 s for power circuit
    • 900 A 40 °C - 1 s for power circuit
    • 110 A 40 °C - 10 min for power circuit
    • 260 A 40 °C - 1 min for power circuit
      • Associated fuse rating
      • 125 A gG at <= 690 V coordination type 1 for power circuit
      • 125 A gG at <= 690 V coordination type 2 for power circuit
        • Average impedance
          1.5 mOhm - Ith 80 A 50 Hz for power circuit
          [Ui] rated insulation voltage
        • power circuit: 600 V CSA certified
        • power circuit: 600 V UL certified
        • power circuit: 690 V conforming to IEC 60947-4-1
          • Electrical durability
            1.4 Mcycles 80 A AC-1 at Ue <= 440 V
            Power dissipation per pole
            9.6 W AC-1
            Protective cover
            without
            Mounting support
          • plate
          • rail
            • Standards
            • CSA C22.2 No 14
            • EN 60947-4-1
            • EN 60947-5-1
            • IEC 60947-4-1
            • IEC 60947-5-1
            • UL 508
              • Product certifications
              • GL
              • BV
              • UL
              • DNV
              • LROS (Lloyds register of shipping)
              • CCC
              • CSA
              • RINA
              • GOST
                • Connections - terminals
                • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
                • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
                • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
                • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
                • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end
                • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end
                • power circuit: screw clamp terminals 1 cable(s) 1-35 mm²flexible without cable end
                • power circuit: screw clamp terminals 2 cable(s) 1-25 mm²flexible without cable end
                • power circuit: screw clamp terminals 1 cable(s) 1-35 mm²flexible with cable end
                • power circuit: screw clamp terminals 2 cable(s) 1-25 mm²flexible with cable end
                • power circuit: screw clamp terminals 1 cable(s) 1-35 mm²solid without cable end
                • power circuit: screw clamp terminals 2 cable(s) 1-25 mm²solid without cable end
                  • Tightening torque
                  • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                  • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
                  • power circuit: 8 N.m - on screw clamp terminals - cable 25-35 mm² hexagonal screw head 4 mm
                  • power circuit: 5 N.m - on screw clamp terminals - cable 1-25 mm² hexagonal screw head 4 mm
                    • Operating time
                    • 4...19 ms opening
                    • 12...26 ms closing
                      • Safety reliability level
                      • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                      • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                        • Mechanical durability
                          6 Mcycles
                          Maximum operating rate
                          3600 cyc/h 60 °C
                          Coil technology
                          without built-in suppressor module
                          Inrush power in VA
                        • 140-140 VA 60 Hz cos phi 0.75 (at 20 °C)
                        • 160-160 VA 50 Hz cos phi 0.75 (at 20 °C)
                          • Hold-in power consumption in VA
                          • 13-13 VA 60 Hz cos phi 0.3 (at 20 °C)
                          • 15-15 VA 50 Hz cos phi 0.3 (at 20 °C)
                            • Heat dissipation
                              4-5 W at 50/60 Hz
                              Contact compatibility
                              M1
                              Compatibility code
                              LC1D
                              IP degree of protection
                              IP20 front face conforming to IEC 60529
                              Protective treatment
                              TH conforming to IEC 60068-2-30
                              Pollution degree
                              3
                              Ambient air temperature for storage
                              -60-80 °C
                              Operating altitude
                              3000 m without derating
                              Fire resistance
                              850 °C conforming to IEC 60695-2-1
                              Flame retardance
                              V1 conforming to UL 94
                              Mechanical robustness
                            • vibrations contactor open: 2 Gn, 5...300 Hz
                            • vibrations contactor closed: 4 Gn, 5...300 Hz
                            • shocks contactor closed: 15 Gn for 11 ms
                            • shocks contactor open: 10 Gn for 11 ms
                              • Height
                                127 mm
                                Width
                                85 mm
                                Depth
                                125 mm
                                Net weight
                                1.45 kg
                                Unit Type of Package 1
                                PCE
                                Number of Units in Package 1
                                1
                                Package 1 Weight
                                1.468 kg
                                Package 1 Height
                                15.8 cm
                                Package 1 width
                                13.8 cm
                                Package 1 Length
                                11.6 cm
                                Sustainable offer status
                                Green Premium product
                                REACh free of SVHC
                                Yes
                                EU RoHS Directive
                                Compliant
                                Toxic heavy metal free
                                Yes
                                Mercury free
                                Yes
                                RoHS exemption information
                                Yes
                                China RoHS Regulation
                                 Pro-active China RoHS declaration (out of China RoHS legal scope)
                                Environmental Disclosure
                                ENVPEP1503009EN
                                Circularity Profile
                                ENVEOLI1503009EN
                                WEEE
                                The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                                PVC free
                                Yes
                                California proposition 65
                                WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov
                                Warranty
                                18 months

                                Documents & downloads

                                hide show
                                Filter items
                                • All

                                • Product Brochures

                                • Technical Data Catalogues

                                • Installation Instruction

                                • End of Life Manual

                                • Product Environmental

                                • Data Bulletin

                                • Certificates (MSDS)

                                • Declaration of Conformity

                                Frequently Asked Questions

                                hide show

                                What is the power terminal lug data for the LC1D40, LC1D50, LC1D65, LP1D40, LP1D50, and LP1D65 contactor?

                                Issue:
                                Identifying power terminal lug data for the D2 style contactors

                                Product Line:
                                Tesys D line contactors

                                Environment:
                                Products sold and used in the United States

                                Cause:
                                Power terminal lug data required

                                Resolution:
                                For contactors with screw clamp terminals:
                                stranded cable w/o cable end : One #10-3 AWG or Two #10-4 AWG per terminal.
                                stranded cable w/cable end: One #10-4 AWG or Two #12-2 AWG per terminal.
                                solid cable: One #10-3 AWG or Two #10-6 AWG per terminal.

                                What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

                                Issue:
                                Identifying maximum voltage of an LC1D contactor

                                Product Line:
                                TeSys D Contactors

                                Environment:
                                IEC contactors and starters used in North America

                                Cause:
                                n/a

                                Resolution:
                                IThe maximum voltage per UL and CSA is 600VAC. 
                                 

                                Are the D-Line contactors rated to break DC voltages?

                                Issue: 
                                Can the TeSys D line be used to control DC loads? 

                                Product Line:
                                Tesys D contactors

                                Environment:
                                Products sold and used in the United States
                                 
                                Cause:
                                 DC power circuit
                                 
                                Resolution:
                                 
                                Yes, 75 VDC (125 VDC for D115 & D150) per pole which means that through a four pole device breaking 300 VDC is possible by wiring all four power poles in series. However, be aware that the device current ratings will differ according to the number of poles in series and the type of application.

                                Devices are suitable but not UL Listed for DC applications.

                                More information on their DC ratings can be found in the current TeSys Motor Control and Protection Compentns catalog: https://www.schneider-electric.us/en/download/document/MKTED210011EN/


                                 

                                Video: What auxiliary contact modules are available for the LC1D and LC2D contactors?

                                Issue:
                                Auxiliary contact modules for the LC1D and LC2D contactors

                                Product Line: 
                                Contactor and Starters - IEC

                                Environment:
                                North American Products

                                Resolution:
                                Select based on application requirements. Please note that the TeSys and Pre-TeSys auxiliary blocks are backward/forward compatible.
                                Front Mounting; maximum of 1 block per contactor:

                                N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
                                --1-----------1---------LADN11-----------LA1DN11
                                --1-----------1---------LADN11G---------LA1DN11G (See Footnote 1)
                                --1-----------1---------LADN11P---------LA1DN11P (See Footnote 1)
                                --2-----------0---------LADN20-----------LA1DN20
                                --2-----------0---------LA1DX20---------LA1DX20 (See Footnote 2)
                                --2-----------0---------LA1DY20---------LA1DY20 (See Footnote 3)
                                --0-----------2---------LADN02-----------LA1DN02
                                --2-----------2---------LADN22-----------LA1DN22
                                --2-----------2---------LADN22G---------LA1DN22G (See Footnote 1)
                                --2-----------2---------LADN22P---------LA1DN22P (See Footnote 1)
                                --2-----------2---------LADC22------------LA1DC22 (See Footnote 4)
                                --3-----------1---------LADN31------------LA1DN31
                                --3-----------1---------LA1DZ31----------LA1DZ31 (See Footnote 5)
                                --1-----------3---------LADN13------------LA1DN13
                                --4-----------0---------LADN40------------LA1DN40
                                --4-----------0---------LA1DZ40-----------LA1DZ40 (See Footnote 6)
                                --0-----------4---------LADN04------------LA1DN04




                                Front Mounting; maximum of 1 block per contactor: For use with D2 Series 25 amp through 80 amp contactors and TeSys Series 40 amp through 80 amp only.

                                N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
                                --1-----------0--------LADN10----------LA1DN10
                                --0-----------1--------LADN01----------LA1DN01

                                Side Mounting; maximum of 1 block on each side for D2 Series and Tesys Series 40 through 80 amp contactors. Tesys 9 through 32, 115, and 150 amps contactors will accept 1 block and is limited to left side only. (*) DC control devices will not accept side mount auxiliaries.
                                (*) DC control exceptions that will accept one left side mounted auxiliary: LC1D115 & LC1D150.

                                N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
                                --1-----------1--------LAD8N11----------LA8DN11
                                --2-----------0--------LAD8N20----------LA8DN20
                                --0-----------2--------LAD8N02----------N/A

                                Footnotes:
                                {1} EN50 012 Machine Tool Terminal Markings
                                {2} (2) NO Sealed Dust Tight Contacts
                                {3} Gold Flash Contacts
                                {4} (1) NO & (1) NC Standard and (1) NO & (1) NC Make Before Break
                                {5} (2) NO Dust Tight Contacts & (1) NO & (1) NC Standard Contacts
                                {6} (2) NO Dust Tight Contacts & (2) NO Standard Contacts

                                What is the color scheme of the Tesys D-Line contactors?

                                Issue:
                                Looking for different color scheme of the Tesys D-Line contactors.

                                Product Line:
                                Tesys D Contactors

                                Environment:
                                LC1D contactors

                                Resolution:
                                Beige and dark gray.
                                 

                                Where are the control coil terminals for TeSys LC1D09 to LC1D38 contactor?

                                Issue:
                                Determine the control coil terminal marking and location on LC1D09 to LC1D38 contactor

                                Product Line: 
                                Tesys D Contactors

                                Environment:
                                IEC contactors

                                Resolution:
                                The coil terminals are marked A1 and A2, you can see them on the front of the contactor on the white part (control section).  They are next to the auxiliary contact (13/14, 21/22) terminals.
                                 

                                What are the stand alone short circuit current ratings on the LC1D** contactors?

                                Issue:
                                Tesys D SCCR

                                Product Line:
                                Contactors and Overload Relays

                                Environment:
                                TeSys™ D Contactors and Overload Relays
                                 
                                Resolution:
                                The contactors have a stand alone withstand rating that has been established by UL and is based on the maximum horsepower rating for a given device. However, only combination type starters are supplied with short circuit protective devices having a short circuit current rating.

                                They are as follows:
                                Horsepower SCCR (A)

                                0 thru 1 1,000
                                1 thru 50 5,000
                                51 thru 200 10,000
                                201 thru 400 18,000
                                401 thru 600 30,000
                                601 thru 900 42,000
                                901 thru 1600 85,000
                                1601+ 100,000

                                What is the replacement AC coil for LC1D/LC2D40, D50, D65, D80, and D95?

                                Issue:
                                AC Coil information for LC1D/LC2D40, D50, D65, D80, and D95

                                Product Line:
                                Tesys D Replacement Parts

                                Environment:
                                TeSys™ D AC Coils

                                Resolution:

                                Will the LAD** time delay auxiliary contact module fit the D2 series pre-Tesys contactors?

                                Issue:
                                Can new accessories be used on older style contactors

                                Product Line:
                                IEC contactors and starters

                                Environment:
                                Products sold and used in the United States

                                Cause:
                                Identifying product compatibility

                                Resolution:
                                Yes, all front mount D2 and Tesys series auxiliary modules are backward forward compatible.


                                 

                                What is the part cod for a contactor 4P 2N/C 2N/O 48Vac coil

                                 The part code is LC1D40008E7

                                What is the replacement coil part number for the LC*D09 through LC*D32 and LC*DT20 through LC*DT40 TeSys contactors?

                                Issue:
                                Identifying replacement coils for tesys D non-reversing and reversing conactors

                                Product Line:
                                IEC Contactors and Starters

                                Environment:
                                Products sold and used in the United States

                                Cause:
                                Replacement coil is needed

                                Resolution:
                                DC replacement coils are not available.
                                AC Coils are 50/60 hertz for voltages as listed below:

                                Volts - Part Number
                                12 ____ LXD1J7
                                21 ____ LXD1Z7
                                24 ____ LXD1B7
                                32 ____ LXD1C7
                                36 ____ LXD1CC7
                                42 ____ LXD1D7
                                48 ____ LXD1E7
                                60 ____ LXD1EE7
                                100 ___ LXD1K7 ( never brought to North America )
                                110 ___ LXD1F7
                                115 ___ LXD1FE7
                                120 ___ LXD1G7
                                127 ___ LXD1FC7
                                200 ___ LXD1L7
                                208 ___ LXD1LE7
                                220 ___ LXD1M7
                                230 ___ LXD1P7
                                240 ___ LXD1U7
                                277 ___ LXD1W7
                                380 ___ LXD1Q7
                                400 ___ LXD1V7
                                415 ___ LXD1N7
                                440 ___ LXD1R7
                                480 ___ LXD1T7
                                575 ___ LXD1SC7
                                600 ___ LXD1X7
                                690 ___ LXD1Y7


                                Note: A contactor with an AC coil can be changed to a different AC voltage coil, IE you can take an LC1D09 with a 120VAC coil and put a 24VAC coil in it instead. An AC device cannot be switched to a DC coil, and a DC device cannot be switches to an AC coil. 

                                What is the difference between the LC1D25E7 and LC1D258E7?

                                The LC1D25E7 is a 3 Poles 25 Amps (AC-3) Contactor

                                Where as

                                The LC1D258E7 is a 4 Pole (2NO + 2NC) 25 Amps (AC-3) Contactor

                                https://www.schneider-electric.com.au/en/search/LC1D25E7