TeSys LC1D contactor, 3 poles, power connections by EverLink, with cover, 40A to 65A

TeSys D Contactor, 3P(3 NO), AC-3, <= 440V, 50A, 12VAC, 50 Hz Coil

Catalogue Number: LC1D50AJ5

Discontinued

TeSys LC1D contactor, 3 poles, power connections by EverLink, with cover, 40A to 65A
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Range of product
TeSys D
Range
TeSys
Product name
TeSys D
Product or component type
contactor
Device short name
LC1D
Contactor application
  • motor control
  • resistive load
    • Utilisation category
    • AC-1
    • AC-3
    • AC-4
      • Poles description
        3P
        Pole contact composition
        3 NO
        [Ue] rated operational voltage
      • power circuit: <= 690 V AC 25...400 Hz
      • power circuit: <= 300 V DC
        • [Ie] rated operational current
        • 50 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
        • 80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
          • Motor power kW
          • 15 kW at 220...230 V AC 50/60 Hz (AC-3)
          • 22 kW at 380...400 V AC 50/60 Hz (AC-3)
          • 30 kW at 500 V AC 50/60 Hz (AC-3)
          • 33 kW at 660...690 V AC 50/60 Hz (AC-3)
          • 25 kW at 415 V AC 50/60 Hz (AC-3)
          • 30 kW at 440 V AC 50/60 Hz (AC-3)
          • 11 kW at 400 V AC 50/60 Hz (AC-4)
            • Motor power hp
            • 3 hp at 115 V AC 50/60 Hz for 1 phase motors
            • 7.5 hp at 230/240 V AC 50/60 Hz for 1 phase motors
            • 15 hp at 200/208 V AC 50/60 Hz for 3 phases motors
            • 15 hp at 230/240 V AC 50/60 Hz for 3 phases motors
            • 40 hp at 460/480 V AC 50/60 Hz for 3 phases motors
            • 40 hp at 575/600 V AC 50/60 Hz for 3 phases motors
              • Control circuit type
                AC at 50 Hz
                [Uc] control circuit voltage
                12 V AC 50 Hz
                Auxiliary contact composition
                1 NO + 1 NC
                [Uimp] rated impulse withstand voltage
                6 kV conforming to IEC 60947
                Overvoltage category
                III
                [Ith] conventional free air thermal current
              • 10 A (at 60 °C) for signalling circuit
              • 80 A (at 60 °C) for power circuit
                • Irms rated making capacity
                • 140 A AC for signalling circuit conforming to IEC 60947-5-1
                • 250 A DC for signalling circuit conforming to IEC 60947-5-1
                • 900 A at 440 V for power circuit conforming to IEC 60947
                  • Rated breaking capacity
                    900 A at 440 V for power circuit conforming to IEC 60947
                    [Icw] rated short-time withstand current
                  • 400 A 40 °C - 10 s for power circuit
                  • 810 A 40 °C - 1 s for power circuit
                  • 84 A 40 °C - 10 min for power circuit
                  • 208 A 40 °C - 1 min for power circuit
                  • 100 A - 1 s for signalling circuit
                  • 120 A - 500 ms for signalling circuit
                  • 140 A - 100 ms for signalling circuit
                    • Associated fuse rating
                    • 10 A gG for signalling circuit conforming to IEC 60947-5-1
                    • 100 A gG at <= 690 V coordination type 1 for power circuit
                    • 100 A gG at <= 690 V coordination type 2 for power circuit
                      • Average impedance
                        1.5 mOhm - Ith 80 A 50 Hz for power circuit
                        [Ui] rated insulation voltage
                      • power circuit: 600 V CSA certified
                      • power circuit: 600 V UL certified
                      • signalling circuit: 690 V conforming to IEC 60947-1
                      • signalling circuit: 600 V CSA certified
                      • signalling circuit: 600 V UL certified
                      • power circuit: 690 V conforming to IEC 60947-4-1
                        • Electrical durability
                        • 1.45 Mcycles 50 A AC-3 at Ue <= 440 V
                        • 1.1 Mcycles 80 A AC-1 at Ue <= 440 V
                          • Power dissipation per pole
                          • 3.7 W AC-3
                          • 9.6 W AC-1
                            • Protective cover
                              with
                              Mounting support
                            • plate
                            • rail
                              • Standards
                              • CSA C22.2 No 14
                              • EN 60947-4-1
                              • EN 60947-5-1
                              • IEC 60947-4-1
                              • IEC 60947-5-1
                              • UL 508
                                • Product certifications
                                • RINA
                                • LROS (Lloyds register of shipping)
                                • CSA
                                • DNV
                                • BV
                                • UL
                                • GOST
                                • CCC
                                • GL
                                  • Connections - terminals
                                  • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
                                  • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
                                  • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
                                  • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
                                  • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end
                                  • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end
                                  • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²flexible without cable end
                                  • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²flexible without cable end
                                  • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²flexible with cable end
                                  • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²flexible with cable end
                                  • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²solid without cable end
                                  • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²solid without cable end
                                    • Tightening torque
                                    • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                                    • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
                                    • power circuit: 8 N.m - on EverLink BTR screw connectors - cable 25-35 mm² hexagonal screw head 4 mm
                                    • power circuit: 5 N.m - on EverLink BTR screw connectors - cable 1-25 mm² hexagonal screw head 4 mm
                                      • Operating time
                                      • 4...19 ms opening
                                      • 12...26 ms closing
                                        • Safety reliability level
                                        • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                                        • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                                          • Mechanical durability
                                            6 Mcycles
                                            Maximum operating rate
                                            3600 cyc/h 60 °C
                                            Coil technology
                                            without built-in suppressor module
                                            Control circuit voltage limits
                                          • operational: 0.8...1.1 Uc AC 50 Hz (at 60 °C)
                                          • drop-out: 0.3...0.6 Uc AC 50 Hz (at 60 °C)
                                            • Inrush power in VA
                                              160-160 VA 50 Hz cos phi 0.75 (at 20 °C)
                                              Hold-in power consumption in VA
                                              15-15 VA 50 Hz cos phi 0.3 (at 20 °C)
                                              Heat dissipation
                                              4-5 W at 50 Hz
                                              Auxiliary contacts type
                                            • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
                                            • type mirror contact 1 NC conforming to IEC 60947-4-1
                                              • Signalling circuit frequency
                                                25...400 Hz
                                                Minimum switching current
                                                5 mA for signalling circuit
                                                Minimum switching voltage
                                                17 V for signalling circuit
                                                Non-overlap time
                                              • 1.5 ms on de-energisation between NC and NO contact
                                              • 1.5 ms on energisation between NC and NO contact
                                                • Insulation resistance
                                                  > 10 MOhm for signalling circuit
                                                  Contact compatibility
                                                  M2
                                                  Compatibility code
                                                  LC1D
                                                  IP degree of protection
                                                  IP20 front face conforming to IEC 60529
                                                  Protective treatment
                                                  TH conforming to IEC 60068-2-30
                                                  Pollution degree
                                                  3
                                                  Ambient air temperature for operation
                                                  -5-60 °C
                                                  Ambient air temperature for storage
                                                  -60-80 °C
                                                  Permissible ambient air temperature around the device
                                                  -40-70 °C at Uc
                                                  Operating altitude
                                                  3000 m without
                                                  Fire resistance
                                                  850 °C conforming to IEC 60695-2-1
                                                  Flame retardance
                                                  V1 conforming to UL 94
                                                  Mechanical robustness
                                                • vibrations contactor open: 2 Gn, 5...300 Hz
                                                • vibrations contactor closed: 4 Gn, 5...300 Hz
                                                • shocks contactor closed: 15 Gn for 11 ms
                                                • shocks contactor open: 10 Gn for 11 ms
                                                  • Height
                                                    122 mm
                                                    Width
                                                    55 mm
                                                    Depth
                                                    120 mm
                                                    Net weight
                                                    0.855 kg
                                                    Warranty
                                                    18 months

                                                    Documents & downloads

                                                    hide show
                                                    Filter items
                                                    • All

                                                    • Product Brochures

                                                    • Installation Instruction

                                                    • Data Bulletin

                                                    • Product Environmental

                                                    • End of Life Manual

                                                    • Certificates (MSDS)

                                                    • Declaration of Conformity

                                                    Frequently Asked Questions

                                                    hide show

                                                    What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

                                                    Issue:
                                                    Identifying maximum power voltage of an LC1D contactor

                                                    Product Line:
                                                    Digest 177 Section 18: IEC Contactors

                                                    Environment:
                                                    Products sold and used in the United States

                                                    Cause:
                                                    Identifying ratings per UL and CSA

                                                    Resolution:
                                                    It is 600Vac.


                                                     

                                                    What is the power terminal lug data for the LC1D40, LC1D50, LC1D65, LP1D40, LP1D50, and LP1D65 contactor?

                                                    Issue:
                                                    Identifying power terminal lug data for the D2 style contactors

                                                    Product Line:
                                                    Tesys D line contactors

                                                    Environment:
                                                    Products sold and used in the United States

                                                    Cause:
                                                    Power terminal lug data required

                                                    Resolution:
                                                    For contactors with screw clamp terminals:
                                                    stranded cable w/o cable end : One #10-3 AWG or Two #10-4 AWG per terminal.
                                                    stranded cable w/cable end: One #10-4 AWG or Two #12-2 AWG per terminal.
                                                    solid cable: One #10-3 AWG or Two #10-6 AWG per terminal.

                                                    What is the altitude derating for a TeSys D-Line contactor?

                                                    Issue:​
                                                    What is the altitude derating for a TeSys D-Line contactor?

                                                    Product Line:
                                                    Digest 177 Section 18 : Contactors and Starters, IEC

                                                    Environment:
                                                    North American Products

                                                    Resolution:
                                                    The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

                                                    Voltage
                                                    3500m x 0.90
                                                    4000m x 0.80
                                                    4500m x 0.70
                                                    5000m x 0.60

                                                    Current
                                                    3500m x 0.92
                                                    4000m x 0.90
                                                    4500m x 0.88
                                                    5000m x 0.86

                                                    For example, an LC1D80 at 5000 meters:
                                                    - The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
                                                    - The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



                                                     

                                                    Looking for a LC1D50A.. with a 240v coil

                                                     Part code is LC1D50AU7

                                                    What replaces LC1D50BD

                                                    Replacement LC1D50ABD

                                                    What is difference between LC1D50U7 and LC1D50AU7?

                                                    Following are the differences between the LC1D50U7 and the LC1D50AU7:

                                                    LC1D50AU7 has everlink terminals.
                                                    LC1D50AU7....is slightly larger case and accommodate LRD3XX overloads
                                                    Whereas
                                                    LC1D50U7 contactors accommodate LRD33XX overloads.

                                                     

                                                    How Can the LC1D50AU7 Contactor be mounted?

                                                    Two ways -  the LC1D50AU7 can be DIN Rail mounted and Plate mounted.

                                                    See the attached datasheet for further information.

                                                    What is the Overload for LC1D50AU7 range is 37..50 Amps?

                                                    LRD350

                                                    What mechanical interlock should I use with the LC1D50A••?

                                                    The mechanical interlock LAD4CM is the correct one for use with the LC1D50A••.

                                                    See attached datasheet for futher information on the LAD4CM.

                                                    What is the part number for the contactor that replaces the LC1D50E5?

                                                    The part number for the contactor that replaces the LC1D50E5 is - LC1D50AE7

                                                    For further information , visit link below:-
                                                    https://www.schneider-electric.com.au/en/search/LC1D50AE7
                                                     

                                                    What is the part code for a 24V AC coil for the LC1D50A?

                                                    LXD3B7
                                                     

                                                    What is the part number for a front mount auxillary to suit a LC1D50A contactor?

                                                    The part number for a front mount auxiliary to suit a LC1D50A contactor is a LADN11.
                                                     

                                                    What is the code for a 40A 110VAC contactor ?

                                                    LC1D40AF7

                                                    What is the part number for overload 37-50A for LC1D50U7?

                                                    The part number for overload 37-50A for LC1D50U7 is LRD3357
                                                    LRD3357
                                                    TeSys LRD thermal overload relays - 37...50 A - class 10A

                                                    For more information see:
                                                    https://eshop.schneider-electric.com/product.aspx?prod_id=LRD3357&org=21&lang=1&dist=276&tab=10&ses_id
                                                     

                                                    Will the LAD** time delay auxiliary contact module fit the D2 series pre-Tesys contactors?

                                                    Issue:
                                                    Can new accessories be used on older style contactors

                                                    Product Line:
                                                    IEC contactors and starters

                                                    Environment:
                                                    Products sold and used in the United States

                                                    Cause:
                                                    Identifying product compatibility

                                                    Resolution:
                                                    Yes, all front mount D2 and Tesys series auxiliary modules are backward forward compatible.


                                                     

                                                    Can I use a LA9D6569 reversing kit with LC1D40AU7 contactors

                                                    No, correct kit is a LAD9R3.

                                                    What is the difference between the LC1D1506N7 and the LC1D150N7?

                                                    The LC1D1506N7 can accept 5X25mm Bars aswell as Lugs or ring terminals. The LC1D150N7 only accepts cable lugs upto 120mm2.

                                                    What is the code for the newer version of the LC1D40U7

                                                    That has been replaced with the Everlink LC1D40AU7

                                                    What is the part number for the red safety cover to go on the LC1D contactors?

                                                    The LC1D09-65 take the LAD9ET1S
                                                    The LC1D80-95 take the LAD9ET3S 
                                                    The LC1D115-150 take the LAD9ET4S

                                                    How many wires can you install on the Power poles for the LC1D65A contactor?

                                                     Issue:
                                                    How many wires can you install on the Power poles for the LC1D65A contactor?

                                                    Product line:
                                                    Tesys D, Everlink

                                                    Environment:
                                                    LC1D40A LC1D50A LC1D65A

                                                    Cause:
                                                    Documentation not found

                                                    Resolution:
                                                    The LC1D40A to LC1D65A Everlink version contactors can use 2 power cables per phase.  1x AWG 16 to AWG 4 plus 1x AWG 16 to AWG 2. 

                                                    Instruction bulletin attached.

                                                    Video: What auxiliary contact modules are available for the LC1D and LC2D contactors?

                                                    Issue:
                                                    Auxiliary contact modules for the LC1D and LC2D contactors

                                                    Product Line: 
                                                    Contactor and Starters - IEC

                                                    Environment:
                                                    North American Products

                                                    Resolution:
                                                    Select based on application requirements. Please note that the TeSys and Pre-TeSys auxiliary blocks are backward/forward compatible.
                                                    Front Mounting; maximum of 1 block per contactor:

                                                    N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
                                                    --1-----------1---------LADN11-----------LA1DN11
                                                    --1-----------1---------LADN11G---------LA1DN11G (See Footnote 1)
                                                    --1-----------1---------LADN11P---------LA1DN11P (See Footnote 1)
                                                    --2-----------0---------LADN20-----------LA1DN20
                                                    --2-----------0---------LA1DX20---------LA1DX20 (See Footnote 2)
                                                    --2-----------0---------LA1DY20---------LA1DY20 (See Footnote 3)
                                                    --0-----------2---------LADN02-----------LA1DN02
                                                    --2-----------2---------LADN22-----------LA1DN22
                                                    --2-----------2---------LADN22G---------LA1DN22G (See Footnote 1)
                                                    --2-----------2---------LADN22P---------LA1DN22P (See Footnote 1)
                                                    --2-----------2---------LADC22------------LA1DC22 (See Footnote 4)
                                                    --3-----------1---------LADN31------------LA1DN31
                                                    --3-----------1---------LA1DZ31----------LA1DZ31 (See Footnote 5)
                                                    --1-----------3---------LADN13------------LA1DN13
                                                    --4-----------0---------LADN40------------LA1DN40
                                                    --4-----------0---------LA1DZ40-----------LA1DZ40 (See Footnote 6)
                                                    --0-----------4---------LADN04------------LA1DN04




                                                    Front Mounting; maximum of 1 block per contactor: For use with D2 Series 25 amp through 80 amp contactors and TeSys Series 40 amp through 80 amp only.

                                                    N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
                                                    --1-----------0--------LADN10----------LA1DN10
                                                    --0-----------1--------LADN01----------LA1DN01

                                                    Side Mounting; maximum of 1 block on each side for D2 Series and Tesys Series 40 through 80 amp contactors. Tesys 9 through 32, 115, and 150 amps contactors will accept 1 block and is limited to left side only. (*) DC control devices will not accept side mount auxiliaries.
                                                    (*) DC control exceptions that will accept one left side mounted auxiliary: LC1D115 & LC1D150.

                                                    N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
                                                    --1-----------1--------LAD8N11----------LA8DN11
                                                    --2-----------0--------LAD8N20----------LA8DN20
                                                    --0-----------2--------LAD8N02----------N/A

                                                    Footnotes:
                                                    {1} EN50 012 Machine Tool Terminal Markings
                                                    {2} (2) NO Sealed Dust Tight Contacts
                                                    {3} Gold Flash Contacts
                                                    {4} (1) NO & (1) NC Standard and (1) NO & (1) NC Make Before Break
                                                    {5} (2) NO Dust Tight Contacts & (1) NO & (1) NC Standard Contacts
                                                    {6} (2) NO Dust Tight Contacts & (2) NO Standard Contacts

                                                    What are the dimensions of LC1D40AB7 ?

                                                    Height 122 mm
                                                    Width 55 mm
                                                    Depth 120 mm
                                                    Product weight 1.4 kg

                                                    What is the part number for a 3 POLE, 40A, 24V AC coil contactor?

                                                    The Part number for a 3 pole, 40A, 24V AC coil contactor is LC1D40AB7

                                                    Are the D-Line contactors rated to break DC voltages?

                                                    Issue: 
                                                    Can the TeSys D line be used to control DC loads? 

                                                    Product Line:
                                                    Tesys D contactors

                                                    Environment:
                                                    Products sold and used in the United States
                                                     
                                                    Cause:
                                                     DC power circuit
                                                     
                                                    Resolution:
                                                     
                                                    Yes, 75 VDC (125 VDC for D115 & D150) per pole which means that through a four pole device breaking 300 VDC is possible by wiring all four power poles in series. However, be aware that the device current ratings will differ according to the number of poles in series and the type of application.

                                                    Devices are suitable but not UL Listed for DC applications.

                                                    More information on their DC ratings can be found in the current TeSys Motor Control and Protection Compentns catalog: https://www.schneider-electric.us/en/download/document/MKTED210011EN/


                                                     

                                                    What are the stand alone short circuit current ratings on the LC1D** contactors?

                                                    Issue:
                                                    Tesys D SCCR

                                                    Product Line:
                                                    Contactors and Overload Relays

                                                    Environment:
                                                    TeSys™ D Contactors and Overload Relays
                                                     
                                                    Resolution:
                                                    The contactors have a stand alone withstand rating that has been established by UL and is based on the maximum horsepower rating for a given device. However, only combination type starters are supplied with short circuit protective devices having a short circuit current rating.

                                                    They are as follows:
                                                    Horsepower SCCR (A)

                                                    0 thru 1 1,000
                                                    1 thru 50 5,000
                                                    51 thru 200 10,000
                                                    201 thru 400 18,000
                                                    401 thru 600 30,000
                                                    601 thru 900 42,000
                                                    901 thru 1600 85,000
                                                    1601+ 100,000

                                                    Are contactors LC1D38.. and LC1D40A.. the same size?

                                                    No the two contactor are not the same size, LC1D40A.. is bigger.

                                                    LC1D38N7
                                                    TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 38 A - 415 V AC 50/60 Hz coil     LC1D40AN7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 40 A - 415 V AC 50/60 Hz coil

                                                    For more information see:
                                                    https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LC1D38N7;
                                                    https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LC1D40AN7




                                                     

                                                    What does the (3) designate in the part number LC1D123G7?

                                                    For spring termination versions, add (3) to the catalog number prior to adding the voltage code. (ex. LC1D12G7 becomes a LC1D123G7 or LC1D40AG7 becomes LC1D40A3G7). This applies only for the LC1D09 - LC1D65A contactors. Note: For the LC1D40A to D65A, the spring terminals are only on the control terminations and not on power terminations.



                                                    CTA-ID : 2053127

                                                    What is the auxiliary 3 x N/O and 1 x N/C front fitted needed for a LC1D5011 contactor

                                                    The Auxiliary is an LADN31

                                                    Can the D range AC contactor be mounted on the ceiling ?

                                                    The AC contactor mounted horizontally as follows - Not recommended practice

                                                    For contactors with AC coil, when the contactor is mounted in horizontal position, the speed for making and breaking is impacted :
                                                    Floor mounted : the opening is slower.
                                                    Ceiling mounted : the closing is slower.
                                                    Then when mounted in horizontal position, the following recommendations shall apply :
                                                    Use on fix machines only (no vertical shocks allowed),
                                                    Additives forbidden,
                                                    Electrical durability not guaranteed (derating probably in the order of 0,70 but no existing confirmation tests)
                                                    AC1 current derated at 80% of the catalogue values,
                                                     
                                                    Inrush voltage for contactors mounted on the floor:
                                                    CAD/LC1D09/12/18          89%
                                                    LC1D25/32/38                    84%
                                                    LC1D40/50/65                    86%
                                                    LC1D80/95                          84%
                                                     Drop-out voltage for contactors mounted on the floor:
                                                    CAD/LC1D09/12/18          96%
                                                    LC1D25/32/38                    94%
                                                    LC1D40/50/65                    97%
                                                    LC1D80/95                          94%

                                                    Inrush voltage for contactors mounted on the ceiling:
                                                     CAD/LC1D09/12/18         114%
                                                    LC1D25/32/38                    114%
                                                    LC1D40/50/65                    111%
                                                    LC1D80/95                          111%
                                                    Drop-out voltage for contactors mounted on the ceiling:
                                                    CAD/LC1D09/12/18          108%
                                                    LC1D25/32/38                    106%
                                                    LC1D40/50/65                    107%
                                                    LC1D80/95                          105%
                                                     
                                                    For example, for LC1D32* fitted:
                                                    in normal position, the drop out control voltage limits is 0,3 to 0,6 Uc,
                                                    on floor position, the drop out control voltage limits is 0,28 to 0,56 Uc (0,3x0,94 and 0,6x0,94).

                                                    Is there a retrofit plate available for replacement of LC1D40-D65 contactors with the LC1D40A-65A contactors?

                                                    Use a LAD7X3 retrofit plate.


                                                    CTA-ID : 2053453

                                                    What replaces LC1D1801U5

                                                     Part code LC1D18U7

                                                    What are the part numbers of contactors in LE3AC075N7*

                                                    Part no LE3AC075N7 consists  Two  of LC1D80U7 and one of LC1D50U7 contactors.

                                                    What is the spare 48VAC coil for an LC1D40A contactor?

                                                    LXD3E7

                                                    What is the replacement contactor for the LC1D65004F5?

                                                    The new code is LC1DT80AF7 which is made to order.

                                                    What is the code for a 415VAC coil for a LC1D40A Contactor?

                                                    The 415V coil is LXD3N7

                                                    What is the 240V coil needed for a LC1D80008 contactor

                                                     The coil is a LX1D6U7

                                                    What is part number for 28amp overload to suit LC1D40U7?

                                                    The part number for 28amp overload to suit is a LRD3353.

                                                    Does LC1D65AB7 3P (3 NO) TeSys Model D contactor have a normally opened and normally closed auxiliary contact?

                                                    What is the code for a spare 240V coil for a LC1D40A contact (replacement for LC1D40AU7)?

                                                    The code for a spare coil is LXD3U7
                                                     

                                                    What do the LA4D timing modules require for mounting on LC1D40A through LC1D65A contactors?

                                                    Product Line:
                                                     
                                                    Tesys D line Contactors and Accessories

                                                    Resolution:
                                                     
                                                    Mounting this module to TeSys LC1D40A through LC1D65A contactor requires the use of the LAD4BB3 wiring adaptor. This adaptor can be fitted only to contactors with no coil suppressor.
                                                     

                                                    What is the overload for LC1D65AU7 Contactor, when rating is 20-25A ?

                                                    17-25 Amps = LRD325
                                                    23-32 Amps =LRD332

                                                    What is the heat dissipated by the LC1D09 contactor?

                                                    Issue:
                                                    Contactors dissipate heat

                                                    Product Line:
                                                    Tesys D Contactors

                                                    Environment:
                                                    IEC Contactors and Starters

                                                    Resolution:
                                                    Total heat dissipation is 3.60 watts maximum; .20 watts dissipated across each power pole and 2 to 3 watts dissipated by the AC control coil.


                                                     

                                                    What is the replacement 230V contactor/ coil for LC1D4011?

                                                    The LC1D4011 contactor/ coil was replaced with LC1D40AU7.

                                                    For futher informaion please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=LC1D40AU7

                                                    https://www.elektro4000.de/images/product_images/popup_images/Schneider-Electric-Leistungsschuetz-LC1D40AU7-388576_0.jpg

                                                    What is the part number for a replacement contactor for LC1-D5011U5?

                                                    The part number for a replacement contactor for LC1-D5011U5 is - LC1D50AU7

                                                    For further information , visit link below:-
                                                    https://www.schneider-electric.com.au/en/search/LC1D50AU7+
                                                    User-added image

                                                    What does the T indicate in the LC1DT contactor catalog number?

                                                    Issue:
                                                    LC1D with T suffix

                                                    Product Line:
                                                     Tesys D line Contactors

                                                    Environment:
                                                    North American Products

                                                    Resolution:
                                                     The T indicates that the device is a 4 pole, all normally open, and has resisitive contact (AC-1) ratings.

                                                    What are the coil voltage codes for the LC1D115 / LC2D115 and LC1D150 / LC2D150 TeSys contactor?

                                                    Product Line:
                                                     
                                                    Tesys D line Contactors
                                                     
                                                    Resolution:
                                                     
                                                    The following list the more common voltage suffix codes for these product lines.  For a more comprehensive list and to determine compatibility with a given product, refer to the catalog below.

                                                    Note 1: LC1D150 contactors are only available with *7 coil codes.
                                                    Note 2: Coil Code ending number represents frequency rating as follows:
                                                    5 = 50 Hertz
                                                    6 = 60 Hertz
                                                    7 = 50/60 Hertz

                                                    AC Volts ___Code                DC Volts ___Code
                                                    24 ___ B5 or B6 or B7          12 ___ Not Avail.        
                                                    42 ___ D5 or D7                   24 ___ BD
                                                    48 ___ E5 or E6 or E7          36 ___ CD
                                                    110 ___ F5 or F6 or F7         48 ___ ED
                                                    115 ___ FE5 or FE7             60 ___ ND
                                                    120 ___ G6 or G7                72 ___ SD
                                                    127 ___ FC5 or FC7            110 ___ FD
                                                    208 ___ L6 or LE7               125 ___ GD
                                                    220 ___ M5 or M6 or M7       220 ___ MD
                                                    230 ___ P5 or P7                 250 ___ UD
                                                    240 ___ U5 or U6 or U7        440 ___ RD
                                                    277 ___ W6 or UE7                
                                                    380 ___ Q5 or Q6 or Q7                
                                                    400 ___ V5 or V7                
                                                    415 ___ N5 or N7                
                                                    440 ___ R5 or R6 or R7                
                                                    480 ___ T6 or T7                
                                                    500 ___ S5 or S7                


                                                     

                                                    What is the part number for 60A contactor with 240V/415V coil?

                                                    What is the difference between a LC1D65A3U7 and LC1D65AU7?

                                                    The difference between the LC1D65A3U7 and the LC1D65AU7 is that the Control connections are spring terminals for the LC1D65A3U7 and screw clamp terminals for the LC1D65AU7
                                                    see data sheets for comparrisons...
                                                    https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=lc1d65a3u7

                                                    https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=lc1d65au7
                                                    User-added image.................User-added image

                                                    Will the LR3D325 overload relay fit a LC1D65G7 contactor?

                                                    Issue:
                                                    Will the LC1D65G7 mount to the LR3D325 overload relay?

                                                    Product Line:
                                                    IEC contactors and starters

                                                    Environment:
                                                    Products sold and used in the United States

                                                    Cause:
                                                    Identifying product compatibility

                                                    Resolution:
                                                    No, the LR3D325 is a overload relay with Everlink termination and will direct mount only to the LC1D40A to LC1D65A contactors.


                                                    CTA-ID : 2050461

                                                    Does the 150A IEC contactor LC1D150BD with a 24 volt DC coil have a coil suppressor built in?

                                                    Issue: 
                                                    Does the LC1D150 with a DC coil include suppression? 

                                                    Product Line:
                                                     Tesys D line contactors and accessories

                                                    Environment:
                                                    Products sold and used in the United States
                                                     
                                                    Cause:
                                                     Identifying components and accessories
                                                     
                                                    Resolution:
                                                     
                                                    Yes. Suppression is built into the 150A DC contactor coil.
                                                     
                                                    Show More