Product name
TeSys D Green
Product or component type
contactor
Contactor application
resistive loadmotor control
Pole contact composition
3 NO
[Ue] rated operational voltage
power circuit: <= 690 V AC 25...400 Hz
[Ie] rated operational current
80 A (at <60 °C) at <= 440 V AC-1 for power circuit50 A (at <60 °C) at <= 440 V AC-3 for power circuit
Motor power kW
15 kW at 220...230 V AC 50 Hz (AC-3)22 kW at 380...400 V AC 50 Hz (AC-3)25 kW at 415 V AC 50 Hz (AC-3)30 kW at 440 V AC 50 Hz (AC-3)30 kW at 500 V AC 50 Hz (AC-3)33 kW at 660...690 V AC 50 Hz (AC-3)
Motor power hp
3 hp at 115 V AC 60 Hz for 1 phase motors7.5 hp at 230/240 V AC 60 Hz for 1 phase motors15 hp at 200/208 V AC 60 Hz for 3 phases motors15 hp at 230/240 V AC 60 Hz for 3 phases motors40 hp at 460/480 V AC 60 Hz for 3 phases motors40 hp at 575/600 V AC 60 Hz for 3 phases motors
Control circuit type
AC/DC at 50/60 Hz AC/DC electronic
[Uc] control circuit voltage
48...130 V AC 50/60 Hz48...130 V DC
Coil type
AC/DC electronic
Auxiliary contact composition
1 NO + 1 NC
[Uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947
[Ith] conventional free air thermal current
80 A (at 60 °C) for power circuit10 A (at 60 °C) for signalling circuit
Irms rated making capacity
900 A at 440 V for power circuit conforming to IEC 60947140 A AC for signalling circuit conforming to IEC 60947-5-1250 A DC for signalling circuit conforming to IEC 60947-5-1
Rated breaking capacity
900 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current
100 A - 1 s for signalling circuit120 A - 500 ms for signalling circuit140 A - 100 ms for signalling circuit84 A 40 °C - 10 min for power circuit208 A 40 °C - 1 min for power circuit400 A 40 °C - 10 s for power circuit810 A 40 °C - 1 s for power circuit
Associated fuse rating
10 A gG for signalling circuit conforming to IEC 60947-5-1100 A gG at <= 690 V coordination type 1 for power circuit100 A gG at <= 690 V coordination type 2 for power circuit
Average impedance
1.5 mOhm - Ith 80 A 50 Hz for power circuit
[Ui] rated insulation voltage
power circuit: 690 V conforming to IEC 60947-4-1signalling circuit: 690 V conforming to IEC 60947-1
Electrical durability
1.8 Mcycles 42 A AC-3 at Ue <= 440 V0.5 Mcycles 80 A AC-1 at Ue <= 440 V
Power dissipation per pole
Standards
EN/IEC 60947-4-1EN/IEC 60947-5-1UL 60947-4-1CSA C22.2 No 60947-4-1
Product certifications
CCCCSAEACULKCDNV-GLLROS (Lloyds register of shipping)
Connections - terminals
control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable endcontrol circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable endcontrol circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable endcontrol circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable endcontrol circuit: screw clamp terminals 1 cable(s) 1-4 mm²solidcontrol circuit: screw clamp terminals 2 cable(s) 1-4 mm²solidpower circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²flexible without cable endpower circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²flexible with cable endpower circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²solidpower circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²flexible without cable endpower circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²flexible with cable endpower circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²solid
Tightening torque
control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mmcontrol circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2power circuit: 8 N.m - on EverLink BTR screw connectors - cable 25-35 mm² hexagonal screw head 4 mmpower circuit: 5 N.m - on EverLink BTR screw connectors - cable 1-25 mm² hexagonal screw head 4 mm
Operating time
55...65 ms closing20...120 ms opening (date code >= 17221)20...80 ms opening (date code >= 18011)
Safety reliability level
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical durability
6 Mcycles
Maximum operating rate
3600 cyc/h 60 °C
Coil technology
built-in bidirectional peak limiting
Control circuit voltage limits
<= 0.1 Uc 60-60 °C drop-out0.85...1.1 Uc 60-60 °C operational
Inrush power in VA
23-23 VA 50/60 Hz (at 20 °C)
Inrush power in W
19-19 W at 20 °C
Hold-in power consumption in VA
1.4-1.4 VA (at 20 °C) 50/60 Hz
Hold-in power consumption in W
0.9-0.9 W at 20 °C
Heat dissipation
0.9-0.9 W at 50/60 Hz
Auxiliary contacts type
type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1 type mirror contact 1 NC conforming to IEC 60947-4-1
Signalling circuit frequency
25...400 Hz
Minimum switching current
5 mA for signalling circuit
Minimum switching voltage
17 V for signalling circuit
Non-overlap time
1.5 ms on de-energisation between NC and NO contact1.5 ms on energisation between NC and NO contact
Insulation resistance
> 10 MOhm for signalling circuit
IP degree of protection
IP20 front face conforming to IEC 60529
Protective treatment
TH conforming to IEC 60068-2-30
Ambient air temperature for operation
-25-60 °C
Ambient air temperature for storage
-60-80 °C
Permissible ambient air temperature around the device
-40-70 °C at Uc
Operating altitude
3000 m without
Fire resistance
850 °C conforming to IEC 60695-2-1
Flame retardance
V1 conforming to UL 94
Mechanical robustness
vibrations contactor open: 2 Gn, 5...300 Hzvibrations contactor closed: 4 Gn, 5...300 Hzshocks contactor open: 10 Gn for 11 msshocks contactor closed: 15 Gn for 11 ms
Sustainable offer status
Green Premium product
REACh Regulation
Free of Substances of Very High Concern above the threshold
EU RoHS Directive
Compliant
RoHS exemption information
Yes
China RoHS Regulation
Product out of China RoHS scope. Substance declaration for your information
Environmental Disclosure
ENVPEP1607010EN
Circularity Profile
ENVEOLI1607010EN
WEEE
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins