TeSys D contactor-3P-AC3 440V 40A 48-130V ACDC coil

TeSys D Contactor-3 Pole AC3 <= 440V 40A, 48 - 130V ACDC Coil

Catalogue Number: LC1D40AEHE
TeSys D contactor-3P-AC3 440V 40A 48-130V ACDC coil
Retail
$1,720.19
RRP (Inc. GST)

Specifications

hide show
Range of product
TeSys D
Range
TeSys
Product name
TeSys D Green
Product or component type
contactor
Device short name
LC1D
Contactor application
  • motor control
  • resistive load
    • Utilisation category
    • AC-3
    • AC-1
      • Poles description
        3P
        Pole contact composition
        3 NO
        [Ue] rated operational voltage
        power circuit: <= 690 V AC 25...400 Hz
        [Ie] rated operational current
      • 60 A (at <60 °C) at <= 440 V AC-1 for power circuit
      • 40 A (at <60 °C) at <= 440 V AC-3 for power circuit
        • Motor power kW
        • 11 kW at 220...230 V AC 50 Hz (AC-3)
        • 18.5 kW at 380...400 V AC 50 Hz (AC-3)
        • 22 kW at 415 V AC 50 Hz (AC-3)
        • 22 kW at 440 V AC 50 Hz (AC-3)
        • 22 kW at 500 V AC 50 Hz (AC-3)
        • 30 kW at 660...690 V AC 50 Hz (AC-3)
          • Motor power hp
          • 3 hp at 115 V AC 60 Hz for 1 phase motors
          • 5 hp at 230/240 V AC 60 Hz for 1 phase motors
          • 10 hp at 200/208 V AC 60 Hz for 3 phases motors
          • 10 hp at 230/240 V AC 60 Hz for 3 phases motors
          • 30 hp at 460/480 V AC 60 Hz for 3 phases motors
          • 30 hp at 575/600 V AC 60 Hz for 3 phases motors
            • Control circuit type
              AC/DC at 50/60 Hz AC/DC electronic
              [Uc] control circuit voltage
            • 48...130 V AC 50/60 Hz
            • 48...130 V DC
              • Coil type
                AC/DC electronic
                Auxiliary contact composition
                1 NO + 1 NC
                [Uimp] rated impulse withstand voltage
                6 kV conforming to IEC 60947
                Overvoltage category
                III
                [Ith] conventional free air thermal current
              • 60 A (at 60 °C) for power circuit
              • 10 A (at 60 °C) for signalling circuit
                • Irms rated making capacity
                • 800 A at 440 V for power circuit conforming to IEC 60947
                • 140 A AC for signalling circuit conforming to IEC 60947-5-1
                • 250 A DC for signalling circuit conforming to IEC 60947-5-1
                  • Rated breaking capacity
                    800 A at 440 V for power circuit conforming to IEC 60947
                    [Icw] rated short-time withstand current
                  • 72 A 40 °C - 10 min for power circuit
                  • 165 A 40 °C - 1 min for power circuit
                  • 320 A 40 °C - 10 s for power circuit
                  • 720 A 40 °C - 1 s for power circuit
                  • 100 A - 1 s for signalling circuit
                  • 120 A - 500 ms for signalling circuit
                  • 140 A - 100 ms for signalling circuit
                    • Associated fuse rating
                    • 80 A gG at <= 690 V coordination type 1 for power circuit
                    • 80 A gG at <= 690 V coordination type 2 for power circuit
                    • 10 A gG for signalling circuit conforming to IEC 60947-5-1
                      • Average impedance
                        1.5 mOhm - Ith 60 A 50 Hz for power circuit
                        [Ui] rated insulation voltage
                      • power circuit: 690 V conforming to IEC 60947-4-1
                      • signalling circuit: 690 V conforming to IEC 60947-1
                        • Electrical durability
                        • 2 Mcycles 35 A AC-3 at Ue <= 440 V
                        • 0.7 Mcycles 60 A AC-1 at Ue <= 440 V
                          • Power dissipation per pole
                          • 5.4 W AC-1
                          • 2.4 W AC-3
                            • Protective cover
                              with
                              Mounting support
                            • plate
                            • rail
                              • Standards
                              • EN/IEC 60947-4-1
                              • EN/IEC 60947-5-1
                              • UL 60947-4-1
                              • CSA C22.2 No 60947-4-1
                                • Product certifications
                                • CCC
                                • CSA
                                • EAC
                                • UL
                                • KC
                                • DNV-GL
                                • LROS (Lloyds register of shipping)
                                  • Connections - terminals
                                  • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
                                  • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
                                  • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
                                  • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
                                  • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid
                                  • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid
                                  • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²flexible without cable end
                                  • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²flexible with cable end
                                  • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²solid
                                  • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²flexible without cable end
                                  • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²flexible with cable end
                                  • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²solid
                                    • Tightening torque
                                    • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                                    • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
                                    • power circuit: 8 N.m - on EverLink BTR screw connectors - cable 25-35 mm² hexagonal screw head 4 mm
                                    • power circuit: 5 N.m - on EverLink BTR screw connectors - cable 1-25 mm² hexagonal screw head 4 mm
                                      • Operating time
                                      • 55...65 ms closing
                                      • 20...120 ms opening (date code >= 17221)
                                      • 20...80 ms opening (date code >= 18011)
                                        • Safety reliability level
                                        • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                                        • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                                          • Mechanical durability
                                            6 Mcycles
                                            Maximum operating rate
                                            3600 cyc/h 60 °C
                                            Coil technology
                                            built-in bidirectional peak limiting
                                            Control circuit voltage limits
                                          • <= 0.1 Uc 60-60 °C drop-out
                                          • 0.85...1.1 Uc 60-60 °C operational
                                            • Inrush power in VA
                                              23-23 VA 50/60 Hz (at 20 °C)
                                              Inrush power in W
                                              19-19 W at 20 °C
                                              Hold-in power consumption in VA
                                              1.4-1.4 VA (at 20 °C) 50/60 Hz
                                              Hold-in power consumption in W
                                              0.9-0.9 W at 20 °C
                                              Heat dissipation
                                              0.9-0.9 W at 50/60 Hz
                                              Auxiliary contacts type
                                            • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
                                            • type mirror contact 1 NC conforming to IEC 60947-4-1
                                              • Signalling circuit frequency
                                                25...400 Hz
                                                Minimum switching current
                                                5 mA for signalling circuit
                                                Minimum switching voltage
                                                17 V for signalling circuit
                                                Non-overlap time
                                              • 1.5 ms on de-energisation between NC and NO contact
                                              • 1.5 ms on energisation between NC and NO contact
                                                • Insulation resistance
                                                  > 10 MOhm for signalling circuit
                                                  Compatibility code
                                                  LC1D
                                                  IP degree of protection
                                                  IP20 front face conforming to IEC 60529
                                                  Protective treatment
                                                  TH conforming to IEC 60068-2-30
                                                  Pollution degree
                                                  3
                                                  Ambient air temperature for operation
                                                  -25-60 °C
                                                  Ambient air temperature for storage
                                                  -60-80 °C
                                                  Permissible ambient air temperature around the device
                                                  -40-70 °C at Uc
                                                  Operating altitude
                                                  3000 m without
                                                  Fire resistance
                                                  850 °C conforming to IEC 60695-2-1
                                                  Flame retardance
                                                  V1 conforming to UL 94
                                                  Mechanical robustness
                                                • vibrations contactor open: 2 Gn, 5...300 Hz
                                                • vibrations contactor closed: 4 Gn, 5...300 Hz
                                                • shocks contactor open: 10 Gn for 11 ms
                                                • shocks contactor closed: 15 Gn for 11 ms
                                                  • Height
                                                    122 mm
                                                    Width
                                                    55 mm
                                                    Depth
                                                    120 mm
                                                    Net weight
                                                    0.992 kg
                                                    Sustainable offer status
                                                    Green Premium product
                                                    EU RoHS Directive
                                                    Compliant
                                                    Mercury free
                                                    Yes
                                                    RoHS exemption information
                                                    Yes
                                                    China RoHS Regulation
                                                    Product out of China RoHS scope. Substance declaration for your information
                                                    Environmental Disclosure
                                                    ENVPEP1607010EN
                                                    Circularity Profile
                                                    ENVEOLI1607010EN
                                                    WEEE
                                                    The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                                                    Halogen content performance
                                                    Halogen free plastic parts & cables product
                                                    Warranty
                                                    18 months

                                                    Documents & downloads

                                                    hide show
                                                    Filter items
                                                    • All

                                                    • Product Brochures

                                                    • CAD Files and Packs

                                                    • Technical Data Catalogues

                                                    • End of Life Manual

                                                    • Product Environmental

                                                    • Installation Instruction

                                                    • Data Bulletin

                                                    • Declaration of Conformity

                                                    Frequently Asked Questions

                                                    hide show

                                                    Do the Everlink reversing contactors come with electrical interlocking?

                                                    Issue:
                                                    Looking for electrical interlock kit for the LC1D65A Everlnk contactors

                                                    Product line:
                                                    Tesys D LC1D40A, LC1D50A, LC1D65A

                                                    Environment:
                                                    Everlink, all voltage codes

                                                    Cause:
                                                    Old D2 version offered an electrical interlock kit

                                                    Resolution:
                                                    The current Everlink version does not offer an electrical interlock kit.  The customer can wire electrical interlocking using the normally closed contacts provided on the contactor.

                                                    What is the code for a 40A 110VAC contactor ?

                                                    LC1D40AF7

                                                    What is the power terminal lug data for the LC1D40, LC1D50, LC1D65, LP1D40, LP1D50, and LP1D65 contactor?

                                                    Issue:
                                                    Identifying power terminal lug data for the D2 style contactors

                                                    Product Line:
                                                    Tesys D line contactors

                                                    Environment:
                                                    Products sold and used in the United States

                                                    Cause:
                                                    Power terminal lug data required

                                                    Resolution:
                                                    For contactors with screw clamp terminals:
                                                    stranded cable w/o cable end : One #10-3 AWG or Two #10-4 AWG per terminal.
                                                    stranded cable w/cable end: One #10-4 AWG or Two #12-2 AWG per terminal.
                                                    solid cable: One #10-3 AWG or Two #10-6 AWG per terminal.

                                                    Can I use a LA9D6569 reversing kit with LC1D40AU7 contactors

                                                    No, correct kit is a LAD9R3.

                                                    What is the altitude derating for a TeSys D-Line contactor?

                                                    Issue:​
                                                    What is the altitude derating for a TeSys D-Line contactor?

                                                    Product Line:
                                                    Digest 177 Section 18 : Contactors and Starters, IEC

                                                    Environment:
                                                    North American Products

                                                    Resolution:
                                                    The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

                                                    Voltage
                                                    3500m x 0.90
                                                    4000m x 0.80
                                                    4500m x 0.70
                                                    5000m x 0.60

                                                    Current
                                                    3500m x 0.92
                                                    4000m x 0.90
                                                    4500m x 0.88
                                                    5000m x 0.86

                                                    For example, an LC1D80 at 5000 meters:
                                                    - The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
                                                    - The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



                                                     

                                                    What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

                                                    Issue:
                                                    Identifying maximum voltage of an LC1D contactor

                                                    Product Line:
                                                    TeSys D Contactors

                                                    Environment:
                                                    IEC contactors and starters used in North America

                                                    Cause:
                                                    n/a

                                                    Resolution:
                                                    IThe maximum voltage per UL and CSA is 600VAC. 
                                                     

                                                    Is there a retrofit plate available for replacement of LC1D40-D65 contactors with the LC1D40A-65A contactors?

                                                    Use a LAD7X3 retrofit plate.


                                                    CTA-ID : 2053453

                                                    What is the code for the newer version of the LC1D40U7

                                                    That has been replaced with the Everlink LC1D40AU7

                                                    Looking for a LC1D50A.. with a 240v coil

                                                     Part code is LC1D50AU7

                                                    What is the code for a spare 240V coil for a LC1D40A contact (replacement for LC1D40AU7)?

                                                    The code for a spare coil is LXD3U7
                                                     

                                                    What is difference between LC1D50U7 and LC1D50AU7?

                                                    Following are the differences between the LC1D50U7 and the LC1D50AU7:

                                                    LC1D50AU7 has everlink terminals.
                                                    LC1D50AU7....is slightly larger case and accommodate LRD3XX overloads
                                                    Whereas
                                                    LC1D50U7 contactors accommodate LRD33XX overloads.

                                                     

                                                    What are the dimensions of LC1D40AB7 ?

                                                    Height 122 mm
                                                    Width 55 mm
                                                    Depth 120 mm
                                                    Product weight 1.4 kg
                                                    Show More