Quantcast

TeSys D Contactor-3 Pole AC3 <= 440V 40A, 24 - 60V ACDC Coil

TeSys D Contactor-3 Pole AC3 <= 440V 40A, 24 - 60V ACDC Coil

TeSys D Contactor-3 Pole AC3 <= 440V 40A, 24 - 60V ACDC Coil

Item Number: LC1D40ABNE

Retail
$1,720.19
RRP (Inc. GST)

Product Dimensions

Width icon

Width55 mm

Height icon

Height122 mm

Depth icon

Depth120 mm

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

TeSys D

Range

TeSys

Product or component type

contactor

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

[Ue] rated operational voltage

power circuit: <= 690 V AC 25...400 Hz

[Ie] rated operational current

  • 60 A (at <60 °C) at <= 440 V AC-1 for power circuit
  • 40 A (at <60 °C) at <= 440 V AC-3 for power circuit
    • Electrical durability

    • 2 Mcycles 35 A AC-3 at Ue <= 440 V
    • 0.7 Mcycles 60 A AC-1 at Ue <= 440 V
      • Mounting support

      • plate
      • rail
        • Standards

        • EN/IEC 60947-4-1
        • EN/IEC 60947-5-1
        • UL 60947-4-1
        • CSA C22.2 No 60947-4-1
          • Product certifications

          • CCC
          • CSA
          • EAC
          • UL
          • KC
          • DNV-GL
          • LROS (Lloyds register of shipping)
            • Connections - terminals

            • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
            • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
            • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
            • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
            • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid
            • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid
            • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²flexible without cable end
            • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²flexible with cable end
            • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²solid
            • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²flexible without cable end
            • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²flexible with cable end
            • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²solid
              • Mechanical durability

                6 Mcycles

                Insulation resistance

                > 10 MOhm for signalling circuit

                IP degree of protection

                IP20 front face conforming to IEC 60529

                Ambient air temperature for operation

              • -40-60 °C
              • 60-70 °C with derating
                • Ambient air temperature for storage

                  -60-80 °C

                  Height

                  122 mm

                  Width

                  55 mm

                  Depth

                  120 mm

                  Net weight

                  0.992 kg

                  REACh Regulation

                  Free of Substances of Very High Concern above the threshold

                  EU RoHS Directive

                  Compliant

                  Mercury free

                  Yes

                  RoHS exemption information

                  Yes

                  China RoHS Regulation

                  Product out of China RoHS scope. Substance declaration for your information

                  Environmental Disclosure

                  ENVPEP1607010EN

                  Circularity Profile

                  ENVEOLI1607010EN

                  Others

                  Product name

                  TeSys D Green

                  Device short name

                  LC1D

                  Contactor application

                • resistive load
                • motor control
                  • Utilisation category

                  • AC-3
                  • AC-1
                    • Poles description

                      3P

                      Pole contact composition

                      3 NO

                      Motor power kW

                    • 11 kW at 220...230 V AC 50 Hz (AC-3)
                    • 18.5 kW at 380...400 V AC 50 Hz (AC-3)
                    • 22 kW at 415 V AC 50 Hz (AC-3)
                    • 22 kW at 440 V AC 50 Hz (AC-3)
                    • 22 kW at 500 V AC 50 Hz (AC-3)
                    • 30 kW at 660...690 V AC 50 Hz (AC-3)
                      • Motor power hp

                      • 3 hp at 115 V AC 60 Hz for 1 phase motors
                      • 5 hp at 230/240 V AC 60 Hz for 1 phase motors
                      • 10 hp at 200/208 V AC 60 Hz for 3 phases motors
                      • 10 hp at 230/240 V AC 60 Hz for 3 phases motors
                      • 30 hp at 460/480 V AC 60 Hz for 3 phases motors
                      • 30 hp at 575/600 V AC 60 Hz for 3 phases motors
                        • Control circuit type

                          AC/DC at 50/60 Hz AC/DC electronic

                          [Uc] control circuit voltage

                        • 24...60 V AC 50/60 Hz
                        • 24...60 V DC
                          • Coil type

                            AC/DC electronic

                            Auxiliary contact composition

                            1 NO + 1 NC

                            [Uimp] rated impulse withstand voltage

                            6 kV conforming to IEC 60947

                            Overvoltage category

                            III

                            [Ith] conventional free air thermal current

                          • 60 A (at 60 °C) for power circuit
                          • 10 A (at 60 °C) for signalling circuit
                            • Irms rated making capacity

                            • 800 A at 440 V for power circuit conforming to IEC 60947
                            • 140 A AC for signalling circuit conforming to IEC 60947-5-1
                            • 250 A DC for signalling circuit conforming to IEC 60947-5-1
                              • Rated breaking capacity

                                800 A at 440 V for power circuit conforming to IEC 60947

                                [Icw] rated short-time withstand current

                              • 72 A 40 °C - 10 min for power circuit
                              • 165 A 40 °C - 1 min for power circuit
                              • 320 A 40 °C - 10 s for power circuit
                              • 720 A 40 °C - 1 s for power circuit
                              • 100 A - 1 s for signalling circuit
                              • 120 A - 500 ms for signalling circuit
                              • 140 A - 100 ms for signalling circuit
                                • Associated fuse rating

                                • 80 A gG at <= 690 V coordination type 1 for power circuit
                                • 80 A gG at <= 690 V coordination type 2 for power circuit
                                • 10 A gG for signalling circuit conforming to IEC 60947-5-1
                                  • Average impedance

                                    1.5 mOhm - Ith 60 A 50 Hz for power circuit

                                    [Ui] rated insulation voltage

                                  • power circuit: 690 V conforming to IEC 60947-4-1
                                  • signalling circuit: 690 V conforming to IEC 60947-1
                                    • Power dissipation per pole

                                    • 5.4 W AC-1
                                    • 2.4 W AC-3
                                      • Protective cover

                                        with

                                        Tightening torque

                                      • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                                      • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
                                      • power circuit: 8 N.m - on EverLink BTR screw connectors - cable 25-35 mm² hexagonal screw head 4 mm
                                      • power circuit: 5 N.m - on EverLink BTR screw connectors - cable 1-25 mm² hexagonal screw head 4 mm
                                        • Operating time

                                        • 55...65 ms closing
                                        • 20...120 ms opening (date code >= 17221)
                                        • 20...80 ms opening (date code >= 18011)
                                          • Safety reliability level

                                          • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                                          • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                                            • Maximum operating rate

                                              3600 cyc/h 60 °C

                                              Coil technology

                                              built-in bidirectional peak limiting

                                              Control circuit voltage limits

                                            • <= 0.1 Uc (-40-70 °C):drop-out AC/DC
                                            • 0.85...1.1 Uc (-40-60 °C):operational AC
                                            • 0.8...1.1 Uc (-40-60 °C):operational DC
                                            • 1...1.1 Uc (60-70 °C):operational AC/DC
                                              • Inrush power in VA

                                                15-15 VA 50/60 Hz (at 20 °C)

                                                Inrush power in W

                                                16-16 W at 20 °C

                                                Hold-in power consumption in VA

                                                1-1 VA (at 20 °C) 50/60 Hz

                                                Hold-in power consumption in W

                                                0.7-0.7 W at 20 °C

                                                Heat dissipation

                                                0.7-0.7 W at 50/60 Hz

                                                Auxiliary contacts type

                                              • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
                                              • type mirror contact 1 NC conforming to IEC 60947-4-1
                                                • Signalling circuit frequency

                                                  25...400 Hz

                                                  Minimum switching current

                                                  5 mA for signalling circuit

                                                  Minimum switching voltage

                                                  17 V for signalling circuit

                                                  Non-overlap time

                                                • 1.5 ms on de-energisation between NC and NO contact
                                                • 1.5 ms on energisation between NC and NO contact
                                                  • Compatibility code

                                                    LC1D

                                                    Protective treatment

                                                    TH conforming to IEC 60068-2-30

                                                    Pollution degree

                                                    3

                                                    Operating altitude

                                                    0...3000 m

                                                    Fire resistance

                                                    850 °C conforming to IEC 60695-2-1

                                                    Flame retardance

                                                    V1 conforming to UL 94

                                                    Mechanical robustness

                                                  • vibrations contactor open: 2 Gn, 5...300 Hz
                                                  • vibrations contactor closed: 4 Gn, 5...300 Hz
                                                  • shocks contactor open: 10 Gn for 11 ms
                                                  • shocks contactor closed: 15 Gn for 11 ms
                                                    • Unit Type of Package 1

                                                      PCE

                                                      Number of Units in Package 1

                                                      1

                                                      Package 1 Weight

                                                      1.062 kg

                                                      Package 1 Height

                                                      6.2 cm

                                                      Package 1 width

                                                      13.7 cm

                                                      Package 1 Length

                                                      15.2 cm

                                                      Unit Type of Package 2

                                                      S02

                                                      Number of Units in Package 2

                                                      9

                                                      Package 2 Weight

                                                      9.934 kg

                                                      Package 2 Height

                                                      15 cm

                                                      Package 2 width

                                                      30 cm

                                                      Package 2 Length

                                                      40 cm

                                                      WEEE

                                                      The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

                                                      Halogen content performance

                                                      Halogen free plastic parts & cables product
                                                      Show all specifications

                                                      Documents & downloads

                                                      hide show
                                                      Filter items
                                                      • All

                                                      • Product Brochures

                                                      • CAD Files and Packs

                                                      • Technical Data Catalogues

                                                      • Product Environmental

                                                      • End of Life Manual

                                                      • Installation Instruction

                                                      • Data Bulletin

                                                      • Declaration of Conformity

                                                      Frequently Asked Questions

                                                      hide show

                                                      What is the power terminal lug data for the LC1D40, LC1D50, LC1D65, LP1D40, LP1D50, and LP1D65 contactor?

                                                      Issue:
                                                      Identifying power terminal lug data for the D2 style contactors

                                                      Product Line:
                                                      IEC Contactors and Starters

                                                      Environment:
                                                      Tesys D line contactors

                                                      Cause:
                                                      Power terminal lug data required

                                                      Resolution:
                                                      For contactors with screw clamp terminals:
                                                      stranded cable w/o cable end : One #10-3 AWG or Two #10-4 AWG per terminal.
                                                      stranded cable w/cable end: One #10-4 AWG or Two #12-2 AWG per terminal.
                                                      solid cable: One #10-3 AWG or Two #10-6 AWG per terminal.

                                                      What is the code for a spare 24VDC coil for a LC1D50A contactor ?

                                                      There are no spare DC coils available for the 40A...65A contactors.

                                                      The equivalent will be to order a complete LC1D50ABD.

                                                      Can the single pole LA1DN and LADN auxiliary contact module be mounted on the TeSys contactors?

                                                      ISSUE
                                                      In which contactors can the LA1DN and LADN auxiliary contacts be mounted?

                                                      PRODUCT LINE
                                                      Auxiliary contacts for the Tesys D line

                                                      ENVIRONMENT
                                                      Tesys D-Line and Tesys F

                                                      RESOLUTION
                                                      These contacts will only fit on the following contactors:
                                                      Front mount only for LC1D40 through LC1D115 devices and LC1D40A - LC1D65A.
                                                      Left side mount only to LC1F contactors

                                                      What is the code for a 415VAC coil for a LC1D40A Contactor?

                                                      The 415V coil is LXD3N7