Number of Units in Package 1
1
Number of Units in Package 2
20
Package 2 Weight
8.597 kg
Unit Type of Package 1
PCE
Unit Type of Package 2
S02
WEEE
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Contactor application
motor controlresistive load
Pole contact composition
3 NO
Motor power kW
18.5 kW at 500 V AC 50/60 Hz (AC-3)18.5 kW at 660...690 V AC 50/60 Hz (AC-3)7.5 kW at 400 V AC 50/60 Hz (AC-4)18.5 kW at 380...400 V AC 50/60 Hz (AC-3)9 kW at 220...230 V AC 50/60 Hz (AC-3)18.5 kW at 415...440 V AC 50/60 Hz (AC-3)
Motor power hp
10 hp at 230/240 V AC 50/60 Hz for 3 phases motors10 hp at 200/208 V AC 50/60 Hz for 3 phases motors5 hp at 240 V AC 50/60 Hz for 1 phase motors20 hp at 480 V AC 50/60 Hz for 3 phases motors25 hp at 600 V AC 50/60 Hz for 3 phases motors
Control circuit type
AC at 50/60 Hz
[Uc] control circuit voltage
380 V AC 50/60 Hz
Auxiliary contact composition
1 NO + 1 NC
[Uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947
[Ith] conventional free air thermal current
10 A (at 60 °C) for signalling circuit50 A (at 60 °C) for power circuit
Irms rated making capacity
140 A AC for signalling circuit conforming to IEC 60947-5-1250 A DC for signalling circuit conforming to IEC 60947-5-1550 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity
550 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current
60 A 40 °C - 10 min for power circuit430 A 40 °C - 1 s for power circuit150 A 40 °C - 1 min for power circuit310 A 40 °C - 10 s for power circuit100 A - 1 s for signalling circuit120 A - 500 ms for signalling circuit140 A - 100 ms for signalling circuit
Associated fuse rating
10 A gG for signalling circuit conforming to IEC 60947-5-163 A gG at <= 690 V coordination type 1 for power circuit63 A gG at <= 690 V coordination type 2 for power circuit
Average impedance
2 mOhm - Ith 50 A 50 Hz for power circuit
[Ui] rated insulation voltage
power circuit: 600 V CSA certifiedpower circuit: 600 V UL certifiedsignalling circuit: 690 V conforming to IEC 60947-1signalling circuit: 600 V CSA certifiedsignalling circuit: 600 V UL certifiedpower circuit: 690 V conforming to IEC 60947-4-1
Power dissipation per pole
Tightening torque
control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mmcontrol circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mmpower circuit: 2.5 N.m - on screw clamp terminals - with screwdriver Philips No 2
Operating time
4...19 ms opening12...22 ms closing
Safety reliability level
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Maximum operating rate
3600 cyc/h 60 °C
Coil technology
without built-in suppressor module
Control circuit voltage limits
0.3...0.6 Uc (-40-70 °C):drop-out AC 50/60 Hz0.8...1.1 Uc (-40-60 °C):operational AC 50 Hz0.85...1.1 Uc (-40-60 °C):operational AC 60 Hz1...1.1 Uc (60-70 °C):operational AC 50/60 Hz
Inrush power in VA
70-70 VA 60 Hz cos phi 0.75 (at 20 °C)70-70 VA 50 Hz cos phi 0.75 (at 20 °C)
Hold-in power consumption in VA
7.5-7.5 VA 60 Hz cos phi 0.3 (at 20 °C)7-7 VA 50 Hz cos phi 0.3 (at 20 °C)
Heat dissipation
2-3 W at 50/60 Hz
Auxiliary contacts type
type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1 type mirror contact 1 NC conforming to IEC 60947-4-1
Signalling circuit frequency
25...400 Hz
Minimum switching current
5 mA for signalling circuit
Minimum switching voltage
17 V for signalling circuit
Non-overlap time
1.5 ms on de-energisation between NC and NO contact1.5 ms on energisation between NC and NO contact
Power range
7-11 kW at 200-240 V 3 phases15-25 kW at 380-440 V 3 phases15-25 kW at 480-500 V 3 phases15-25 kW at 525-690 V 3 phases4-6 kW at 100-120 V 3 phases
Motor starter type
direct on-line contactor
Protective treatment
TH conforming to IEC 60068-2-30
Operating altitude
0...3000 m
Fire resistance
850 °C conforming to IEC 60695-2-1
Flame retardance
V1 conforming to UL 94
Mechanical robustness
vibrations contactor open: 2 Gn, 5...300 Hzvibrations contactor closed: 4 Gn, 5...300 Hzshocks contactor closed: 15 Gn for 11 msshocks contactor open: 8 Gn for 11 ms