TeSys LC1D25 D32 D38 - 3P - DC coil - screw & screw clamp connector

TeSys D Contactor, 3P(3 NO), AC-3, <= 440V, 25A, 110VDC Coil

Catalogue Number: LC1D25FD
TeSys LC1D25 D32 D38 - 3P - DC coil - screw & screw clamp connector
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Range of product
TeSys D
Range
TeSys
Product name
TeSys D
Product or component type
contactor
Device short name
LC1D
Contactor application
  • resistive load
  • motor control
    • Utilisation category
    • AC-3
    • AC-4
    • AC-1
      • Poles description
        3P
        Pole contact composition
        3 NO
        [Ue] rated operational voltage
      • power circuit: <= 690 V AC 25...400 Hz
      • power circuit: <= 300 V DC
        • [Ie] rated operational current
        • 25 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
        • 40 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
          • Motor power kW
          • 5.5 kW at 220...230 V AC 50/60 Hz (AC-3)
          • 11 kW at 380...400 V AC 50/60 Hz (AC-3)
          • 11 kW at 415...440 V AC 50/60 Hz (AC-3)
          • 15 kW at 500 V AC 50/60 Hz (AC-3)
          • 15 kW at 660...690 V AC 50/60 Hz (AC-3)
          • 5.5 kW at 400 V AC 50/60 Hz (AC-4)
            • Motor power hp
            • 3 hp at 230/240 V AC 50/60 Hz for 1 phase motors
            • 2 hp at 115 V AC 50/60 Hz for 1 phase motors
            • 7.5 hp at 230/240 V AC 50/60 Hz for 3 phases motors
            • 15 hp at 460/480 V AC 50/60 Hz for 3 phases motors
            • 20 hp at 575/600 V AC 50/60 Hz for 3 phases motors
            • 7.5 hp at 200/208 V AC 50/60 Hz for 3 phases motors
              • Control circuit type
                DC standard
                [Uc] control circuit voltage
                110 V DC
                Auxiliary contact composition
                1 NO + 1 NC
                [Uimp] rated impulse withstand voltage
                6 kV conforming to IEC 60947
                Overvoltage category
                III
                [Ith] conventional free air thermal current
              • 10 A (at 60 °C) for signalling circuit
              • 40 A (at 60 °C) for power circuit
                • Irms rated making capacity
                • 140 A AC for signalling circuit conforming to IEC 60947-5-1
                • 250 A DC for signalling circuit conforming to IEC 60947-5-1
                • 450 A at 440 V for power circuit conforming to IEC 60947
                  • Rated breaking capacity
                    450 A at 440 V for power circuit conforming to IEC 60947
                    [Icw] rated short-time withstand current
                  • 240 A 40 °C - 10 s for power circuit
                  • 380 A 40 °C - 1 s for power circuit
                  • 50 A 40 °C - 10 min for power circuit
                  • 120 A 40 °C - 1 min for power circuit
                  • 100 A - 1 s for signalling circuit
                  • 120 A - 500 ms for signalling circuit
                  • 140 A - 100 ms for signalling circuit
                    • Associated fuse rating
                    • 10 A gG for signalling circuit conforming to IEC 60947-5-1
                    • 63 A gG at <= 690 V coordination type 1 for power circuit
                    • 40 A gG at <= 690 V coordination type 2 for power circuit
                      • Average impedance
                        2 mOhm - Ith 40 A 50 Hz for power circuit
                        [Ui] rated insulation voltage
                      • power circuit: 690 V conforming to IEC 60947-4-1
                      • power circuit: 600 V CSA certified
                      • power circuit: 600 V UL certified
                      • signalling circuit: 690 V conforming to IEC 60947-1
                      • signalling circuit: 600 V CSA certified
                      • signalling circuit: 600 V UL certified
                        • Electrical durability
                        • 1.65 Mcycles 25 A AC-3 at Ue <= 440 V
                        • 1.4 Mcycles 40 A AC-1 at Ue <= 440 V
                          • Power dissipation per pole
                          • 3.2 W AC-1
                          • 1.25 W AC-3
                            • Protective cover
                              with
                              Mounting support
                            • plate
                            • rail
                              • Standards
                              • CSA C22.2 No 14
                              • EN 60947-4-1
                              • EN 60947-5-1
                              • IEC 60947-4-1
                              • IEC 60947-5-1
                              • UL 508
                                • Product certifications
                                • RINA
                                • DNV
                                • BV
                                • UL
                                • CSA
                                • GL
                                • GOST
                                • CCC
                                • LROS (Lloyds register of shipping)
                                  • Connections - terminals
                                  • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
                                  • power circuit: screw clamp terminals 2 cable(s) 1.5-6 mm²flexible with cable end
                                  • power circuit: screw clamp terminals 1 cable(s) 1.5-10 mm²solid without cable end
                                  • power circuit: screw clamp terminals 2 cable(s) 2.5-10 mm²solid without cable end
                                  • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
                                  • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
                                  • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
                                  • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end
                                  • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end
                                  • power circuit: screw clamp terminals 1 cable(s) 2.5-10 mm²flexible without cable end
                                  • power circuit: screw clamp terminals 2 cable(s) 2.5-10 mm²flexible without cable end
                                  • power circuit: screw clamp terminals 1 cable(s) 1-10 mm²flexible with cable end
                                    • Tightening torque
                                    • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                                    • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
                                    • power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                                    • power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver Philips No 2
                                      • Operating time
                                      • 53.55...72.45 ms closing
                                      • 16...24 ms opening
                                        • Safety reliability level
                                        • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                                        • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                                          • Mechanical durability
                                            30 Mcycles
                                            Maximum operating rate
                                            3600 cyc/h 60 °C
                                            Coil technology
                                            built-in bidirectional peak limiting diode suppressor
                                            Control circuit voltage limits
                                          • drop-out: 0.1...0.25 Uc DC (at 60 °C)
                                          • operational: 0.7...1.25 Uc DC (at 60 °C)
                                            • Time constant
                                              28 ms
                                              Inrush power in W
                                              5.4-5.4 W (at 20 °C)
                                              Hold-in power consumption in W
                                              5.4-5.4 W at 20 °C
                                              Auxiliary contacts type
                                            • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
                                            • type mirror contact 1 NC conforming to IEC 60947-4-1
                                              • Signalling circuit frequency
                                                25...400 Hz
                                                Minimum switching current
                                                5 mA for signalling circuit
                                                Minimum switching voltage
                                                17 V for signalling circuit
                                                Non-overlap time
                                              • 1.5 ms on de-energisation between NC and NO contact
                                              • 1.5 ms on energisation between NC and NO contact
                                                • Insulation resistance
                                                  > 10 MOhm for signalling circuit
                                                  Contact compatibility
                                                  M4
                                                  Compatibility code
                                                  LC1D
                                                  IP degree of protection
                                                  IP20 front face conforming to IEC 60529
                                                  Protective treatment
                                                  TH conforming to IEC 60068-2-30
                                                  Pollution degree
                                                  3
                                                  Ambient air temperature for operation
                                                  -5-60 °C
                                                  Ambient air temperature for storage
                                                  -60-80 °C
                                                  Permissible ambient air temperature around the device
                                                  -40-70 °C at Uc
                                                  Operating altitude
                                                  3000 m without
                                                  Fire resistance
                                                  850 °C conforming to IEC 60695-2-1
                                                  Flame retardance
                                                  V1 conforming to UL 94
                                                  Mechanical robustness
                                                • vibrations contactor open: 2 Gn, 5...300 Hz
                                                • vibrations contactor closed: 4 Gn, 5...300 Hz
                                                • shocks contactor closed: 15 Gn for 11 ms
                                                • shocks contactor open: 8 Gn for 11 ms
                                                  • Height
                                                    85 mm
                                                    Width
                                                    45 mm
                                                    Depth
                                                    101 mm
                                                    Net weight
                                                    0.53 kg
                                                    Sustainable offer status
                                                    Green Premium product
                                                    REACh Regulation
                                                    Free of Substances of Very High Concern above the threshold
                                                    REACh free of SVHC
                                                    Yes
                                                    EU RoHS Directive
                                                    Compliant
                                                    Toxic heavy metal free
                                                    Yes
                                                    Mercury free
                                                    Yes
                                                    RoHS exemption information
                                                    Yes
                                                    China RoHS Regulation
                                                    X
                                                    Environmental Disclosure
                                                    ENVPEP110228EN
                                                    Circularity Profile
                                                    ENVEOLI1102028EN
                                                    WEEE
                                                    The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                                                    California proposition 65
                                                    WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov
                                                    Warranty
                                                    18 months

                                                    Documents & downloads

                                                    hide show
                                                    Filter items
                                                    • All

                                                    • CAD Files and Packs

                                                    • Product Brochures

                                                    • Technical Data Catalogues

                                                    • End of Life Manual

                                                    • Product Environmental

                                                    • Installation Instruction

                                                    • Data Bulletin

                                                    • Certificates (MSDS)

                                                    • Declaration of Conformity

                                                    Frequently Asked Questions

                                                    hide show

                                                    What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

                                                    Issue:
                                                    Identifying maximum voltage of an LC1D contactor

                                                    Product Line:
                                                    TeSys D Contactors

                                                    Environment:
                                                    IEC contactors and starters used in North America

                                                    Cause:
                                                    n/a

                                                    Resolution:
                                                    IThe maximum voltage per UL and CSA is 600VAC. 
                                                     

                                                    What is the altitude derating for a TeSys D-Line contactor?

                                                    Issue:​
                                                    What is the altitude derating for a TeSys D-Line contactor?

                                                    Product Line:
                                                    Digest 177 Section 18 : Contactors and Starters, IEC

                                                    Environment:
                                                    North American Products

                                                    Resolution:
                                                    The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

                                                    Voltage
                                                    3500m x 0.90
                                                    4000m x 0.80
                                                    4500m x 0.70
                                                    5000m x 0.60

                                                    Current
                                                    3500m x 0.92
                                                    4000m x 0.90
                                                    4500m x 0.88
                                                    5000m x 0.86

                                                    For example, an LC1D80 at 5000 meters:
                                                    - The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
                                                    - The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



                                                     

                                                    Where are the control coil terminals for TeSys LC1D09 to LC1D38 contactor?

                                                    Issue:
                                                    Determine the control coil terminal marking and location on LC1D09 to LC1D38 contactor

                                                    Product Line: 
                                                    Tesys D Contactors

                                                    Environment:
                                                    IEC contactors

                                                    Resolution:
                                                    The coil terminals are marked A1 and A2, you can see them on the front of the contactor on the white part (control section).  They are next to the auxiliary contact (13/14, 21/22) terminals.
                                                     

                                                    Can a GV2AF3 or GV2AF4 interconnection block work on a contactor with a DC coil?

                                                    Issue:
                                                    Mounting adaptor for GV2 and LC1D contactor

                                                    Product Line:
                                                    Motor Starters and Protectors

                                                    Environment:
                                                    TeSys GV Manual Starter and Protectors
                                                    Tesys D Contactors
                                                     
                                                    Resolution:
                                                    The GV2AF3 clip has to be moved to the DC position to accommodate the contactor with a DC coil.

                                                    What is the power terminal lug data for the LC1D40, LC1D50, LC1D65, LP1D40, LP1D50, and LP1D65 contactor?

                                                    Issue:
                                                    Identifying power terminal lug data for the D2 style contactors

                                                    Product Line:
                                                    Tesys D line contactors

                                                    Environment:
                                                    Products sold and used in the United States

                                                    Cause:
                                                    Power terminal lug data required

                                                    Resolution:
                                                    For contactors with screw clamp terminals:
                                                    stranded cable w/o cable end : One #10-3 AWG or Two #10-4 AWG per terminal.
                                                    stranded cable w/cable end: One #10-4 AWG or Two #12-2 AWG per terminal.
                                                    solid cable: One #10-3 AWG or Two #10-6 AWG per terminal.

                                                    What is the replacement coil part number for the LC*D09 through LC*D32 and LC*DT20 through LC*DT40 TeSys contactors?

                                                    Issue:
                                                    Identifying replacement coils for tesys D non-reversing and reversing conactors

                                                    Product Line:
                                                    IEC Contactors and Starters

                                                    Environment:
                                                    Products sold and used in the United States

                                                    Cause:
                                                    Replacement coil is needed

                                                    Resolution:
                                                    DC replacement coils are not available.
                                                    AC Coils are 50/60 hertz for voltages as listed below:

                                                    Volts - Part Number
                                                    12 ____ LXD1J7
                                                    21 ____ LXD1Z7
                                                    24 ____ LXD1B7
                                                    32 ____ LXD1C7
                                                    36 ____ LXD1CC7
                                                    42 ____ LXD1D7
                                                    48 ____ LXD1E7
                                                    60 ____ LXD1EE7
                                                    100 ___ LXD1K7 ( never brought to North America )
                                                    110 ___ LXD1F7
                                                    115 ___ LXD1FE7
                                                    120 ___ LXD1G7
                                                    127 ___ LXD1FC7
                                                    200 ___ LXD1L7
                                                    208 ___ LXD1LE7
                                                    220 ___ LXD1M7
                                                    230 ___ LXD1P7
                                                    240 ___ LXD1U7
                                                    277 ___ LXD1W7
                                                    380 ___ LXD1Q7
                                                    400 ___ LXD1V7
                                                    415 ___ LXD1N7
                                                    440 ___ LXD1R7
                                                    480 ___ LXD1T7
                                                    575 ___ LXD1SC7
                                                    600 ___ LXD1X7
                                                    690 ___ LXD1Y7


                                                    Note: A contactor with an AC coil can be changed to a different AC voltage coil, IE you can take an LC1D09 with a 120VAC coil and put a 24VAC coil in it instead. An AC device cannot be switched to a DC coil, and a DC device cannot be switches to an AC coil. 

                                                    What is the color scheme of the Tesys D-Line contactors?

                                                    Issue:
                                                    Looking for different color scheme of the Tesys D-Line contactors.

                                                    Product Line:
                                                    Tesys D Contactors

                                                    Environment:
                                                    LC1D contactors

                                                    Resolution:
                                                    Beige and dark gray.
                                                     

                                                    what is the replacement for an LC1D2510 contactor with 240v coil ?

                                                    The replacement is an LC1D25U7

                                                    Are the D-Line contactors rated to break DC voltages?

                                                    Issue: 
                                                    Can the TeSys D line be used to control DC loads? 

                                                    Product Line:
                                                    Tesys D contactors

                                                    Environment:
                                                    Products sold and used in the United States
                                                     
                                                    Cause:
                                                     DC power circuit
                                                     
                                                    Resolution:
                                                     
                                                    Yes, 75 VDC (125 VDC for D115 & D150) per pole which means that through a four pole device breaking 300 VDC is possible by wiring all four power poles in series. However, be aware that the device current ratings will differ according to the number of poles in series and the type of application.

                                                    Devices are suitable but not UL Listed for DC applications.

                                                    More information on their DC ratings can be found in the current TeSys Motor Control and Protection Compentns catalog: https://www.schneider-electric.us/en/download/document/MKTED210011EN/


                                                     

                                                    What is the coil burden for the standard DC control coil for the LC*D09__ through LC*D38__ TeSys contactors?

                                                    Issue:
                                                    LC*D09-38 coil consumption

                                                    Product Line:
                                                    Contactors and Overload Relays

                                                    Environment:
                                                    TeSys™ D Contactors and Overload Relays

                                                    Resolution:
                                                    The standard DC coil is 5.4 watts of consumption.

                                                    What is the power terminal lug data for the LC1D09, LC1DT20, LC1D12, and LC1DT25 contactor?

                                                    Issue:
                                                    Power terminal lug data required for the 9 and 12 amp rated Tesys D contactors

                                                    Product Line:
                                                    NEMA combination starters

                                                    Environment:
                                                    Products sold and used in the United States

                                                    Resolution:
                                                    For contactors with screw clamp terminals:
                                                    stranded cable w/o cable end : One or Two #18-10 AWG per terminal.
                                                    stranded cable w/cable end: One or Two #18-10 AWG per terminal.
                                                    solid cable: One or Two #18-8 AWG per terminal.

                                                    What is the part number for the spacer used with the LC*D09 through LC*D32 Contactor and the GV2AF3 combination block when the GV2 Motor Circuit Protector is mounted on din rail and the contactor hangs below it?

                                                    Issue:
                                                    Identifying the spacer part number for use with a LC*D, GV2AF3, and GV2 device combination

                                                    Product Line:
                                                    Contactors and Starters IEC

                                                    Environment:
                                                    Tesys D contactors and GV manual starters

                                                    Cause:
                                                    Spacer required

                                                    Resolution:
                                                    Compensation plate catalog number GV1F03, requires 2 pieces snap together.

                                                    What are the stand alone short circuit current ratings on the LC1D** contactors?

                                                    Issue:
                                                    Tesys D SCCR

                                                    Product Line:
                                                    Contactors and Overload Relays

                                                    Environment:
                                                    TeSys™ D Contactors and Overload Relays
                                                     
                                                    Resolution:
                                                    The contactors have a stand alone withstand rating that has been established by UL and is based on the maximum horsepower rating for a given device. However, only combination type starters are supplied with short circuit protective devices having a short circuit current rating.

                                                    They are as follows:
                                                    Horsepower SCCR (A)

                                                    0 thru 1 1,000
                                                    1 thru 50 5,000
                                                    51 thru 200 10,000
                                                    201 thru 400 18,000
                                                    401 thru 600 30,000
                                                    601 thru 900 42,000
                                                    901 thru 1600 85,000
                                                    1601+ 100,000

                                                    What is the difference between the LAD4TB and LAD4TBDL bi-directional peak limiting diode?

                                                    Issue:
                                                    Identifying the difference between LAD4TB and LAD4TBDL

                                                    Product Line:
                                                    IEC contactors and starters

                                                    Environment:
                                                    Products sold and used in the United States

                                                    Cause:
                                                    Identifying the difference between two similar part numbers

                                                    Resolution:
                                                    The LAD4TB is for 24V AC coils for the Tesys Series LC1D09 through LC1D38 contactors when supplied with G7 voltage code. The LAD4TBDL is 24 vdc bi-directional diode offered as a replacement if for some reason the diode supplied with the Tesys LC1D09 through LC1D38 contactors when ordered with BD or BL voltage code breaks or is no longer working.


                                                     

                                                    Will the LAD** time delay auxiliary contact module fit the D2 series pre-Tesys contactors?

                                                    Issue:
                                                    Can new accessories be used on older style contactors

                                                    Product Line:
                                                    IEC contactors and starters

                                                    Environment:
                                                    Products sold and used in the United States

                                                    Cause:
                                                    Identifying product compatibility

                                                    Resolution:
                                                    Yes, all front mount D2 and Tesys series auxiliary modules are backward forward compatible.


                                                     

                                                    Video: What auxiliary contact modules are available for the LC1D and LC2D contactors?

                                                    Issue:
                                                    Auxiliary contact modules for the LC1D and LC2D contactors

                                                    Product Line: 
                                                    Contactor and Starters - IEC

                                                    Environment:
                                                    North American Products

                                                    Resolution:
                                                    Select based on application requirements. Please note that the TeSys and Pre-TeSys auxiliary blocks are backward/forward compatible.
                                                    Front Mounting; maximum of 1 block per contactor:

                                                    N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
                                                    --1-----------1---------LADN11-----------LA1DN11
                                                    --1-----------1---------LADN11G---------LA1DN11G (See Footnote 1)
                                                    --1-----------1---------LADN11P---------LA1DN11P (See Footnote 1)
                                                    --2-----------0---------LADN20-----------LA1DN20
                                                    --2-----------0---------LA1DX20---------LA1DX20 (See Footnote 2)
                                                    --2-----------0---------LA1DY20---------LA1DY20 (See Footnote 3)
                                                    --0-----------2---------LADN02-----------LA1DN02
                                                    --2-----------2---------LADN22-----------LA1DN22
                                                    --2-----------2---------LADN22G---------LA1DN22G (See Footnote 1)
                                                    --2-----------2---------LADN22P---------LA1DN22P (See Footnote 1)
                                                    --2-----------2---------LADC22------------LA1DC22 (See Footnote 4)
                                                    --3-----------1---------LADN31------------LA1DN31
                                                    --3-----------1---------LA1DZ31----------LA1DZ31 (See Footnote 5)
                                                    --1-----------3---------LADN13------------LA1DN13
                                                    --4-----------0---------LADN40------------LA1DN40
                                                    --4-----------0---------LA1DZ40-----------LA1DZ40 (See Footnote 6)
                                                    --0-----------4---------LADN04------------LA1DN04




                                                    Front Mounting; maximum of 1 block per contactor: For use with D2 Series 25 amp through 80 amp contactors and TeSys Series 40 amp through 80 amp only.

                                                    N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
                                                    --1-----------0--------LADN10----------LA1DN10
                                                    --0-----------1--------LADN01----------LA1DN01

                                                    Side Mounting; maximum of 1 block on each side for D2 Series and Tesys Series 40 through 80 amp contactors. Tesys 9 through 32, 115, and 150 amps contactors will accept 1 block and is limited to left side only. (*) DC control devices will not accept side mount auxiliaries.
                                                    (*) DC control exceptions that will accept one left side mounted auxiliary: LC1D115 & LC1D150.

                                                    N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
                                                    --1-----------1--------LAD8N11----------LA8DN11
                                                    --2-----------0--------LAD8N20----------LA8DN20
                                                    --0-----------2--------LAD8N02----------N/A

                                                    Footnotes:
                                                    {1} EN50 012 Machine Tool Terminal Markings
                                                    {2} (2) NO Sealed Dust Tight Contacts
                                                    {3} Gold Flash Contacts
                                                    {4} (1) NO & (1) NC Standard and (1) NO & (1) NC Make Before Break
                                                    {5} (2) NO Dust Tight Contacts & (1) NO & (1) NC Standard Contacts
                                                    {6} (2) NO Dust Tight Contacts & (2) NO Standard Contacts

                                                    What is the difference between the LC1D25E7 and LC1D258E7?

                                                    The LC1D25E7 is a 3 Poles 25 Amps (AC-3) Contactor

                                                    Where as

                                                    The LC1D258E7 is a 4 Pole (2NO + 2NC) 25 Amps (AC-3) Contactor

                                                    https://www.schneider-electric.com.au/en/search/LC1D25E7

                                                    What is the complete part number for a 25A 11Kw 3P Contactor with 24VDC coil?

                                                    LC1D25BD is the correct part number

                                                    What is the part number for a 24VAC coil for a LC1D25?

                                                    The part number for a 24VAC coil for a LC1D25 is LXD1B7.

                                                    what coil voltage is the LC1D25N7 TeSys D?

                                                    it is 415v a.c.

                                                     

                                                    What are the coil voltage codes for the LC1D09 / LC2D09 through LC1D38 / LC2D38 TeSys contactors?

                                                    Issue:
                                                    What are the coil voltage codes for the LC1D09 / LC2D09through LC1D38 / LC2D38 TeSys contactors?

                                                    Product Line:
                                                    IEC Contactors

                                                    Environment:
                                                    Ordering

                                                    Cause:
                                                    Selection

                                                    Resolution:
                                                    The following lists the more common voltage suffix codes for these product lines.  For a more comprehensive list and to determine compatibility with a given product, refer to the catalog below.

                                                    AC Volts ___Code     AC Volts ___Code
                                                    12 ___ J7                   208 ___ LE7
                                                    21 ___ Z7                   220 ___ M7
                                                    24 ___ B7                  230 ___ P7
                                                    32 ___ C7                  240 ___ U7
                                                    36 ___ CC7               277 ___ W7
                                                    42 ___ D7                  380 ___ Q7
                                                    48 ___ E7                   400 ___ V7
                                                    60 ___ EE7                415 ___ N7
                                                    100 ___ K7                440 ___ R7
                                                    110 ___ F7                480 ___ T7
                                                    115 ___ FE7              575 ___ SC7
                                                    120 ___ G7                600 ___ X7
                                                    127 ___ FC7              690 ___ Y7
                                                    200 ___ L7                
                                                                   
                                                    Standard Coil                Low Consumption
                                                    DC Volts ___Code          DC Volts ___Code
                                                    12 ___ JD                           5 ___ AL
                                                    24 ___ BD                         12 ___ JL
                                                    36 ___ CD                         20 ___ ZL
                                                    48 ___ ED                         24 ___ BL
                                                    60 ___ ND                         48 ___ EL
                                                    72 ___ SD                         72 ___ SL
                                                    110 ___ FD                       96 ___ DL
                                                    125 ___ GD                     110 ___ FL
                                                    220 ___ MD                    220 ___ ML
                                                    250 ___ UD                     250 ___ UL
                                                    440 ___ RD                

                                                    What is the difference between LC1DT25 and LC1D25

                                                     LC1DT25 is 4 pole and LC1D25 is 3 pole

                                                    What is the inrush current for the LC1D25B7 Contactor?

                                                    The inrush current of the LC1D25B7 will be 70VA..or 2.92 Amps
                                                    see technical data sheet on coil...
                                                    https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=lxd1b7
                                                     

                                                    What is the part number of the spare coil for LC1D25B7 contactor?

                                                    LXD1B7 is the part number of the spare coil to suit LC1D25B7 contactor. For further information on the coil, please refer to the attached datasheet.
                                                     

                                                    What is the part number of the mechanical link for reversing contactors LC1D25U7

                                                    LAD9R1V

                                                    What is the replacement for the LC1F22510?

                                                    The replacement is LC1F225F5

                                                    What is the 110V DC coil to fit a Telemechanique contactor 3P 32Amp

                                                     The part code is LC1D32FD

                                                    Will LA6DK20* mechanical latch block suit LC1D150* contactor?

                                                    Yes,  LA6DK20* mechanical latch block can be used with LC1D150* contactor. 
                                                    For further information, please visit https://www.schneider-electric.com/en/product/LA6DK20M/contactor-latch-block-iec/

                                                    What replaces LC1D50BD

                                                    Replacement LC1D50ABD

                                                    LC1D6511 contactor with 220V coil - NZ equivalent?

                                                    LC1D65A contactor with a U7 240VAC coil is the closest.

                                                    What is the replacement AC coil for LC1D/LC2D40, D50, D65, D80, and D95?

                                                    Issue:
                                                    AC Coil information for LC1D/LC2D40, D50, D65, D80, and D95

                                                    Product Line:
                                                    Tesys D Replacement Parts

                                                    Environment:
                                                    TeSys™ D AC Coils

                                                    Resolution:

                                                    What overload to suit LC1D95U7 need to be 80-104A

                                                     Part code for the overload LRD3365

                                                    What is the code for the 240VAC Coil for the LC1D32 Contactor ?

                                                    Part Code = LXD1U7 
                                                    The LXD1U7 also fits the LC1D09 - D38 Contactors

                                                    Where do I find the Coil voltage on the Tesys D 3 Pole AC Contactor?

                                                    On the Tesys D 3 Pole AC Contactor you will find the coil voltage marked at the top, behind the Power terminals of the Contactor, for example U7, 240V 50/60 Hz

                                                    For the DC Version, the coil voltage is marked on the front of the Contactor. Hence it has got complete part number for the Contactor on the front, for example: LC1D25BD for 24V DC Coil.

                                                    What is the part code for a 4P 2 N/O and 2 N/C 40Amp 240V ac coil contactor

                                                    Part code is LC1D258U7

                                                    Difference between older D2 LC1D contactors and newwer LC1D contactors

                                                    Issue:
                                                    What is the difference between the older D2 style contactors where aux contacts had to be specified and the newer LC1D contactors?

                                                    Product Line:
                                                    TeSysD contactors

                                                    Environment:
                                                    US product

                                                    Cause:
                                                    Crossing into new units from old units require a review of differences

                                                    Resolution:
                                                    The older D2 style contactors required a specification of needed auxiliary contacts.  For example:

                                                    LC1D2501G6 would be an LC1D25 with 1 NC contact
                                                    LC1D2510G6 would be an LC1D25 with 1 NO contact

                                                    The newer contactors automatically come with 1 NO and 1 NC auxiliary contact.  For example:
                                                    LC1D25G7 has 1 NO and 1 NC contact

                                                    The older contactors usually had a dedicated 60hz coil.  This is designated by the 6 at the end of the part number.  The newer contactors have coils designed for 50/60hz and are signified by the 7 at the end of the part number.
                                                     

                                                    Will a LC1D12F7 operate on 60V DC as a control voltage

                                                    No it will not

                                                    LC1D1506 What are the dimensions? Weight?

                                                    Height 158 mm
                                                    Width 120 mm
                                                    Depth 136 mm
                                                    Product weight 2.5 kg

                                                    What is the 240v coil to fit an LC1D1506

                                                     The 240v coil is an LX1D8U7

                                                    What is the code for a complete LC1D95 with a 415vAC Coil?

                                                       The code for the contactor is LC1D95N7

                                                    On a LC1D25 contactor , are the aux contacts rated at 25A

                                                    The aux contacts on all our contactors are rated at 10A Ith

                                                    Will the LR3D325 overload relay fit a LC1D65G7 contactor?

                                                    Issue:
                                                    Will the LC1D65G7 mount to the LR3D325 overload relay?

                                                    Product Line:
                                                    IEC contactors and starters

                                                    Environment:
                                                    Products sold and used in the United States

                                                    Cause:
                                                    Identifying product compatibility

                                                    Resolution:
                                                    No, the LR3D325 is a overload relay with Everlink termination and will direct mount only to the LC1D40A to LC1D65A contactors.


                                                    CTA-ID : 2050461

                                                    What is the code for a 32Amp 24VDC 3 Pole Contactor ?

                                                    Code = LC1D32BD

                                                    What is the part number for the overload that fits LC1D95U7 60-90 Amps?

                                                    The overload to suit is the LRD3365

                                                     

                                                    What is the Mechanical Interlock for the LC1D12F7 ?

                                                    LAD9R1V Is the code for the Mechanical and Electrical Interlock kit.

                                                    What is the part number for spare contact set for LC1D1506 contactor?

                                                    The part number for spare contact set for LC1D1506 contactor is LA5D150803.

                                                    LA5D150803 
                                                    contacts set LA5-D - 3 poles - for LC1-D150
                                                    For more information see:https://www.schneider-electric.com.au/en/product-range-selector/664-tesys-d?p_url=http%3A%2F%2Fwww.ops-ecat.schneider-electric.com%2Fecat%2Fbrowse.do%3Fconf%3Dnull%26el_typ%3Dproduct%26range_id%3D664%26prd_id%3DLA5D150803%26scp_id%3DAU_en

                                                    What is the part number for a replacement 240VAC coil for the LC1D1506 contactor?

                                                    The part number for a replacement 240VAC coil for the LC1D1506 contactor is - LX1D8U7

                                                    For further information, visit the link below:-
                                                    https://www.schneider-electric.com.au/en/search/LX1D8U7
                                                    User-added image

                                                    What is the part number for a varistor coil surge suppressor for a LC1D09 to LC1D32 3 pole and LC1DT20 to LC1DT40 4 pole?

                                                    Issue:
                                                    Surge suppressor part number is needed

                                                    Product Line:
                                                    TeSys D line Contactors

                                                    Environment:
                                                    Products sold and used in the United States

                                                    Cause:
                                                    Need a varistor coil surge suppressor in their application

                                                    Resolution:
                                                    For 24 to 48 volts AC LAD4VE, for 50 to 127 volts AC LAD4VG, and for 110 to 250 volts AC LAD4VU.
                                                    These will limit the transient to 2 times nominal voltage and increases drop out time 1.1 to 1.5 times normal.

                                                     

                                                    What is the replacement for a LP1D1210BD

                                                    You can use a LC1D12BD or for low consumption a LC1D12BL.

                                                    I have a LC1D12BD contactor and want to fit a LA4DFB to it

                                                     You need to use a LAD4BB adaptor
                                                    Show More