TeSys D Contactor, 3P(3 NO), AC-3, <= 440V, 25A, 48VDC Coil

TeSys D Contactor, 3P(3 NO), AC-3, <= 440V, 25A, 48VDC Coil

TeSys D Contactor, 3P(3 NO), AC-3, <= 440V, 25A, 48VDC Coil

Item Number: LC1D25EL

Retail
$688.35
RRP (Inc. GST)

Product Dimensions

Width icon

Width45 mm

Height icon

Height85 mm

Depth icon

Depth101 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

TeSys D

Range

TeSys

Product or component type

contactor

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

[Ue] rated operational voltage

  • power circuit: <= 690 V AC 25...400 Hz
  • power circuit: <= 300 V DC
    • [Ie] rated operational current

    • 25 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
    • 40 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
      • Electrical durability

      • 1.65 Mcycles 25 A AC-3 at Ue <= 440 V
      • 1.4 Mcycles 40 A AC-1 at Ue <= 440 V
        • Mounting support

        • rail
        • plate
          • Standards

          • CSA C22.2 No 14
          • EN 60947-4-1
          • EN 60947-5-1
          • IEC 60947-4-1
          • IEC 60947-5-1
          • UL 508
            • Product certifications

            • DNV
            • LROS (Lloyds register of shipping)
            • CSA
            • GOST
            • RINA
            • UL
            • BV
            • CCC
            • GL
              • Connections - terminals

              • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
              • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
              • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
              • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
              • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end
              • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end
              • power circuit: screw clamp terminals 1 cable(s) 2.5-10 mm²flexible without cable end
              • power circuit: screw clamp terminals 2 cable(s) 2.5-10 mm²flexible without cable end
              • power circuit: screw clamp terminals 1 cable(s) 1-10 mm²flexible with cable end
              • power circuit: screw clamp terminals 2 cable(s) 1.5-6 mm²flexible with cable end
              • power circuit: screw clamp terminals 1 cable(s) 1.5-10 mm²solid without cable end
              • power circuit: screw clamp terminals 2 cable(s) 2.5-10 mm²solid without cable end
                • Mechanical durability

                  30 Mcycles

                  Insulation resistance

                  > 10 MOhm for signalling circuit

                  IP degree of protection

                  IP20 front face conforming to IEC 60529

                  Ambient air temperature for storage

                  -60-80 °C

                  Height

                  85 mm

                  Width

                  45 mm

                  Depth

                  101 mm

                  Net weight

                  0.53 kg

                  REACh free of SVHC

                  Yes

                  EU RoHS Directive

                  Compliant

                  Toxic heavy metal free

                  Yes

                  Mercury free

                  Yes

                  RoHS exemption information

                  Yes

                  China RoHS Regulation

                   Pro-active China RoHS declaration (out of China RoHS legal scope)

                  Environmental Disclosure

                  ENVPEP110229EN

                  Circularity Profile

                  ENVEOLI1102029EN

                  Others

                  Product name

                  TeSys D

                  Device short name

                  LC1D

                  Contactor application

                • resistive load
                • motor control
                  • Utilisation category

                  • AC-1
                  • AC-3
                  • AC-4
                    • Poles description

                      3P

                      Pole contact composition

                      3 NO

                      Motor power kW

                    • 5.5 kW at 220...230 V AC 50/60 Hz (AC-3)
                    • 11 kW at 380...400 V AC 50/60 Hz (AC-3)
                    • 11 kW at 415...440 V AC 50/60 Hz (AC-3)
                    • 15 kW at 500 V AC 50/60 Hz (AC-3)
                    • 15 kW at 660...690 V AC 50/60 Hz (AC-3)
                    • 5.5 kW at 400 V AC 50/60 Hz (AC-4)
                      • Motor power hp

                      • 3 hp at 230/240 V AC 50/60 Hz for 1 phase motors
                      • 2 hp at 115 V AC 50/60 Hz for 1 phase motors
                      • 7.5 hp at 230/240 V AC 50/60 Hz for 3 phases motors
                      • 15 hp at 460/480 V AC 50/60 Hz for 3 phases motors
                      • 20 hp at 575/600 V AC 50/60 Hz for 3 phases motors
                      • 7.5 hp at 200/208 V AC 50/60 Hz for 3 phases motors
                        • Control circuit type

                          DC low consumption

                          [Uc] control circuit voltage

                          48 V DC

                          Auxiliary contact composition

                          1 NO + 1 NC

                          [Uimp] rated impulse withstand voltage

                          6 kV conforming to IEC 60947

                          Overvoltage category

                          III

                          [Ith] conventional free air thermal current

                        • 10 A (at 60 °C) for signalling circuit
                        • 40 A (at 60 °C) for power circuit
                          • Irms rated making capacity

                          • 140 A AC for signalling circuit conforming to IEC 60947-5-1
                          • 250 A DC for signalling circuit conforming to IEC 60947-5-1
                          • 450 A at 440 V for power circuit conforming to IEC 60947
                            • Rated breaking capacity

                              450 A at 440 V for power circuit conforming to IEC 60947

                              [Icw] rated short-time withstand current

                            • 240 A 40 °C - 10 s for power circuit
                            • 380 A 40 °C - 1 s for power circuit
                            • 50 A 40 °C - 10 min for power circuit
                            • 120 A 40 °C - 1 min for power circuit
                            • 100 A - 1 s for signalling circuit
                            • 120 A - 500 ms for signalling circuit
                            • 140 A - 100 ms for signalling circuit
                              • Associated fuse rating

                              • 10 A gG for signalling circuit conforming to IEC 60947-5-1
                              • 63 A gG at <= 690 V coordination type 1 for power circuit
                              • 40 A gG at <= 690 V coordination type 2 for power circuit
                                • Average impedance

                                  2 mOhm - Ith 40 A 50 Hz for power circuit

                                  [Ui] rated insulation voltage

                                • power circuit: 690 V conforming to IEC 60947-4-1
                                • power circuit: 600 V CSA certified
                                • power circuit: 600 V UL certified
                                • signalling circuit: 690 V conforming to IEC 60947-1
                                • signalling circuit: 600 V CSA certified
                                • signalling circuit: 600 V UL certified
                                  • Power dissipation per pole

                                  • 3.2 W AC-1
                                  • 1.25 W AC-3
                                    • Protective cover

                                      with

                                      Tightening torque

                                    • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                                    • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
                                    • power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                                    • power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver Philips No 2
                                      • Operating time

                                      • 65.45...88.55 ms closing
                                      • 20...30 ms opening
                                        • Safety reliability level

                                        • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                                        • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                                          • Maximum operating rate

                                            3600 cyc/h 60 °C

                                            Coil technology

                                            built-in bidirectional peak limiting diode suppressor

                                            Time constant

                                            40 ms

                                            Inrush power in W

                                            2.4-2.4 W (at 20 °C)

                                            Hold-in power consumption in W

                                            2.4-2.4 W at 20 °C

                                            Auxiliary contacts type

                                          • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
                                          • type mirror contact 1 NC conforming to IEC 60947-4-1
                                            • Signalling circuit frequency

                                              25...400 Hz

                                              Minimum switching current

                                              5 mA for signalling circuit

                                              Minimum switching voltage

                                              17 V for signalling circuit

                                              Non-overlap time

                                            • 1.5 ms on de-energisation between NC and NO contact
                                            • 1.5 ms on energisation between NC and NO contact
                                              • Contact compatibility

                                                M5

                                                Compatibility code

                                                LC1D

                                                Protective treatment

                                                TH conforming to IEC 60068-2-30

                                                Pollution degree

                                                3

                                                Operating altitude

                                                3000 m without derating

                                                Fire resistance

                                                850 °C conforming to IEC 60695-2-1

                                                Flame retardance

                                                V1 conforming to UL 94

                                                Mechanical robustness

                                              • vibrations contactor open: 2 Gn, 5...300 Hz
                                              • vibrations contactor closed: 4 Gn, 5...300 Hz
                                              • shocks contactor closed: 15 Gn for 11 ms
                                              • shocks contactor open: 8 Gn for 11 ms
                                                • Unit Type of Package 1

                                                  PCE

                                                  Number of Units in Package 1

                                                  1

                                                  Package 1 Weight

                                                  581 g

                                                  Package 1 Height

                                                  5 cm

                                                  Package 1 width

                                                  9.2 cm

                                                  Package 1 Length

                                                  11.1 cm

                                                  WEEE

                                                  The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

                                                  PVC free

                                                  Yes
                                                  Show all specifications

                                                  Documents & downloads

                                                  hide show
                                                  Filter items
                                                  • All

                                                  • CAD Files and Packs

                                                  • Product Brochures

                                                  • Technical Data Catalogues

                                                  • Product Environmental

                                                  • Installation Instruction

                                                  • End of Life Manual

                                                  • Certificates (MSDS)

                                                  • Declaration of Conformity

                                                  Frequently Asked Questions

                                                  hide show

                                                  What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

                                                  Issue:
                                                  Identifying maximum voltage of an LC1D contactor

                                                  Product Line:
                                                  TeSys D Contactors

                                                  Environment:
                                                  IEC contactors and starters used in North America

                                                  Cause:
                                                  n/a

                                                  Resolution:
                                                  IThe maximum voltage per UL and CSA is 600VAC. 
                                                   

                                                  What is the altitude derating for a TeSys D-Line contactor?

                                                  Issue:​
                                                  What is the altitude derating for a TeSys D-Line contactor?

                                                  Product Line:
                                                  Digest 177 Section 18 : Contactors and Starters, IEC

                                                  Environment:
                                                  North American Products

                                                  Resolution:
                                                  The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

                                                  Voltage
                                                  3500m x 0.90
                                                  4000m x 0.80
                                                  4500m x 0.70
                                                  5000m x 0.60

                                                  Current
                                                  3500m x 0.92
                                                  4000m x 0.90
                                                  4500m x 0.88
                                                  5000m x 0.86

                                                  For example, an LC1D80 at 5000 meters:
                                                  - The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
                                                  - The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



                                                   

                                                  Where are the control coil terminals for TeSys LC1D09 to LC1D38 contactor?

                                                  Issue:
                                                  Determine the control coil terminal marking and location on LC1D09 to LC1D38 contactor

                                                  Product Line: 
                                                  Tesys D Contactors

                                                  Environment:
                                                  IEC contactors

                                                  Resolution:
                                                  The coil terminals are marked A1 and A2, you can see them on the front of the contactor on the white part (control section).  They are next to the auxiliary contact (13/14, 21/22) terminals.
                                                   

                                                  What is the replacement coil part number for the LC*D09 through LC*D32 and LC*DT20 through LC*DT40 TeSys contactors?

                                                  Issue:
                                                  Identifying replacement coils for tesys D non-reversing and reversing conactors

                                                  Product Line:
                                                  IEC Contactors and Starters

                                                  Environment:
                                                  Products sold and used in the United States

                                                  Cause:
                                                  Replacement coil is needed

                                                  Resolution:
                                                  DC replacement coils are not available.
                                                  AC Coils are 50/60 hertz for voltages as listed below:

                                                  Volts - Part Number
                                                  12 ____ LXD1J7
                                                  21 ____ LXD1Z7
                                                  24 ____ LXD1B7
                                                  32 ____ LXD1C7
                                                  36 ____ LXD1CC7
                                                  42 ____ LXD1D7
                                                  48 ____ LXD1E7
                                                  60 ____ LXD1EE7
                                                  100 ___ LXD1K7 ( never brought to North America )
                                                  110 ___ LXD1F7
                                                  115 ___ LXD1FE7
                                                  120 ___ LXD1G7
                                                  127 ___ LXD1FC7
                                                  200 ___ LXD1L7
                                                  208 ___ LXD1LE7
                                                  220 ___ LXD1M7
                                                  230 ___ LXD1P7
                                                  240 ___ LXD1U7
                                                  277 ___ LXD1W7
                                                  380 ___ LXD1Q7
                                                  400 ___ LXD1V7
                                                  415 ___ LXD1N7
                                                  440 ___ LXD1R7
                                                  480 ___ LXD1T7
                                                  575 ___ LXD1SC7
                                                  600 ___ LXD1X7
                                                  690 ___ LXD1Y7


                                                  Note: A contactor with an AC coil can be changed to a different AC voltage coil, IE you can take an LC1D09 with a 120VAC coil and put a 24VAC coil in it instead. An AC device cannot be switched to a DC coil, and a DC device cannot be switches to an AC coil. 

                                                  Can a GV2AF3 or GV2AF4 interconnection block work on a contactor with a DC coil?

                                                  Issue:
                                                  Mounting adaptor for GV2 and LC1D contactor

                                                  Product Line:
                                                  Motor Starters and Protectors

                                                  Environment:
                                                  TeSys GV Manual Starter and Protectors
                                                  Tesys D Contactors
                                                   
                                                  Resolution:
                                                  The GV2AF3 clip has to be moved to the DC position to accommodate the contactor with a DC coil.

                                                  What is the power terminal lug data for the LC1D40, LC1D50, LC1D65, LP1D40, LP1D50, and LP1D65 contactor?

                                                  Issue:
                                                  Identifying power terminal lug data for the D2 style contactors

                                                  Product Line:
                                                  Tesys D line contactors

                                                  Environment:
                                                  Products sold and used in the United States

                                                  Cause:
                                                  Power terminal lug data required

                                                  Resolution:
                                                  For contactors with screw clamp terminals:
                                                  stranded cable w/o cable end : One #10-3 AWG or Two #10-4 AWG per terminal.
                                                  stranded cable w/cable end: One #10-4 AWG or Two #12-2 AWG per terminal.
                                                  solid cable: One #10-3 AWG or Two #10-6 AWG per terminal.

                                                  What is the difference between the LC1D25E7 and LC1D258E7?

                                                  The LC1D25E7 is a 3 Poles 25 Amps (AC-3) Contactor

                                                  Where as

                                                  The LC1D258E7 is a 4 Pole (2NO + 2NC) 25 Amps (AC-3) Contactor

                                                  https://www.schneider-electric.com.au/en/search/LC1D25E7

                                                  What is the power terminal lug data for the LC1D09, LC1DT20, LC1D12, and LC1DT25 contactor?

                                                  Issue:
                                                  Power terminal lug data required for the 9 and 12 amp rated Tesys D contactors

                                                  Product Line:
                                                  NEMA combination starters

                                                  Environment:
                                                  Products sold and used in the United States

                                                  Resolution:
                                                  For contactors with screw clamp terminals:
                                                  stranded cable w/o cable end : One or Two #18-10 AWG per terminal.
                                                  stranded cable w/cable end: One or Two #18-10 AWG per terminal.
                                                  solid cable: One or Two #18-8 AWG per terminal.

                                                  What is the color scheme of the Tesys D-Line contactors?

                                                  Issue:
                                                  Looking for different color scheme of the Tesys D-Line contactors.

                                                  Product Line:
                                                  Tesys D Contactors

                                                  Environment:
                                                  LC1D contactors

                                                  Resolution:
                                                  Beige and dark gray.
                                                   

                                                  what is the replacement for an LC1D2510 contactor with 240v coil ?

                                                  The replacement is an LC1D25U7

                                                  Are the D-Line contactors rated to break DC voltages?

                                                  Issue: 
                                                  Can the TeSys D line be used to control DC loads? 

                                                  Product Line:
                                                  Tesys D contactors

                                                  Environment:
                                                  Products sold and used in the United States
                                                   
                                                  Cause:
                                                   DC power circuit
                                                   
                                                  Resolution:
                                                   
                                                  Yes, 75 VDC (125 VDC for D115 & D150) per pole which means that through a four pole device breaking 300 VDC is possible by wiring all four power poles in series. However, be aware that the device current ratings will differ according to the number of poles in series and the type of application.

                                                  Devices are suitable but not UL Listed for DC applications.

                                                  More information on their DC ratings can be found in the current TeSys Motor Control and Protection Compentns catalog: https://www.schneider-electric.us/en/download/document/MKTED210011EN/


                                                   

                                                  What is the coil burden for the standard DC control coil for the LC*D09__ through LC*D38__ TeSys contactors?

                                                  Issue:
                                                  LC*D09-38 coil consumption

                                                  Product Line:
                                                  Contactors and Overload Relays

                                                  Environment:
                                                  TeSys™ D Contactors and Overload Relays

                                                  Resolution:
                                                  The standard DC coil is 5.4 watts of consumption.
                                                  Show More