TeSys LC1D09 D12 D18 - 3P - DC coil - screw & screw clamp connector

TeSys D Contactor, 3P(3 NO), AC-3, <= 440V, 18A, 60VDC Coil

Catalogue Number: LC1D18ND
TeSys LC1D09 D12 D18 - 3P - DC coil - screw & screw clamp connector
Colour:
Colour: Per UOM Std.
  • 1 PCE
Added to cart
Successfully added, you can view your cart here

Key Features & Specifications

hide show
Range of product
TeSys D
Range
TeSys
Product name
TeSys D
Product or component type
contactor
Device short name
LC1D
Contactor application
  • resistive load
  • motor control
    • Utilisation category
    • AC-1
    • AC-4
    • AC-3
      • Poles description
        3P
        Pole contact composition
        3 NO
        [Ue] rated operational voltage
      • power circuit: <= 690 V AC 25...400 Hz
      • power circuit: <= 300 V DC
        • [Ie] rated operational current
        • 18 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
        • 32 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
          • Motor power kW
          • 4 kW at 220...230 V AC 50/60 Hz (AC-3)
          • 7.5 kW at 380...400 V AC 50/60 Hz (AC-3)
          • 9 kW at 415...440 V AC 50/60 Hz (AC-3)
          • 10 kW at 500 V AC 50/60 Hz (AC-3)
          • 10 kW at 660...690 V AC 50/60 Hz (AC-3)
          • 4 kW at 400 V AC 50/60 Hz (AC-4)
            • Motor power hp
            • 1 hp at 115 V AC 50/60 Hz for 1 phase motors
            • 3 hp at 230/240 V AC 50/60 Hz for 1 phase motors
            • 5 hp at 200/208 V AC 50/60 Hz for 3 phases motors
            • 5 hp at 230/240 V AC 50/60 Hz for 3 phases motors
            • 10 hp at 460/480 V AC 50/60 Hz for 3 phases motors
            • 15 hp at 575/600 V AC 50/60 Hz for 3 phases motors
              • Control circuit type
                DC standard
                [Uc] control circuit voltage
                60 V DC
                Auxiliary contact composition
                1 NO + 1 NC
                [Uimp] rated impulse withstand voltage
                6 kV conforming to IEC 60947
                Overvoltage category
                III
                [Ith] conventional free air thermal current
              • 10 A (at 60 °C) for signalling circuit
              • 32 A (at 60 °C) for power circuit
                • Irms rated making capacity
                • 140 A AC for signalling circuit conforming to IEC 60947-5-1
                • 250 A DC for signalling circuit conforming to IEC 60947-5-1
                • 300 A at 440 V for power circuit conforming to IEC 60947
                  • Rated breaking capacity
                    300 A at 440 V for power circuit conforming to IEC 60947
                    [Icw] rated short-time withstand current
                  • 145 A 40 °C - 10 s for power circuit
                  • 240 A 40 °C - 1 s for power circuit
                  • 40 A 40 °C - 10 min for power circuit
                  • 84 A 40 °C - 1 min for power circuit
                  • 100 A - 1 s for signalling circuit
                  • 120 A - 500 ms for signalling circuit
                  • 140 A - 100 ms for signalling circuit
                    • Associated fuse rating
                    • 10 A gG for signalling circuit conforming to IEC 60947-5-1
                    • 50 A gG at <= 690 V coordination type 1 for power circuit
                    • 35 A gG at <= 690 V coordination type 2 for power circuit
                      • Average impedance
                        2.5 mOhm - Ith 32 A 50 Hz for power circuit
                        [Ui] rated insulation voltage
                      • power circuit: 690 V conforming to IEC 60947-4-1
                      • power circuit: 600 V CSA certified
                      • power circuit: 600 V UL certified
                      • signalling circuit: 690 V conforming to IEC 60947-1
                      • signalling circuit: 600 V CSA certified
                      • signalling circuit: 600 V UL certified
                        • Electrical durability
                        • 1.65 Mcycles 18 A AC-3 at Ue <= 440 V
                        • 1 Mcycles 32 A AC-1 at Ue <= 440 V
                          • Power dissipation per pole
                          • 2.5 W AC-1
                          • 0.8 W AC-3
                            • Protective cover
                              with
                              Mounting support
                            • plate
                            • rail
                              • Standards
                              • CSA C22.2 No 14
                              • EN 60947-4-1
                              • EN 60947-5-1
                              • IEC 60947-4-1
                              • IEC 60947-5-1
                              • UL 508
                                • Product certifications
                                • GOST
                                • RINA
                                • CSA
                                • DNV
                                • CCC
                                • LROS (Lloyds register of shipping)
                                • BV
                                • UL
                                • GL
                                  • Connections - terminals
                                  • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
                                  • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
                                  • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
                                  • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
                                  • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end
                                  • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end
                                  • power circuit: screw clamp terminals 1 cable(s) 1.5-6 mm²flexible without cable end
                                  • power circuit: screw clamp terminals 2 cable(s) 1.5-6 mm²flexible without cable end
                                  • power circuit: screw clamp terminals 1 cable(s) 1-6 mm²flexible with cable end
                                  • power circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible with cable end
                                  • power circuit: screw clamp terminals 1 cable(s) 1.5-6 mm²solid without cable end
                                  • power circuit: screw clamp terminals 2 cable(s) 1.5-6 mm²solid without cable end
                                    • Tightening torque
                                    • power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                                    • power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
                                    • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                                    • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
                                      • Operating time
                                      • 53.55...72.45 ms closing
                                      • 16...24 ms opening
                                        • Safety reliability level
                                        • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                                        • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                                          • Mechanical durability
                                            30 Mcycles
                                            Maximum operating rate
                                            3600 cyc/h 60 °C
                                            Coil technology
                                            with integral suppression device
                                            Control circuit voltage limits
                                          • drop-out: 0.1...0.25 Uc DC (at 60 °C)
                                          • operational: 0.7...1.25 Uc DC (at 60 °C)
                                            • Time constant
                                              28 ms
                                              Inrush power in W
                                              5.4-5.4 W (at 20 °C)
                                              Hold-in power consumption in W
                                              5.4-5.4 W at 20 °C
                                              Auxiliary contacts type
                                            • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
                                            • type mirror contact 1 NC conforming to IEC 60947-4-1
                                              • Signalling circuit frequency
                                                25...400 Hz
                                                Minimum switching current
                                                5 mA for signalling circuit
                                                Minimum switching voltage
                                                17 V for signalling circuit
                                                Non-overlap time
                                              • 1.5 ms on de-energisation between NC and NO contact
                                              • 1.5 ms on energisation between NC and NO contact
                                                • Insulation resistance
                                                  > 10 MOhm for signalling circuit
                                                  Contact compatibility
                                                  M4
                                                  Compatibility code
                                                  LC1D
                                                  IP degree of protection
                                                  IP20 front face conforming to IEC 60529
                                                  Protective treatment
                                                  TH conforming to IEC 60068-2-30
                                                  Pollution degree
                                                  3
                                                  Ambient air temperature for operation
                                                  -5-60 °C
                                                  Ambient air temperature for storage
                                                  -60-80 °C
                                                  Permissible ambient air temperature around the device
                                                  -40-70 °C at Uc
                                                  Operating altitude
                                                  3000 m without
                                                  Fire resistance
                                                  850 °C conforming to IEC 60695-2-1
                                                  Flame retardance
                                                  V1 conforming to UL 94
                                                  Mechanical robustness
                                                • vibrations contactor open: 2 Gn, 5...300 Hz
                                                • vibrations contactor closed: 4 Gn, 5...300 Hz
                                                • shocks contactor open: 10 Gn for 11 ms
                                                • shocks contactor closed: 15 Gn for 11 ms
                                                  • Height
                                                    77 mm
                                                    Width
                                                    45 mm
                                                    Depth
                                                    95 mm
                                                    Net weight
                                                    0.49 kg
                                                    Sustainable offer status
                                                    Green Premium product
                                                    REACh Regulation
                                                    Free of Substances of Very High Concern above the threshold
                                                    EU RoHS Directive
                                                    Compliant
                                                    Mercury free
                                                    Yes
                                                    RoHS exemption information
                                                    Yes
                                                    China RoHS Regulation
                                                    Product out of China RoHS scope. Substance declaration for your information
                                                    Environmental Disclosure
                                                    ENVPEP110230EN
                                                    Circularity Profile
                                                    ENVEOLI1102030EN
                                                    WEEE
                                                    The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                                                    California proposition 65
                                                    WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov
                                                    Warranty
                                                    18 months

                                                    Documents & downloads

                                                    hide show
                                                    Filter items
                                                    • All

                                                    • CAD Files and Packs

                                                    • Product Brochures

                                                    • Movies

                                                    • Technical Data Catalogues

                                                    • Catalog Page

                                                    • Technical Leaflet

                                                    • End of Life Manual

                                                    • Product Environmental

                                                    • Data Bulletin

                                                    • Installation Instruction

                                                    • Handout

                                                    • Operating Manuals

                                                    • Application Solutions

                                                    • Certificates (MSDS)

                                                    • Declaration of Conformity

                                                    • White Paper

                                                    • Marine Certificate

                                                    • eTechPub

                                                    • Software - Released