Quantcast

TeSys D Contactor, 3P(3 NO), AC-3, <= 440V, 18A, 24VDC Coil

TeSys D Contactor, 3P(3 NO), AC-3, <= 440V, 18A, 24VDC Coil

TeSys D Contactor, 3P(3 NO), AC-3, <= 440V, 18A, 24VDC Coil

Item Number: LC1D18BL

Retail
$525.14
RRP (Inc. GST)

Product Dimensions

Width icon

Width45 mm

Height icon

Height77 mm

Depth icon

Depth95 mm

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

TeSys D

Range

TeSys

Product or component type

contactor

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

[Ue] rated operational voltage

  • power circuit: <= 690 V AC 25...400 Hz
  • power circuit: <= 300 V DC
    • [Ie] rated operational current

    • 18 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
    • 32 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
      • Electrical durability

      • 1.65 Mcycles 18 A AC-3 at Ue <= 440 V
      • 1 Mcycles 32 A AC-1 at Ue <= 440 V
        • Mounting support

        • plate
        • rail
          • Standards

          • CSA C22.2 No 14
          • EN 60947-4-1
          • EN 60947-5-1
          • IEC 60947-4-1
          • IEC 60947-5-1
          • UL 508
            • Product certifications

            • BV
            • GOST
            • CCC
            • DNV
            • LROS (Lloyds register of shipping)
            • UL
            • GL
            • CSA
            • RINA
            • UKCA
              • Connections - terminals

              • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
              • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
              • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
              • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
              • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end
              • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end
              • power circuit: screw clamp terminals 1 cable(s) 1.5-6 mm²flexible without cable end
              • power circuit: screw clamp terminals 2 cable(s) 1.5-6 mm²flexible without cable end
              • power circuit: screw clamp terminals 1 cable(s) 1-6 mm²flexible with cable end
              • power circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible with cable end
              • power circuit: screw clamp terminals 1 cable(s) 1.5-6 mm²solid without cable end
              • power circuit: screw clamp terminals 2 cable(s) 1.5-6 mm²solid without cable end
                • Mechanical durability

                  30 Mcycles

                  Insulation resistance

                  > 10 MOhm for signalling circuit

                  IP degree of protection

                  IP20 front face conforming to IEC 60529

                  Ambient air temperature for operation

                • -40-60 °C
                • 60-70 °C with derating
                  • Ambient air temperature for storage

                    -60-80 °C

                    Height

                    77 mm

                    Width

                    45 mm

                    Depth

                    95 mm

                    Net weight

                    0.49 kg

                    REACh Regulation

                    Free of Substances of Very High Concern above the threshold

                    REACh free of SVHC

                    Yes

                    EU RoHS Directive

                    Compliant

                    Toxic heavy metal free

                    Yes

                    Mercury free

                    Yes

                    RoHS exemption information

                    Yes

                    China RoHS Regulation

                     Pro-active China RoHS declaration (out of China RoHS legal scope)

                    Environmental Disclosure

                    ENVPEP1501004EN

                    Circularity Profile

                    ENVEOLI1501004EN

                    California proposition 65

                    WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov

                    Others

                    Product name

                    TeSys D

                    Device short name

                    LC1D

                    Contactor application

                  • motor control
                  • resistive load
                    • Utilisation category

                    • AC-1
                    • AC-3
                    • AC-4
                      • Poles description

                        3P

                        Pole contact composition

                        3 NO

                        Motor power kW

                      • 4 kW at 220...230 V AC 50/60 Hz (AC-3)
                      • 7.5 kW at 380...400 V AC 50/60 Hz (AC-3)
                      • 9 kW at 415...440 V AC 50/60 Hz (AC-3)
                      • 10 kW at 500 V AC 50/60 Hz (AC-3)
                      • 10 kW at 660...690 V AC 50/60 Hz (AC-3)
                      • 4 kW at 400 V AC 50/60 Hz (AC-4)
                        • Motor power hp

                        • 1 hp at 115 V AC 50/60 Hz for 1 phase motors
                        • 3 hp at 230/240 V AC 50/60 Hz for 1 phase motors
                        • 5 hp at 200/208 V AC 50/60 Hz for 3 phases motors
                        • 5 hp at 230/240 V AC 50/60 Hz for 3 phases motors
                        • 10 hp at 460/480 V AC 50/60 Hz for 3 phases motors
                        • 15 hp at 575/600 V AC 50/60 Hz for 3 phases motors
                          • Control circuit type

                            DC low consumption

                            [Uc] control circuit voltage

                            24 V DC

                            Auxiliary contact composition

                            1 NO + 1 NC

                            [Uimp] rated impulse withstand voltage

                            6 kV conforming to IEC 60947

                            Overvoltage category

                            III

                            [Ith] conventional free air thermal current

                          • 10 A (at 60 °C) for signalling circuit
                          • 32 A (at 60 °C) for power circuit
                            • Irms rated making capacity

                            • 140 A AC for signalling circuit conforming to IEC 60947-5-1
                            • 250 A DC for signalling circuit conforming to IEC 60947-5-1
                            • 300 A at 440 V for power circuit conforming to IEC 60947
                              • Rated breaking capacity

                                300 A at 440 V for power circuit conforming to IEC 60947

                                [Icw] rated short-time withstand current

                              • 145 A 40 °C - 10 s for power circuit
                              • 240 A 40 °C - 1 s for power circuit
                              • 40 A 40 °C - 10 min for power circuit
                              • 84 A 40 °C - 1 min for power circuit
                              • 100 A - 1 s for signalling circuit
                              • 120 A - 500 ms for signalling circuit
                              • 140 A - 100 ms for signalling circuit
                                • Associated fuse rating

                                • 10 A gG for signalling circuit conforming to IEC 60947-5-1
                                • 50 A gG at <= 690 V coordination type 1 for power circuit
                                • 35 A gG at <= 690 V coordination type 2 for power circuit
                                  • Average impedance

                                    2.5 mOhm - Ith 32 A 50 Hz for power circuit

                                    [Ui] rated insulation voltage

                                  • power circuit: 690 V conforming to IEC 60947-4-1
                                  • power circuit: 600 V CSA certified
                                  • power circuit: 600 V UL certified
                                  • signalling circuit: 690 V conforming to IEC 60947-1
                                  • signalling circuit: 600 V CSA certified
                                  • signalling circuit: 600 V UL certified
                                    • Power dissipation per pole

                                    • 2.5 W AC-1
                                    • 0.8 W AC-3
                                      • Protective cover

                                        with

                                        Tightening torque

                                      • power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                                      • power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
                                      • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                                      • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
                                        • Operating time

                                        • 65.45...88.55 ms closing
                                        • 20...30 ms opening
                                          • Safety reliability level

                                          • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                                          • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                                            • Maximum operating rate

                                              3600 cyc/h 60 °C

                                              Coil technology

                                              built-in bidirectional peak limiting diode suppressor

                                              Control circuit voltage limits

                                            • 0.1...0.3 Uc (-40-70 °C):drop-out DC
                                            • 0.8...1.25 Uc (-40-60 °C):operational DC
                                            • 1...1.25 Uc (60-70 °C):operational DC
                                              • Time constant

                                                40 ms

                                                Inrush power in W

                                                2.4-2.4 W (at 20 °C)

                                                Hold-in power consumption in W

                                                2.4-2.4 W at 20 °C

                                                Auxiliary contacts type

                                              • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
                                              • type mirror contact 1 NC conforming to IEC 60947-4-1
                                                • Signalling circuit frequency

                                                  25...400 Hz

                                                  Minimum switching current

                                                  5 mA for signalling circuit

                                                  Minimum switching voltage

                                                  17 V for signalling circuit

                                                  Non-overlap time

                                                • 1.5 ms on de-energisation between NC and NO contact
                                                • 1.5 ms on energisation between NC and NO contact
                                                  • Contact compatibility

                                                    M5

                                                    Compatibility code

                                                    LC1D

                                                    Power range

                                                  • 4-6 kW at 200-240 V 3 phases
                                                  • 7-11 kW at 380-440 V 3 phases
                                                  • 7-11 kW at 480-500 V 3 phases
                                                    • Motor starter type

                                                      direct on-line contactor

                                                      Contactor coil voltage

                                                      24 V DC low consumption

                                                      Protective treatment

                                                      TH conforming to IEC 60068-2-30

                                                      Pollution degree

                                                      3

                                                      Operating altitude

                                                      0...3000 m

                                                      Fire resistance

                                                      850 °C conforming to IEC 60695-2-1

                                                      Flame retardance

                                                      V1 conforming to UL 94

                                                      Mechanical robustness

                                                    • vibrations contactor open: 2 Gn, 5...300 Hz
                                                    • vibrations contactor closed: 4 Gn, 5...300 Hz
                                                    • shocks contactor open: 10 Gn for 11 ms
                                                    • shocks contactor closed: 15 Gn for 11 ms
                                                      • Unit Type of Package 1

                                                        PCE

                                                        Number of Units in Package 1

                                                        1

                                                        Package 1 Weight

                                                        534 g

                                                        Package 1 Height

                                                        5 cm

                                                        Package 1 width

                                                        9 cm

                                                        Package 1 Length

                                                        11 cm

                                                        Unit Type of Package 2

                                                        S02

                                                        Number of Units in Package 2

                                                        15

                                                        Package 2 Weight

                                                        8.284 kg

                                                        Package 2 Height

                                                        15 cm

                                                        Package 2 width

                                                        30 cm

                                                        Package 2 Length

                                                        40 cm

                                                        Unit Type of Package 3

                                                        P06

                                                        Number of Units in Package 3

                                                        240

                                                        Package 3 Weight

                                                        142.98 kg

                                                        Package 3 Height

                                                        77 cm

                                                        Package 3 width

                                                        80 cm

                                                        Package 3 Length

                                                        60 cm

                                                        WEEE

                                                        The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

                                                        PVC free

                                                        Yes
                                                        Show all specifications

                                                        Documents & downloads

                                                        hide show
                                                        Filter items
                                                        • All

                                                        • CAD Files and Packs

                                                        • Product Brochures

                                                        • Technical Data Catalogues

                                                        • Installation Instruction

                                                        • Handout

                                                        • Data Bulletin

                                                        • End of Life Manual

                                                        • Product Environmental

                                                        • Technical Drawing

                                                        • Declaration of Conformity

                                                        • Certificates (MSDS)

                                                        • eTechPub

                                                        Frequently Asked Questions

                                                        hide show

                                                        What is the difference between the LAD4TB and LAD4TBDL bi-directional peak limiting diode?

                                                        Issue:
                                                        Identifying the difference between LAD4TB and LAD4TBDL

                                                        Product Line:
                                                        IEC contactors and starters

                                                        Environment:
                                                        Products sold and used in the United States

                                                        Cause:
                                                        Identifying the difference between two similar part numbers

                                                        Resolution:
                                                        The LAD4TB is for 24V AC coils for the Tesys Series LC1D09 through LC1D38 contactors when supplied with G7 voltage code. The LAD4TBDL is 24 vdc bi-directional diode offered as a replacement if for some reason the diode supplied with the Tesys LC1D09 through LC1D38 contactors when ordered with BD or BL voltage code breaks or is no longer working.