Product or component type
contactor
Contactor application
motor controlresistive load
Pole contact composition
3 NO
[Ue] rated operational voltage
power circuit: <= 1000 V AC 25...400 Hzpower circuit: <= 300 V DC
[Ie] rated operational current
200 A (at <60 °C) at <= 440 V AC AC-1 for power circuit150 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
Motor power kW
40 kW at 220...230 V AC 50/60 Hz (AC-3)75 kW at 380...400 V AC 50/60 Hz (AC-3)80 kW at 415...440 V AC 50/60 Hz (AC-3)90 kW at 500 V AC 50/60 Hz (AC-3)100 kW at 660...690 V AC 50/60 Hz (AC-3)75 kW at 1000 V AC 50/60 Hz (AC-3)22 kW at 400 V AC 50/60 Hz (AC-4)
Motor power hp
40 hp at 200/208 V AC 50/60 Hz for 3 phases motors50 hp at 230/240 V AC 50/60 Hz for 3 phases motors100 hp at 460/480 V AC 50/60 Hz for 3 phases motors125 hp at 575/600 V AC 50/60 Hz for 3 phases motors
Control circuit type
AC at 50/60 Hz
[Uc] control circuit voltage
120 V AC 50/60 Hz
Auxiliary contact composition
1 NO + 1 NC
[Uimp] rated impulse withstand voltage
8 kV conforming to IEC 60947
[Ith] conventional free air thermal current
200 A (at 60 °C) for power circuit
Irms rated making capacity
140 A AC for signalling circuit conforming to IEC 60947-5-1250 A DC for signalling circuit conforming to IEC 60947-5-11660 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity
1400 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current
250 A 40 °C - 10 min for power circuit580 A 40 °C - 1 min for power circuit1200 A 40 °C - 10 s for power circuit1400 A 40 °C - 1 s for power circuit100 A - 1 s for signalling circuit120 A - 500 ms for signalling circuit140 A - 100 ms for signalling circuit
Associated fuse rating
10 A gG for signalling circuit conforming to IEC 60947-5-1315 A gG at <= 690 V coordination type 1 for power circuit250 A gG at <= 690 V coordination type 2 for power circuit
Average impedance
0.6 mOhm - Ith 200 A 50 Hz for power circuit
[Ui] rated insulation voltage
power circuit: 600 V CSA certifiedpower circuit: 600 V UL certifiedpower circuit: 1000 V conforming to IEC 60947-4-1signalling circuit: 690 V conforming to IEC 60947-1signalling circuit: 600 V CSA certifiedsignalling circuit: 600 V UL certified
Electrical durability
0.85 Mcycles 150 A AC-3 at Ue <= 440 V1 Mcycles 200 A AC-1 at Ue <= 440 V
Power dissipation per pole
Standards
CSA C22.2 No 14EN 60947-4-1EN 60947-5-1IEC 60947-4-1IEC 60947-5-1UL 508
Product certifications
CSAULDNVGOSTRINALROS (Lloyds register of shipping)GLCCCBV
Connections - terminals
control circuit: lugs-ring terminals (external diameter: 8 mm) power circuit: lugs-ring terminals (external diameter: 25 mm) power circuit: bars 1 cable(s) - busbar cross section: 5 x 25 mm
Tightening torque
control circuit: 1.2 N.m - on lugs-ring terminals - with screwdriver flat Ø 6 mm M3.5control circuit: 1.2 N.m - on lugs-ring terminals - with screwdriver Philips No 2 M3.5power circuit: 12 N.m - on lugs-ring terminals hexagonal screw head 13 mm M8power circuit: 12 N.m - on bars hexagonal screw head 13 mm M8
Operating time
20...35 ms closing40...75 ms opening
Safety reliability level
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical durability
8 Mcycles
Maximum operating rate
1200 cyc/h 60 °C
Coil technology
built-in bidirectional peak limiting diode suppressor
Control circuit voltage limits
drop-out: 0.3...0.5 Uc AC 50/60 Hz (at 55 °C)operational: 0.8...1.15 Uc AC 50/60 Hz (at 55 °C)
Inrush power in VA
280-350 VA 60 Hz cos phi 0.9 (at 20 °C)280-350 VA 50 Hz cos phi 0.9 (at 20 °C)
Hold-in power consumption in VA
2-18 VA 60 Hz cos phi 0.9 (at 20 °C)2-18 VA 50 Hz cos phi 0.9 (at 20 °C)
Heat dissipation
3-4.5 W at 50/60 Hz
Auxiliary contacts type
type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1 type mirror contact 1 NC conforming to IEC 60947-4-1
Signalling circuit frequency
25...400 Hz
Minimum switching current
5 mA for signalling circuit
Minimum switching voltage
17 V for signalling circuit
Non-overlap time
1.5 ms on de-energisation between NC and NO contact1.5 ms on energisation between NC and NO contact
Insulation resistance
> 10 MOhm for signalling circuit
Contact compatibility
M13
IP degree of protection
IP20 front face conforming to IEC 60529
Protective treatment
TH conforming to IEC 60068-2-30
Ambient air temperature for operation
-5-60 °C
Ambient air temperature for storage
-60-80 °C
Permissible ambient air temperature around the device
-40-70 °C at Uc
Operating altitude
3000 m without
Fire resistance
850 °C conforming to IEC 60695-2-1
Flame retardance
V1 conforming to UL 94
Mechanical robustness
vibrations contactor open: 2 Gn, 5...300 Hzvibrations contactor closed: 4 Gn, 5...300 Hzshocks contactor closed: 15 Gn for 11 msshocks contactor open: 6 Gn for 11 ms
Sustainable offer status
Green Premium product
REACh Regulation
Free of Substances of Very High Concern above the threshold
EU RoHS Directive
Compliant
RoHS exemption information
Yes
China RoHS Regulation
Product out of China RoHS scope. Substance declaration for your information
Environmental Disclosure
ENVPEP060301EN
Circularity Profile
ENVEOLI100405
WEEE
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
California proposition 65
WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov