TeSys D contactor-3P-AC3 440V 12A 48-130V ACDC coil

TeSys D Contactor-3 Pole AC3 <= 440V 12A, 48 - 130V ACDC Coil

Catalogue Number: LC1D12EHE
TeSys D contactor-3P-AC3 440V 12A 48-130V ACDC coil
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Range of product
TeSys D
Range
TeSys
Product name
TeSys D Green
Product or component type
contactor
Device short name
LC1D
Contactor application
  • motor control
  • resistive load
    • Utilisation category
    • AC-1
    • AC-3
      • Poles description
        3P
        Pole contact composition
        3 NO
        [Ue] rated operational voltage
        power circuit: <= 690 V AC 25...400 Hz
        [Ie] rated operational current
      • 25 A (at <60 °C) at <= 440 V AC-1 for power circuit
      • 12 A (at <60 °C) at <= 440 V AC-3 for power circuit
        • Motor power kW
        • 3 kW at 220...230 V AC 50 Hz (AC-3)
        • 5.5 kW at 380...400 V AC 50 Hz (AC-3)
        • 5.5 kW at 415 V AC 50 Hz (AC-3)
        • 5.5 kW at 440 V AC 50 Hz (AC-3)
        • 7.5 kW at 500 V AC 50 Hz (AC-3)
        • 7.5 kW at 660...690 V AC 50 Hz (AC-3)
          • Motor power hp
          • 0.5 hp at 115 V AC 60 Hz for 1 phase motors
          • 2 hp at 230/240 V AC 60 Hz for 1 phase motors
          • 3 hp at 200/208 V AC 60 Hz for 3 phases motors
          • 3 hp at 230/240 V AC 60 Hz for 3 phases motors
          • 7.5 hp at 460/480 V AC 60 Hz for 3 phases motors
          • 10 hp at 575/600 V AC 60 Hz for 3 phases motors
            • Control circuit type
              AC/DC at 50/60 Hz AC/DC electronic
              [Uc] control circuit voltage
            • 48...130 V AC 50/60 Hz
            • 48...130 V DC
              • Coil type
                AC/DC electronic
                Auxiliary contact composition
                1 NO + 1 NC
                [Uimp] rated impulse withstand voltage
                6 kV conforming to IEC 60947
                Overvoltage category
                III
                [Ith] conventional free air thermal current
              • 10 A (at 60 °C) for signalling circuit
              • 25 A (at 60 °C) for power circuit
                • Irms rated making capacity
                • 250 A at 440 V for power circuit conforming to IEC 60947
                • 140 A AC for signalling circuit conforming to IEC 60947-5-1
                • 250 A DC for signalling circuit conforming to IEC 60947-5-1
                  • Rated breaking capacity
                    250 A at 440 V for power circuit conforming to IEC 60947
                    [Icw] rated short-time withstand current
                  • 100 A - 1 s for signalling circuit
                  • 120 A - 500 ms for signalling circuit
                  • 140 A - 100 ms for signalling circuit
                  • 30 A 40 °C - 10 min for power circuit
                  • 61 A 40 °C - 1 min for power circuit
                  • 105 A 40 °C - 10 s for power circuit
                  • 210 A 40 °C - 1 s for power circuit
                    • Associated fuse rating
                    • 10 A gG for signalling circuit conforming to IEC 60947-5-1
                    • 40 A gG at <= 690 V coordination type 1 for power circuit
                    • 25 A gG at <= 690 V coordination type 2 for power circuit
                      • Average impedance
                        2.5 mOhm - Ith 25 A 50 Hz for power circuit
                        [Ui] rated insulation voltage
                      • power circuit: 690 V conforming to IEC 60947-4-1
                      • signalling circuit: 690 V conforming to IEC 60947-1
                        • Electrical durability
                        • 2.3 Mcycles 11 A AC-3 at Ue <= 440 V
                        • 0.8 Mcycles 25 A AC-1 at Ue <= 440 V
                          • Power dissipation per pole
                          • 1.56 W AC-1
                          • 0.36 W AC-3
                            • Protective cover
                              with
                              Mounting support
                            • plate
                            • rail
                              • Standards
                              • EN/IEC 60947-4-1
                              • EN/IEC 60947-5-1
                              • UL 60947-4-1
                              • CSA C22.2 No 60947-4-1
                                • Product certifications
                                • CCC
                                • CSA
                                • EAC
                                • UL
                                • KC
                                • DNV-GL
                                • LROS (Lloyds register of shipping)
                                  • Connections - terminals
                                  • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
                                  • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
                                  • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
                                  • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
                                  • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid
                                  • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid
                                  • power circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
                                  • power circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
                                  • power circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
                                  • power circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
                                  • power circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid
                                  • power circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid
                                    • Tightening torque
                                    • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                                    • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
                                    • power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                                    • power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
                                      • Operating time
                                      • 45...55 ms closing
                                      • 20...90 ms opening
                                        • Safety reliability level
                                        • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                                        • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                                          • Mechanical durability
                                            15 Mcycles
                                            Maximum operating rate
                                            3600 cyc/h 60 °C
                                            Coil technology
                                            built-in bidirectional peak limiting
                                            Control circuit voltage limits
                                          • <= 0.1 Uc 60-60 °C drop-out
                                          • 0.85...1.1 Uc 60-60 °C operational
                                            • Inrush power in VA
                                              25-25 VA 50/60 Hz (at 20 °C)
                                              Inrush power in W
                                              24-24 W at 20 °C
                                              Hold-in power consumption in VA
                                              1.3-1.3 VA (at 20 °C) 50/60 Hz
                                              Hold-in power consumption in W
                                              0.8-0.8 W at 20 °C
                                              Heat dissipation
                                              0.8-0.8 W at 50/60 Hz
                                              Auxiliary contacts type
                                            • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
                                            • type mirror contact 1 NC conforming to IEC 60947-4-1
                                              • Signalling circuit frequency
                                                25...400 Hz
                                                Minimum switching current
                                                5 mA for signalling circuit
                                                Minimum switching voltage
                                                17 V for signalling circuit
                                                Non-overlap time
                                              • 1.5 ms on de-energisation between NC and NO contact
                                              • 1.5 ms on energisation between NC and NO contact
                                                • Insulation resistance
                                                  > 10 MOhm for signalling circuit
                                                  Compatibility code
                                                  LC1D
                                                  IP degree of protection
                                                  IP20 front face conforming to IEC 60529
                                                  Protective treatment
                                                  TH conforming to IEC 60068-2-30
                                                  Pollution degree
                                                  3
                                                  Ambient air temperature for operation
                                                  -25-60 °C
                                                  Ambient air temperature for storage
                                                  -60-80 °C
                                                  Permissible ambient air temperature around the device
                                                  -40-70 °C at Uc
                                                  Operating altitude
                                                  3000 m without
                                                  Fire resistance
                                                  850 °C conforming to IEC 60695-2-1
                                                  Flame retardance
                                                  V1 conforming to UL 94
                                                  Mechanical robustness
                                                • vibrations contactor open: 2 Gn, 5...300 Hz
                                                • vibrations contactor closed: 4 Gn, 5...300 Hz
                                                • shocks contactor open: 10 Gn for 11 ms
                                                • shocks contactor closed: 15 Gn for 11 ms
                                                  • Height
                                                    77 mm
                                                    Width
                                                    45 mm
                                                    Depth
                                                    86 mm
                                                    Net weight
                                                    0.373 kg
                                                    Sustainable offer status
                                                    Green Premium product
                                                    EU RoHS Directive
                                                    Compliant
                                                    Mercury free
                                                    Yes
                                                    RoHS exemption information
                                                    Yes
                                                    China RoHS Regulation
                                                    Product out of China RoHS scope. Substance declaration for your information
                                                    Environmental Disclosure
                                                    ENVPEP1609001EN
                                                    Circularity Profile
                                                    ENVEOLI1609001EN
                                                    WEEE
                                                    The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                                                    Halogen content performance
                                                    Halogen free plastic parts & cables product
                                                    Warranty
                                                    18 months

                                                    Documents & downloads

                                                    hide show
                                                    Filter items
                                                    • All

                                                    • Product Brochures

                                                    • CAD Files and Packs

                                                    • Technical Data Catalogues

                                                    • Product Environmental

                                                    • End of Life Manual

                                                    • Installation Instruction

                                                    • Data Bulletin

                                                    • Declaration of Conformity

                                                    Frequently Asked Questions

                                                    hide show

                                                    What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

                                                    Issue:
                                                    Identifying maximum power voltage of an LC1D contactor

                                                    Product Line:
                                                    Digest 177 Section 18: IEC Contactors

                                                    Environment:
                                                    Products sold and used in the United States

                                                    Cause:
                                                    Identifying ratings per UL and CSA

                                                    Resolution:
                                                    It is 600Vac.


                                                     

                                                    What is the replacement coil part number for the LC*D09 through LC*D32 and LC*DT20 through LC*DT40 TeSys contactors?

                                                    Issue:
                                                    Identifying replacement coils for tesys D non-reversing and reversing conactors

                                                    Product Line:
                                                    IEC Contactors and Starters

                                                    Environment:
                                                    Products sold and used in the United States

                                                    Cause:
                                                    Replacement coil is needed

                                                    Resolution:
                                                    DC replacement coils are not available.
                                                    AC Coils are 50/60 hertz for voltages as listed below:

                                                    Volts - Part Number
                                                    12 ____ LXD1J7
                                                    21 ____ LXD1Z7
                                                    24 ____ LXD1B7
                                                    32 ____ LXD1C7
                                                    36 ____ LXD1CC7
                                                    42 ____ LXD1D7
                                                    48 ____ LXD1E7
                                                    60 ____ LXD1EE7
                                                    100 ___ LXD1K7 ( never brought to North America )
                                                    110 ___ LXD1F7
                                                    115 ___ LXD1FE7
                                                    120 ___ LXD1G7
                                                    127 ___ LXD1FC7
                                                    200 ___ LXD1L7
                                                    208 ___ LXD1LE7
                                                    220 ___ LXD1M7
                                                    230 ___ LXD1P7
                                                    240 ___ LXD1U7
                                                    277 ___ LXD1W7
                                                    380 ___ LXD1Q7
                                                    400 ___ LXD1V7
                                                    415 ___ LXD1N7
                                                    440 ___ LXD1R7
                                                    480 ___ LXD1T7
                                                    575 ___ LXD1SC7
                                                    600 ___ LXD1X7
                                                    690 ___ LXD1Y7


                                                    Note: A contactor with an AC coil can be changed to a different AC voltage coil, IE you can take an LC1D09 with a 120VAC coil and put a 24VAC coil in it instead. An AC device cannot be switched to a DC coil, and a DC device cannot be switches to an AC coil. 

                                                    What is the altitude derating for a TeSys D-Line contactor?

                                                    Issue:​
                                                    What is the altitude derating for a TeSys D-Line contactor?

                                                    Product Line:
                                                    Digest 177 Section 18 : Contactors and Starters, IEC

                                                    Environment:
                                                    North American Products

                                                    Resolution:
                                                    The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

                                                    Voltage
                                                    3500m x 0.90
                                                    4000m x 0.80
                                                    4500m x 0.70
                                                    5000m x 0.60

                                                    Current
                                                    3500m x 0.92
                                                    4000m x 0.90
                                                    4500m x 0.88
                                                    5000m x 0.86

                                                    For example, an LC1D80 at 5000 meters:
                                                    - The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
                                                    - The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



                                                     

                                                    What is the power terminal lug data for the LC1D09, LC1DT20, LC1D12, and LC1DT25 contactor?

                                                    Issue:
                                                    Power terminal lug data required for the 9 and 12 amp rated Tesys D contactors

                                                    Product Line:
                                                    NEMA combination starters

                                                    Environment:
                                                    Products sold and used in the United States

                                                    Resolution:
                                                    For contactors with screw clamp terminals:
                                                    stranded cable w/o cable end : One or Two #18-10 AWG per terminal.
                                                    stranded cable w/cable end: One or Two #18-10 AWG per terminal.
                                                    solid cable: One or Two #18-8 AWG per terminal.

                                                    What is the replacement for a LP1D1210BD

                                                    You can use a LC1D12BD or for low consumption a LC1D12BL.

                                                    Will the LAD** time delay auxiliary contact module fit the D2 series pre-Tesys contactors?

                                                    Issue:
                                                    Can new accessories be used on older style contactors

                                                    Product Line:
                                                    IEC contactors and starters

                                                    Environment:
                                                    Products sold and used in the United States

                                                    Cause:
                                                    Identifying product compatibility

                                                    Resolution:
                                                    Yes, all front mount D2 and Tesys series auxiliary modules are backward forward compatible.


                                                     

                                                    Video: What auxiliary contact modules are available for the LC1D and LC2D contactors?

                                                    Issue:
                                                    Auxiliary contact modules for the LC1D and LC2D contactors

                                                    Product Line: 
                                                    Contactor and Starters - IEC

                                                    Environment:
                                                    North American Products

                                                    Resolution:
                                                    Select based on application requirements. Please note that the TeSys and Pre-TeSys auxiliary blocks are backward/forward compatible.
                                                    Front Mounting; maximum of 1 block per contactor:

                                                    N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
                                                    --1-----------1---------LADN11-----------LA1DN11
                                                    --1-----------1---------LADN11G---------LA1DN11G (See Footnote 1)
                                                    --1-----------1---------LADN11P---------LA1DN11P (See Footnote 1)
                                                    --2-----------0---------LADN20-----------LA1DN20
                                                    --2-----------0---------LA1DX20---------LA1DX20 (See Footnote 2)
                                                    --2-----------0---------LA1DY20---------LA1DY20 (See Footnote 3)
                                                    --0-----------2---------LADN02-----------LA1DN02
                                                    --2-----------2---------LADN22-----------LA1DN22
                                                    --2-----------2---------LADN22G---------LA1DN22G (See Footnote 1)
                                                    --2-----------2---------LADN22P---------LA1DN22P (See Footnote 1)
                                                    --2-----------2---------LADC22------------LA1DC22 (See Footnote 4)
                                                    --3-----------1---------LADN31------------LA1DN31
                                                    --3-----------1---------LA1DZ31----------LA1DZ31 (See Footnote 5)
                                                    --1-----------3---------LADN13------------LA1DN13
                                                    --4-----------0---------LADN40------------LA1DN40
                                                    --4-----------0---------LA1DZ40-----------LA1DZ40 (See Footnote 6)
                                                    --0-----------4---------LADN04------------LA1DN04




                                                    Front Mounting; maximum of 1 block per contactor: For use with D2 Series 25 amp through 80 amp contactors and TeSys Series 40 amp through 80 amp only.

                                                    N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
                                                    --1-----------0--------LADN10----------LA1DN10
                                                    --0-----------1--------LADN01----------LA1DN01

                                                    Side Mounting; maximum of 1 block on each side for D2 Series and Tesys Series 40 through 80 amp contactors. Tesys 9 through 32, 115, and 150 amps contactors will accept 1 block and is limited to left side only. (*) DC control devices will not accept side mount auxiliaries.
                                                    (*) DC control exceptions that will accept one left side mounted auxiliary: LC1D115 & LC1D150.

                                                    N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
                                                    --1-----------1--------LAD8N11----------LA8DN11
                                                    --2-----------0--------LAD8N20----------LA8DN20
                                                    --0-----------2--------LAD8N02----------N/A

                                                    Footnotes:
                                                    {1} EN50 012 Machine Tool Terminal Markings
                                                    {2} (2) NO Sealed Dust Tight Contacts
                                                    {3} Gold Flash Contacts
                                                    {4} (1) NO & (1) NC Standard and (1) NO & (1) NC Make Before Break
                                                    {5} (2) NO Dust Tight Contacts & (1) NO & (1) NC Standard Contacts
                                                    {6} (2) NO Dust Tight Contacts & (2) NO Standard Contacts

                                                    What does the (3) designate in the part number LC1D123G7?

                                                    For spring termination versions, add (3) to the catalog number prior to adding the voltage code. (ex. LC1D12G7 becomes a LC1D123G7 or LC1D40AG7 becomes LC1D40A3G7). This applies only for the LC1D09 - LC1D65A contactors. Note: For the LC1D40A to D65A, the spring terminals are only on the control terminations and not on power terminations.



                                                    CTA-ID : 2053127

                                                    Are the D-Line contactors rated to break DC voltages?

                                                    Issue: 
                                                    Can the TeSys D line be used to control DC loads? 

                                                    Product Line:
                                                    Tesys D contactors

                                                    Environment:
                                                    Products sold and used in the United States
                                                     
                                                    Cause:
                                                     DC power circuit
                                                     
                                                    Resolution:
                                                     
                                                    Yes, 75 VDC (125 VDC for D115 & D150) per pole which means that through a four pole device breaking 300 VDC is possible by wiring all four power poles in series. However, be aware that the device current ratings will differ according to the number of poles in series and the type of application.

                                                    Devices are suitable but not UL Listed for DC applications.

                                                    More information on their DC ratings can be found in the current TeSys Motor Control and Protection Compentns catalog: https://www.schneider-electric.us/en/download/document/MKTED210011EN/


                                                     

                                                    What is the difference between the LAD4TB and LAD4TBDL bi-directional peak limiting diode?

                                                    Issue:
                                                    Identifying the difference between LAD4TB and LAD4TBDL

                                                    Product Line:
                                                    IEC contactors and starters

                                                    Environment:
                                                    Products sold and used in the United States

                                                    Cause:
                                                    Identifying the difference between two similar part numbers

                                                    Resolution:
                                                    The LAD4TB is for 24V AC coils for the Tesys Series LC1D09 through LC1D38 contactors when supplied with G7 voltage code. The LAD4TBDL is 24 vdc bi-directional diode offered as a replacement if for some reason the diode supplied with the Tesys LC1D09 through LC1D38 contactors when ordered with BD or BL voltage code breaks or is no longer working.


                                                     

                                                    Will the LC1D12U7 contactor go with the LADR2 timer?

                                                    Yes it will. the LADR2 timer slides on the top of the LC1D12U7 contactor.

                                                    What is the mechanical durability of a LC1D12U7 contactor

                                                     It is 15 Million cycles

                                                    Will a LC1D12F7 operate on 60V DC as a control voltage

                                                    No it will not

                                                    What is the rating of auxiliaries on standard LC1D12U7 contactor

                                                     Rated at 10A thermal.

                                                    What are the coil voltage codes for the LC1D09 / LC2D09 through LC1D38 / LC2D38 TeSys contactors?

                                                    Issue:
                                                    What are the coil voltage codes for the LC1D09 / LC2D09through LC1D38 / LC2D38 TeSys contactors?

                                                    Product Line:
                                                    IEC Contactors

                                                    Environment:
                                                    Ordering

                                                    Cause:
                                                    Selection

                                                    Resolution:
                                                    The following lists the more common voltage suffix codes for these product lines.  For a more comprehensive list and to determine compatibility with a given product, refer to the catalog below.

                                                    AC Volts ___Code     AC Volts ___Code
                                                    12 ___ J7                   208 ___ LE7
                                                    21 ___ Z7                   220 ___ M7
                                                    24 ___ B7                  230 ___ P7
                                                    32 ___ C7                  240 ___ U7
                                                    36 ___ CC7               277 ___ W7
                                                    42 ___ D7                  380 ___ Q7
                                                    48 ___ E7                   400 ___ V7
                                                    60 ___ EE7                415 ___ N7
                                                    100 ___ K7                440 ___ R7
                                                    110 ___ F7                480 ___ T7
                                                    115 ___ FE7              575 ___ SC7
                                                    120 ___ G7                600 ___ X7
                                                    127 ___ FC7              690 ___ Y7
                                                    200 ___ L7                
                                                                   
                                                    Standard Coil                Low Consumption
                                                    DC Volts ___Code          DC Volts ___Code
                                                    12 ___ JD                           5 ___ AL
                                                    24 ___ BD                         12 ___ JL
                                                    36 ___ CD                         20 ___ ZL
                                                    48 ___ ED                         24 ___ BL
                                                    60 ___ ND                         48 ___ EL
                                                    72 ___ SD                         72 ___ SL
                                                    110 ___ FD                       96 ___ DL
                                                    125 ___ GD                     110 ___ FL
                                                    220 ___ MD                    220 ___ ML
                                                    250 ___ UD                     250 ___ UL
                                                    440 ___ RD                

                                                    What is the Mechanical Interlock for the LC1D12F7 ?

                                                    LAD9R1V Is the code for the Mechanical and Electrical Interlock kit.

                                                    I have a LC1D12BD contactor and want to fit a LA4DFB to it

                                                     You need to use a LAD4BB adaptor

                                                    What is the difference between LC1D115 and LC1D1156?

                                                    The 6 in LC1D1156.. is that the 6 denotes lug bar terminals. Use LC1D115.. for cable connections.


                                                     

                                                    Are contactors LC1D09U7 and LC1D12U7 the same size?

                                                    Contactors LC1D09 , LC1D12 Aand LC1D18 are all exactly the same physical size with AC coils.
                                                    Height = 77mm
                                                    Width = 45mm
                                                    Depth = 86mm

                                                    What is the part number for the mechanical interlock to suit the LC1D12U7?

                                                    The part number for the mechanical interlock to suit the LC1D12U7 is "LAD9V2"

                                                    https://www.schneider-electric.com.au/en/search/LAD9V2



                                                     

                                                    Are there replacement dc coils available for LC1D12BD

                                                    They are not available as a spare part for the LC1D09-D38 Contactors
                                                     

                                                    What is the coil consumption or burden for the Tesys LC*D** contactors?

                                                    * 1 or 2
                                                    ** 09 through 38

                                                    Issue:
                                                    Coil consumption or burden for the Tesys LC1D/2D contactors from 9A - 38A

                                                    Product Line: 
                                                    Contactors and Starters - IEC

                                                    Environment:
                                                    North American Products

                                                    Resolution:
                                                    All AC coils for the LC1D09 through LC1D38 3-pole contactors ( including ring tongue, quick connect and spring terminal versions ) have an inrush of 70 volt-amps for either 50 or 60 Hertz applications, and a sealed value of 7 volt-amps for 50Hertz applications or 7.5 volt-amps for 60 Hertz applications.

                                                    What is the AC3 rating of the LC1D18***

                                                     The rating is 18A

                                                    Can a side mounted auxiliary be fitted to LC1D18BD?

                                                    No a side mounted auxiliary cannot be fitted to LC1D18BD.

                                                     

                                                    What is the part number for a spare coil LC1D123 contactor?

                                                    Spare 240V coil for LC1D123 contactor is same as for LC1D12 contactor......LXD1U7
                                                    see data sheet......https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=lxd1u7
                                                    User-added image

                                                    What is the code for the 240VAC Coil for the LC1D32 Contactor ?

                                                    Part Code = LXD1U7 
                                                    The LXD1U7 also fits the LC1D09 - D38 Contactors

                                                    Will the LAD4BB adapter work with a LC1D12BD contactor?

                                                    Issue:
                                                    Can we use the LAD4BB with the LC1D12BD?

                                                    Product Line:
                                                    IEC contactors and starters

                                                    Environment:
                                                    Products sold and used in the United States

                                                    Cause:
                                                    Identifying product compatibility

                                                    Resolution:
                                                    The LAD4BB will not work on the DC contactors, just the AC contactors.
                                                     

                                                    What is the part number for the contactor that replaces the LC1D50E5?

                                                    The part number for the contactor that replaces the LC1D50E5 is - LC1D50AE7

                                                    For further information , visit link below:-
                                                    https://www.schneider-electric.com.au/en/search/LC1D50AE7
                                                     

                                                    What is the part code for a 4P AC-1 rated 20Amp 24V ac coil contactor

                                                     The part code is LC1DT20B7

                                                    What is the difference between the LC1D1506N7 and the LC1D150N7?

                                                    The LC1D1506N7 can accept 5X25mm Bars aswell as Lugs or ring terminals. The LC1D150N7 only accepts cable lugs upto 120mm2.

                                                    What is the difference between the LC1D25E7 and LC1D258E7?

                                                    The LC1D25E7 is a 3 Poles 25 Amps (AC-3) Contactor

                                                    Where as

                                                    The LC1D258E7 is a 4 Pole (2NO + 2NC) 25 Amps (AC-3) Contactor

                                                    https://www.schneider-electric.com.au/en/search/LC1D25E7

                                                    What is the part number for the replacement contactor for the LC1D1210N7?

                                                    The part number for the replacement contactor for the LC1D1210N7 is - LC1D12N7

                                                    For further information, visit the link below:-
                                                    https://www.schneider-electric.com.au/en/search/LC1D12N7
                                                    User-added image

                                                    What is the part number for 4 pole, 415V Coil contactor and 3A overload?

                                                    The part number for 4 pole, 415V Coil contactor and 3A overload is LC1DT20N7 and LRD08



                                                    For more information on either item refer to:
                                                    https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LC1DT20N7
                                                    https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LRD08

                                                    What is the Tesys D-Line maximum frequency for Power Poles?

                                                    Issue:
                                                    Checking on the maximum Hz voltage that can be applied to the Tesys D-line contactors.

                                                    Product Line:
                                                    Tesys D Contactors

                                                    Environment:
                                                    IEC Contactors and Starters

                                                    Cause:
                                                    Product Characteristics

                                                    Resolution:
                                                    These units have been tested for frequencies 25Hz to 400hz within the operational current of the device .  No testing has been done beyond this frequency.

                                                    Does the 150A IEC contactor LC1D150BD with a 24 volt DC coil have a coil suppressor built in?

                                                    Issue: 
                                                    Does the LC1D150 with a DC coil include suppression? 

                                                    Product Line:
                                                     Tesys D line contactors and accessories

                                                    Environment:
                                                    Products sold and used in the United States
                                                     
                                                    Cause:
                                                     Identifying components and accessories
                                                     
                                                    Resolution:
                                                     
                                                    Yes. Suppression is built into the 150A DC contactor coil.
                                                     

                                                    What is the largest amperage D Line IEC contactor that can accomodate spring terminals, using a ``3`` after the amperage in the part number, such as an LC1D123G7?

                                                    The ``3`` form for spring terminals is available on 65A and below IEC contactors. On the 40, 50 and 65 amp devices the spring terminals are on the control circuit only. It is not available on 80A, 115A or 150A D Line contactors.


                                                    CTA-ID : 2053331

                                                    Are replacement contacts available for LC1D115?

                                                    Issue:
                                                    Replacement contacts needed for 115 amp D line contactor

                                                    Product Line:
                                                    IEC contactors and starters

                                                    Environment:
                                                    Products sold and used in the United States

                                                    Cause:
                                                    Identifying part number to order replacement contact kit

                                                    Resolution:
                                                    Yes, order LA5D1158031 for 3 pole kit or LA5D115804 for 4 pole kit.


                                                    CTA-ID : 11125

                                                    What is the replacement for the LR2D1316 to fit the LC1D12U7 Contactor?

                                                    The replacement for the LR2D1316 to fit the LC1D12U7 Contactor is "LRD16"

                                                    https://www.schneider-electric.com.au/en/search/LRD16