TeSys LC1D115 or LC1D150 contactor, 3 poles, screw clamp terminals or lugs, with cover, 115A or 150A

LC1D1156U5

TeSys D Contactor, 3P(3 NO), AC-3, <= 440V, 115A, 240VAC, 50 Hz Coil

TeSys LC1D115 or LC1D150 contactor, 3 poles, screw clamp terminals or lugs, with cover, 115A or 150A
Colour:
Colour: Per UOM Std.
  • 1 PCE
Added to cart
Successfully added, you can view your cart here

Key Features & Specifications

hide show
Range of product
TeSys D
Range
TeSys
Product name
TeSys D
Product or component type
contactor
Device short name
LC1D
Contactor application
  • motor control
  • resistive load
    • Utilisation category
    • AC-3
    • AC-1
    • AC-4
      • Poles description
        3P
        Pole contact composition
        3 NO
        [Ue] rated operational voltage
      • power circuit: <= 1000 V AC 25...400 Hz
      • power circuit: <= 300 V DC
        • [Ie] rated operational current
        • 200 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
        • 115 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
          • Motor power kW
          • 30 kW at 220...230 V AC 50/60 Hz (AC-3)
          • 55 kW at 380...400 V AC 50/60 Hz (AC-3)
          • 59 kW at 415...440 V AC 50/60 Hz (AC-3)
          • 75 kW at 500 V AC 50/60 Hz (AC-3)
          • 80 kW at 660...690 V AC 50/60 Hz (AC-3)
          • 65 kW at 1000 V AC 50/60 Hz (AC-3)
          • 18.5 kW at 400 V AC 50/60 Hz (AC-4)
            • Motor power hp
            • 30 hp at 200/208 V AC 50/60 Hz for 3 phases motors
            • 40 hp at 230/240 V AC 50/60 Hz for 3 phases motors
            • 75 hp at 460/480 V AC 50/60 Hz for 3 phases motors
            • 100 hp at 575/600 V AC 50/60 Hz for 3 phases motors
              • Control circuit type
                AC at 50 Hz
                [Uc] control circuit voltage
                240 V AC 50 Hz
                Auxiliary contact composition
                1 NO + 1 NC
                [Uimp] rated impulse withstand voltage
                8 kV conforming to IEC 60947
                Overvoltage category
                III
                [Ith] conventional free air thermal current
                200 A (at 60 °C) for power circuit
                Irms rated making capacity
              • 1260 A at 440 V for power circuit conforming to IEC 60947
              • 140 A AC for signalling circuit conforming to IEC 60947-5-1
              • 250 A DC for signalling circuit conforming to IEC 60947-5-1
                • Rated breaking capacity
                  1100 A at 440 V for power circuit conforming to IEC 60947
                  [Icw] rated short-time withstand current
                • 250 A 40 °C - 10 min for power circuit
                • 550 A 40 °C - 1 min for power circuit
                • 950 A 40 °C - 10 s for power circuit
                • 1100 A 40 °C - 1 s for power circuit
                • 100 A - 1 s for signalling circuit
                • 120 A - 500 ms for signalling circuit
                • 140 A - 100 ms for signalling circuit
                  • Associated fuse rating
                  • 250 A gG at <= 690 V coordination type 1 for power circuit
                  • 200 A gG at <= 690 V coordination type 2 for power circuit
                  • 10 A gG for signalling circuit
                    • Average impedance
                      0.6 mOhm - Ith 200 A 50 Hz for power circuit
                      [Ui] rated insulation voltage
                    • power circuit: 600 V CSA certified
                    • power circuit: 600 V UL certified
                    • power circuit: 1000 V conforming to IEC 60947-4-1
                    • signalling circuit: 690 V conforming to IEC 60947-1
                    • signalling circuit: 600 V CSA certified
                    • signalling circuit: 600 V UL certified
                      • Electrical durability
                      • 0.8 Mcycles 200 A AC-1 at Ue <= 440 V
                      • 0.95 Mcycles 115 A AC-3 at Ue <= 440 V
                        • Power dissipation per pole
                        • 24 W AC-1
                        • 7.9 W AC-3
                          • Protective cover
                            with
                            Mounting support
                          • rail
                          • plate
                            • Standards
                            • CSA C22.2 No 14
                            • EN 60947-4-1
                            • EN 60947-5-1
                            • IEC 60947-4-1
                            • IEC 60947-5-1
                            • UL 508
                              • Product certifications
                              • GOST
                              • CSA
                              • LROS (Lloyds register of shipping)
                              • UL
                              • RINA
                              • DNV
                              • BV
                              • GL
                              • CCC
                                • Connections - terminals
                                • control circuit: lugs-ring terminals (external diameter: 8 mm)
                                • power circuit: lugs-ring terminals (external diameter: 25 mm)
                                • power circuit: bars 1 cable(s) - busbar cross section: 5 x 25 mm
                                  • Tightening torque
                                  • control circuit: 1.2 N.m - on lugs-ring terminals - with screwdriver flat Ø 6 mm M3.5
                                  • control circuit: 1.2 N.m - on lugs-ring terminals - with screwdriver Philips No 2 M3.5
                                  • power circuit: 12 N.m - on lugs-ring terminals hexagonal screw head 13 mm M8
                                  • power circuit: 12 N.m - on bars hexagonal screw head 13 mm M8
                                    • Operating time
                                    • 6...20 ms opening
                                    • 20...50 ms closing
                                      • Safety reliability level
                                      • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                                      • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                                        • Mechanical durability
                                          8 Mcycles
                                          Maximum operating rate
                                          2400 cyc/h 60 °C
                                          Coil technology
                                          without built-in suppressor module
                                          Control circuit voltage limits
                                        • drop-out: 0.3...0.6 Uc AC 50 Hz (at 55 °C)
                                        • operational: 0.85...1.1 Uc AC 50 Hz (at 55 °C)
                                          • Inrush power in VA
                                            300-300 VA 50 Hz cos phi 0.8 (at 20 °C)
                                            Hold-in power consumption in VA
                                            22-22 VA 50 Hz cos phi 0.3 (at 20 °C)
                                            Heat dissipation
                                            3-8 W at 50 Hz
                                            Auxiliary contacts type
                                          • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
                                          • type mirror contact 1 NC conforming to IEC 60947-4-1
                                            • Signalling circuit frequency
                                              25...400 Hz
                                              Minimum switching current
                                              5 mA for signalling circuit
                                              Minimum switching voltage
                                              17 V for signalling circuit
                                              Non-overlap time
                                            • 1.5 ms on de-energisation between NC and NO contact
                                            • 1.5 ms on energisation between NC and NO contact
                                              • Insulation resistance
                                                > 10 MOhm for signalling circuit
                                                Contact compatibility
                                                M13
                                                Compatibility code
                                                LC1D
                                                IP degree of protection
                                                IP20 front face conforming to IEC 60529
                                                Protective treatment
                                                TH conforming to IEC 60068-2-30
                                                Pollution degree
                                                3
                                                Ambient air temperature for operation
                                                -5-60 °C
                                                Ambient air temperature for storage
                                                -60-80 °C
                                                Permissible ambient air temperature around the device
                                                -40-70 °C at Uc
                                                Operating altitude
                                                3000 m without
                                                Fire resistance
                                                850 °C conforming to IEC 60695-2-1
                                                Flame retardance
                                                V1 conforming to UL 94
                                                Mechanical robustness
                                              • vibrations contactor open: 2 Gn, 5...300 Hz
                                              • vibrations contactor closed: 4 Gn, 5...300 Hz
                                              • shocks contactor closed: 15 Gn for 11 ms
                                              • shocks contactor open: 6 Gn for 11 ms
                                                • Height
                                                  158 mm
                                                  Width
                                                  120 mm
                                                  Depth
                                                  136 mm
                                                  Net weight
                                                  2.5 kg
                                                  Sustainable offer status
                                                  Green Premium product
                                                  REACh Regulation
                                                  Reference contains Substances of Very High Concern above the threshold
                                                  EU RoHS Directive
                                                  Pro-active compliance (Product out of EU RoHS legal scope)
                                                  Mercury free
                                                  Yes
                                                  RoHS exemption information
                                                  Yes
                                                  China RoHS Regulation
                                                  Product out of China RoHS scope. Substance declaration for your information
                                                  Environmental Disclosure
                                                  ENVPEP060301EN
                                                  Circularity Profile
                                                  ENVEOLI100405
                                                  WEEE
                                                  The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                                                  Warranty
                                                  18 months

                                                  Documents & downloads

                                                  hide show
                                                  Filter items
                                                  • All

                                                  • CAD Files and Packs

                                                  • Product Brochures

                                                  • Movies

                                                  • Catalog Page

                                                  • Technical Data Catalogues

                                                  • Technical Leaflet

                                                  • End of Life Manual

                                                  • Product Environmental

                                                  • Installation Instruction

                                                  • Handout

                                                  • Data Bulletin

                                                  • Operating Manuals

                                                  • Application Solutions

                                                  • Certificates (MSDS)

                                                  • Declaration of Conformity

                                                  • White Paper

                                                  • Marine Certificate

                                                  • eTechPub

                                                  • Software - Released