What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

Issue:
Identifying maximum voltage of an LC1D contactor

Product Line:
TeSys D Contactors

Environment:
IEC contactors and starters used in North America

Cause:
n/a

Resolution:
IThe maximum voltage per UL and CSA is 600VAC. 
 

What is the replacement coil part number for the LC*D09 through LC*D32 and LC*DT20 through LC*DT40 TeSys contactors?

Issue:
Identifying replacement coils for tesys D non-reversing and reversing conactors

Product Line:
IEC Contactors and Starters

Environment:
Products sold and used in the United States

Cause:
Replacement coil is needed

Resolution:
DC replacement coils are not available.
AC Coils are 50/60 hertz for voltages as listed below:

Volts - Part Number
12 ____ LXD1J7
21 ____ LXD1Z7
24 ____ LXD1B7
32 ____ LXD1C7
36 ____ LXD1CC7
42 ____ LXD1D7
48 ____ LXD1E7
60 ____ LXD1EE7
100 ___ LXD1K7 ( never brought to North America )
110 ___ LXD1F7
115 ___ LXD1FE7
120 ___ LXD1G7
127 ___ LXD1FC7
200 ___ LXD1L7
208 ___ LXD1LE7
220 ___ LXD1M7
230 ___ LXD1P7
240 ___ LXD1U7
277 ___ LXD1W7
380 ___ LXD1Q7
400 ___ LXD1V7
415 ___ LXD1N7
440 ___ LXD1R7
480 ___ LXD1T7
575 ___ LXD1SC7
600 ___ LXD1X7
690 ___ LXD1Y7


Note: A contactor with an AC coil can be changed to a different AC voltage coil, IE you can take an LC1D09 with a 120VAC coil and put a 24VAC coil in it instead. An AC device cannot be switched to a DC coil, and a DC device cannot be switches to an AC coil. 

What is the difference between LC1D115 and LC1D1156?

The 6 in LC1D1156.. is that the 6 denotes lug bar terminals. Use LC1D115.. for cable connections.


 

Where are the control coil terminals for TeSys LC1D09 to LC1D38 contactor?

Issue:
Determine the control coil terminal marking and location on LC1D09 to LC1D38 contactor

Product Line: 
Tesys D Contactors

Environment:
IEC contactors

Resolution:
The coil terminals are marked A1 and A2, you can see them on the front of the contactor on the white part (control section).  They are next to the auxiliary contact (13/14, 21/22) terminals.
 

What is the difference between the LC1D1506N7 and the LC1D150N7?

The LC1D1506N7 can accept 5X25mm Bars aswell as Lugs or ring terminals. The LC1D150N7 only accepts cable lugs upto 120mm2.

Does the LC1D1156U7 come with 1NO & 1NC Aux contact

Yes - all the D range contactors have one of each aux contact

What is the terminal shroud part number for a LC1D1156**

The part code is LA9D115703

What is the code for a contactor rated at 100A AC3 with a 240V AC coil ?

Code = LC1D1156U7 ( 3 Pole Contactor comes with 1 N/C + 1 N/O Auxilliary as a standard ) 

What is the part number for the 415V AC Coil for the LC1D1156 Contactor?

The part number for the 415V AC Coil for the LC1D1156 Contactor is "LX1D8N7"

https://www.schneider-electric.com.au/en/search/lx1d8n7


 

What is the interlock to use with the lcd1156**

 The interlock is LA9D11502

Are the D-Line contactors rated to break DC voltages?

Issue: 
Can the TeSys D line be used to control DC loads? 

Product Line:
Tesys D contactors

Environment:
Products sold and used in the United States
 
Cause:
 DC power circuit
 
Resolution:
 
Yes, 75 VDC (125 VDC for D115 & D150) per pole which means that through a four pole device breaking 300 VDC is possible by wiring all four power poles in series. However, be aware that the device current ratings will differ according to the number of poles in series and the type of application.

Devices are suitable but not UL Listed for DC applications.

More information on their DC ratings can be found in the current TeSys Motor Control and Protection Compentns catalog: https://www.schneider-electric.us/en/download/document/MKTED210011EN/


 

What are the coil voltage codes for the LC1D115 / LC2D115 and LC1D150 / LC2D150 TeSys contactor?

Issue:
LC1D115 / LC2D115 and LC1D150 / LC2D150

Product Line:
Tesys D line Contactors

Environment:
North America

Resolution:
The following list the more common voltage suffix codes for these product lines.  For a more comprehensive list and to determine compatibility with a given product, refer to the catalog below.

Note 1: LC1D150 contactors are only available with *7 coil codes.
Note 2: Coil Code ending number represents frequency rating as follows:
5 = 50 Hertz
6 = 60 Hertz
7 = 50/60 Hertz

AC Volts ___Code                DC Volts ___Code
24 ___ B5 or B6 or B7          12 ___ Not Avail.        
42 ___ D5 or D7                   24 ___ BD
48 ___ E5 or E6 or E7          36 ___ CD
110 ___ F5 or F6 or F7         48 ___ ED
115 ___ FE5 or FE7             60 ___ ND
120 ___ G6 or G7                72 ___ SD
127 ___ FC5 or FC7            110 ___ FD
208 ___ L6 or LE7               125 ___ GD
220 ___ M5 or M6 or M7       220 ___ MD
230 ___ P5 or P7                 250 ___ UD
240 ___ U5 or U6 or U7        440 ___ RD
277 ___ W6 or UE7                
380 ___ Q5 or Q6 or Q7                
400 ___ V5 or V7                
415 ___ N5 or N7                
440 ___ R5 or R6 or R7                
480 ___ T6 or T7                
500 ___ S5 or S7                


 
Show More