Quantcast

TeSys D Contactor, 4P(4 NO), AC-1, <= 440V, 200A, 48VAC, 50/60 Hz Coil

TeSys D Contactor, 4P(4 NO), AC-1, <= 440V, 200A, 48VAC, 50/60 Hz Coil

TeSys D Contactor, 4P(4 NO), AC-1, <= 440V, 200A, 48VAC, 50/60 Hz Coil

Item Number: LC1D1150046E7

Retail
$3,404.69
RRP (Inc. GST)

Product Dimensions

Width icon

Width155 mm

Height icon

Height158 mm

Depth icon

Depth115 mm

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

TeSys D

Range

TeSys

Product or component type

contactor

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

[Ue] rated operational voltage

  • power circuit: <= 1000 V AC 25...400 Hz
  • power circuit: <= 460 V DC
    • [Ie] rated operational current

      200 A (at <60 °C) at <= 440 V AC AC-1 for power circuit

      Electrical durability

      0.8 Mcycles 200 A AC-1 at Ue <= 440 V

      Mounting support

    • rail
    • plate
      • Standards

      • CSA C22.2 No 14
      • EN 60947-4-1
      • EN 60947-5-1
      • IEC 60947-4-1
      • IEC 60947-5-1
      • UL 508
        • Product certifications

        • BV
        • LROS (Lloyds register of shipping)
        • CCC
        • GL
        • DNV
        • RINA
        • GOST
        • UL
        • CSA
          • Connections - terminals

          • control circuit: lugs-ring terminals (external diameter: 8 mm)
          • power circuit: lugs-ring terminals (external diameter: 25 mm)
          • power circuit: bars 1 cable(s) - busbar cross section: 5 x 25 mm
            • Mechanical durability

              8 Mcycles

              IP degree of protection

              IP20 front face conforming to IEC 60529

              Ambient air temperature for operation

            • -40-60 °C
            • 60-70 °C with derating
              • Ambient air temperature for storage

                -60-80 °C

                Height

                158 mm

                Width

                155 mm

                Depth

                115 mm

                Net weight

                2.86 kg

                EU RoHS Directive

                Compliant

                Mercury free

                Yes

                RoHS exemption information

                Yes

                China RoHS Regulation

                Product out of China RoHS scope. Substance declaration for your information

                Environmental Disclosure

                ENVPEP060301EN

                Circularity Profile

                ENVEOLI100405EN

                Others

                Product name

                TeSys D

                Device short name

                LC1D

                Contactor application

                resistive load

                Utilisation category

                AC-1

                Poles description

                4P

                Pole contact composition

                4 NO

                Control circuit type

                AC at 50/60 Hz

                [Uc] control circuit voltage

                48 V AC 50/60 Hz

                [Uimp] rated impulse withstand voltage

                8 kV conforming to IEC 60947

                Overvoltage category

                III

                [Ith] conventional free air thermal current

                200 A (at 60 °C) for power circuit

                Irms rated making capacity

                1260 A at 440 V for power circuit conforming to IEC 60947

                Rated breaking capacity

                1100 A at 440 V for power circuit conforming to IEC 60947

                [Icw] rated short-time withstand current

              • 250 A 40 °C - 10 min for power circuit
              • 550 A 40 °C - 1 min for power circuit
              • 950 A 40 °C - 10 s for power circuit
              • 1100 A 40 °C - 1 s for power circuit
                • Associated fuse rating

                • 250 A gG at <= 690 V coordination type 1 for power circuit
                • 200 A gG at <= 690 V coordination type 2 for power circuit
                  • Average impedance

                    0.6 mOhm - Ith 200 A 50 Hz for power circuit

                    [Ui] rated insulation voltage

                  • power circuit: 600 V CSA certified
                  • power circuit: 600 V UL certified
                  • power circuit: 1000 V conforming to IEC 60947-4-1
                    • Power dissipation per pole

                      24 W AC-1

                      Protective cover

                      with

                      Tightening torque

                    • control circuit: 1.2 N.m - on lugs-ring terminals - with screwdriver flat Ø 6 mm M3.5
                    • control circuit: 1.2 N.m - on lugs-ring terminals - with screwdriver Philips No 2 M3.5
                    • power circuit: 12 N.m - on lugs-ring terminals hexagonal screw head 13 mm M8
                    • power circuit: 12 N.m - on bars hexagonal screw head 13 mm M8
                      • Operating time

                      • 6...20 ms opening
                      • 20...50 ms closing
                        • Safety reliability level

                        • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                        • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                          • Maximum operating rate

                            2400 cyc/h 60 °C

                            Coil technology

                            built-in bidirectional peak limiting diode suppressor

                            Control circuit voltage limits

                          • 0.3...0.5 Uc (-40-70 °C):drop-out AC 50/60 Hz
                          • 0.8...1.15 Uc (-40-55 °C):operational AC 50/60 Hz
                          • 1...1.15 Uc (55-70 °C):operational AC 50/60 Hz
                            • Inrush power in VA

                            • 280-350 VA 60 Hz cos phi 0.8 (at 20 °C)
                            • 280-350 VA 50 Hz cos phi 0.8 (at 20 °C)
                              • Hold-in power consumption in VA

                              • 2-18 VA 60 Hz cos phi 0.3 (at 20 °C)
                              • 2-18 VA 50 Hz cos phi 0.3 (at 20 °C)
                                • Heat dissipation

                                  3-8 W at 50/60 Hz

                                  Contact compatibility

                                  M14

                                  Compatibility code

                                  LC1D

                                  Protective treatment

                                  TH conforming to IEC 60068-2-30

                                  Pollution degree

                                  3

                                  Operating altitude

                                  0...3000 m

                                  Fire resistance

                                  850 °C conforming to IEC 60695-2-1

                                  Flame retardance

                                  V1 conforming to UL 94

                                  Mechanical robustness

                                • vibrations contactor open: 2 Gn, 5...300 Hz
                                • vibrations contactor closed: 4 Gn, 5...300 Hz
                                • shocks contactor closed: 15 Gn for 11 ms
                                • shocks contactor open: 6 Gn for 11 ms
                                  • Unit Type of Package 1

                                    PCE

                                    Number of Units in Package 1

                                    1

                                    Package 1 Weight

                                    2.37 kg

                                    Package 1 Height

                                    16.8 cm

                                    Package 1 width

                                    21.2 cm

                                    Package 1 Length

                                    18.5 cm

                                    WEEE

                                    The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

                                    PVC free

                                    Yes
                                    Show all specifications

                                    Documents & downloads

                                    hide show
                                    Filter items
                                    • All

                                    • CAD Files and Packs

                                    • Product Brochures

                                    • End of Life Manual

                                    • Product Environmental

                                    • Installation Instruction

                                    • Certificates (MSDS)

                                    • Declaration of Conformity