CONTACTOR
TeSys LC1D115004 reversing contactor, 4 poles, with screw clamp terminals or lugs, with cover, 115A
CONTACTOR
TeSys LC1D115004 reversing contactor, 4 poles, with screw clamp terminals or lugs, with cover, 115A

TeSys D Contactor, 4P(4 NO), AC-1, <= 440V, 200A, 24 VDC Standard Coil

Catalogue Number: LC1D1150046BD
CONTACTOR
TeSys LC1D115004 reversing contactor, 4 poles, with screw clamp terminals or lugs, with cover, 115A
CONTACTOR
TeSys LC1D115004 reversing contactor, 4 poles, with screw clamp terminals or lugs, with cover, 115A
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Range of product
TeSys D
Range
TeSys
Product name
TeSys D
Product or component type
contactor
Device short name
LC1D
Contactor application
resistive load
Utilisation category
AC-1
Poles description
4P
Pole contact composition
4 NO
[Ue] rated operational voltage
  • power circuit: <= 1000 V AC 25...400 Hz
  • power circuit: <= 460 V DC
    • [Ie] rated operational current
      200 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
      Control circuit type
      DC standard
      [Uc] control circuit voltage
      24 V DC
      [Uimp] rated impulse withstand voltage
      8 kV conforming to IEC 60947
      Overvoltage category
      III
      [Ith] conventional free air thermal current
      200 A (at 60 °C) for power circuit
      Irms rated making capacity
      1260 A at 440 V for power circuit conforming to IEC 60947
      Rated breaking capacity
      1100 A at 440 V for power circuit conforming to IEC 60947
      [Icw] rated short-time withstand current
    • 250 A 40 °C - 10 min for power circuit
    • 550 A 40 °C - 1 min for power circuit
    • 950 A 40 °C - 10 s for power circuit
    • 1100 A 40 °C - 1 s for power circuit
      • Associated fuse rating
      • 250 A gG at <= 690 V coordination type 1 for power circuit
      • 200 A gG at <= 690 V coordination type 2 for power circuit
        • Average impedance
          0.6 mOhm - Ith 200 A 50 Hz for power circuit
          [Ui] rated insulation voltage
        • power circuit: 600 V CSA certified
        • power circuit: 600 V UL certified
        • power circuit: 1000 V conforming to IEC 60947-4-1
          • Electrical durability
            0.8 Mcycles 200 A AC-1 at Ue <= 440 V
            Power dissipation per pole
            24 W AC-1
            Protective cover
            with
            Mounting support
          • plate
          • rail
            • Standards
            • CSA C22.2 No 14
            • EN 60947-4-1
            • EN 60947-5-1
            • IEC 60947-4-1
            • IEC 60947-5-1
            • UL 508
              • Product certifications
              • LROS (Lloyds register of shipping)
              • RINA
              • CSA
              • DNV
              • GOST
              • CCC
              • UL
              • GL
              • BV
                • Connections - terminals
                • control circuit: lugs-ring terminals (external diameter: 8 mm)
                • power circuit: lugs-ring terminals (external diameter: 25 mm)
                • power circuit: bars 1 cable(s) - busbar cross section: 5 x 25 mm
                  • Tightening torque
                  • control circuit: 1.2 N.m - on lugs-ring terminals - with screwdriver flat Ø 6 mm M3.5
                  • control circuit: 1.2 N.m - on lugs-ring terminals - with screwdriver Philips No 2 M3.5
                  • power circuit: 12 N.m - on lugs-ring terminals hexagonal screw head 13 mm M8
                  • power circuit: 12 N.m - on bars hexagonal screw head 13 mm M8
                    • Operating time
                    • 20...35 ms closing
                    • 40...75 ms opening
                      • Safety reliability level
                      • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                      • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                        • Mechanical durability
                          8 Mcycles
                          Maximum operating rate
                          1200 cyc/h 60 °C
                          Coil technology
                          with integral suppression device
                          Control circuit voltage limits
                        • operational: 0.75...1.2 Uc DC (at 55 °C)
                        • drop-out: 0.15...0.4 Uc DC (at 55 °C)
                          • Time constant
                            25 ms
                            Inrush power in W
                            270-365 W (at 20 °C)
                            Hold-in power consumption in W
                            2.4-5.1 W at 20 °C
                            Contact compatibility
                            M8
                            Compatibility code
                            LC1D
                            IP degree of protection
                            IP20 front face conforming to IEC 60529
                            Protective treatment
                            TH conforming to IEC 60068-2-30
                            Pollution degree
                            3
                            Ambient air temperature for operation
                            -5-60 °C
                            Ambient air temperature for storage
                            -60-80 °C
                            Permissible ambient air temperature around the device
                            -40-70 °C at Uc
                            Operating altitude
                            3000 m without
                            Fire resistance
                            850 °C conforming to IEC 60695-2-1
                            Flame retardance
                            V1 conforming to UL 94
                            Mechanical robustness
                          • vibrations contactor open: 2 Gn, 5...300 Hz
                          • vibrations contactor closed: 4 Gn, 5...300 Hz
                          • shocks contactor closed: 15 Gn for 11 ms
                          • shocks contactor open: 6 Gn for 11 ms
                            • Height
                              158 mm
                              Width
                              155 mm
                              Depth
                              115 mm
                              Net weight
                              2.86 kg
                              Sustainable offer status
                              Green Premium product
                              REACh Regulation
                              Free of Substances of Very High Concern above the threshold
                              EU RoHS Directive
                              Compliant
                              Mercury free
                              Yes
                              RoHS exemption information
                              Yes
                              China RoHS Regulation
                              Product out of China RoHS scope. Substance declaration for your information
                              Environmental Disclosure
                              ENVPEP060301EN
                              Circularity Profile
                              ENVEOLI100405
                              WEEE
                              The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                              California proposition 65
                              WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov
                              Warranty
                              18 months

                              Documents & downloads

                              hide show
                              Filter items
                              • All

                              • CAD Files and Packs

                              • Product Brochures

                              • Technical Data Catalogues

                              • End of Life Manual

                              • Installation Instruction

                              • Data Bulletin

                              • Product Environmental

                              • Certificates (MSDS)

                              • Declaration of Conformity

                              Frequently Asked Questions

                              hide show

                              Video: What auxiliary contact modules are available for the LC1D and LC2D contactors?

                              Issue:
                              Auxiliary contact modules for the LC1D and LC2D contactors

                              Product Line: 
                              Contactor and Starters - IEC

                              Environment:
                              North American Products

                              Resolution:
                              Select based on application requirements. Please note that the TeSys and Pre-TeSys auxiliary blocks are backward/forward compatible.
                              Front Mounting; maximum of 1 block per contactor:

                              N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
                              --1-----------1---------LADN11-----------LA1DN11
                              --1-----------1---------LADN11G---------LA1DN11G (See Footnote 1)
                              --1-----------1---------LADN11P---------LA1DN11P (See Footnote 1)
                              --2-----------0---------LADN20-----------LA1DN20
                              --2-----------0---------LA1DX20---------LA1DX20 (See Footnote 2)
                              --2-----------0---------LA1DY20---------LA1DY20 (See Footnote 3)
                              --0-----------2---------LADN02-----------LA1DN02
                              --2-----------2---------LADN22-----------LA1DN22
                              --2-----------2---------LADN22G---------LA1DN22G (See Footnote 1)
                              --2-----------2---------LADN22P---------LA1DN22P (See Footnote 1)
                              --2-----------2---------LADC22------------LA1DC22 (See Footnote 4)
                              --3-----------1---------LADN31------------LA1DN31
                              --3-----------1---------LA1DZ31----------LA1DZ31 (See Footnote 5)
                              --1-----------3---------LADN13------------LA1DN13
                              --4-----------0---------LADN40------------LA1DN40
                              --4-----------0---------LA1DZ40-----------LA1DZ40 (See Footnote 6)
                              --0-----------4---------LADN04------------LA1DN04




                              Front Mounting; maximum of 1 block per contactor: For use with D2 Series 25 amp through 80 amp contactors and TeSys Series 40 amp through 80 amp only.

                              N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
                              --1-----------0--------LADN10----------LA1DN10
                              --0-----------1--------LADN01----------LA1DN01

                              Side Mounting; maximum of 1 block on each side for D2 Series and Tesys Series 40 through 80 amp contactors. Tesys 9 through 32, 115, and 150 amps contactors will accept 1 block and is limited to left side only. (*) DC control devices will not accept side mount auxiliaries.
                              (*) DC control exceptions that will accept one left side mounted auxiliary: LC1D115 & LC1D150.

                              N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
                              --1-----------1--------LAD8N11----------LA8DN11
                              --2-----------0--------LAD8N20----------LA8DN20
                              --0-----------2--------LAD8N02----------N/A

                              Footnotes:
                              {1} EN50 012 Machine Tool Terminal Markings
                              {2} (2) NO Sealed Dust Tight Contacts
                              {3} Gold Flash Contacts
                              {4} (1) NO & (1) NC Standard and (1) NO & (1) NC Make Before Break
                              {5} (2) NO Dust Tight Contacts & (1) NO & (1) NC Standard Contacts
                              {6} (2) NO Dust Tight Contacts & (2) NO Standard Contacts

                              What is the color scheme of the Tesys D-Line contactors?

                              Issue:
                              Looking for different color scheme of the Tesys D-Line contactors.

                              Product Line:
                              Tesys D Contactors

                              Environment:
                              LC1D contactors

                              Resolution:
                              Beige and dark gray.
                               

                              What code is a mechanical interlock for the 4pole LC1D1150046 contactor?

                              LA9D11502 will fit the 4p LC1D115 and LC1D150 contactors

                              What are the stand alone short circuit current ratings on the LC1D** contactors?

                              Issue:
                              Tesys D SCCR

                              Product Line:
                              Contactors and Overload Relays

                              Environment:
                              TeSys™ D Contactors and Overload Relays
                               
                              Resolution:
                              The contactors have a stand alone withstand rating that has been established by UL and is based on the maximum horsepower rating for a given device. However, only combination type starters are supplied with short circuit protective devices having a short circuit current rating.

                              They are as follows:
                              Horsepower SCCR (A)

                              0 thru 1 1,000
                              1 thru 50 5,000
                              51 thru 200 10,000
                              201 thru 400 18,000
                              401 thru 600 30,000
                              601 thru 900 42,000
                              901 thru 1600 85,000
                              1601+ 100,000

                              Are the D-Line contactors rated to break DC voltages?

                              Issue: 
                              Can the TeSys D line be used to control DC loads? 

                              Product Line:
                              Tesys D contactors

                              Environment:
                              Products sold and used in the United States
                               
                              Cause:
                               DC power circuit
                               
                              Resolution:
                               
                              Yes, 75 VDC (125 VDC for D115 & D150) per pole which means that through a four pole device breaking 300 VDC is possible by wiring all four power poles in series. However, be aware that the device current ratings will differ according to the number of poles in series and the type of application.

                              Devices are suitable but not UL Listed for DC applications.

                              More information on their DC ratings can be found in the current TeSys Motor Control and Protection Compentns catalog: https://www.schneider-electric.us/en/download/document/MKTED210011EN/


                               

                              What are the coil voltage codes for the LC1D115 / LC2D115 and LC1D150 / LC2D150 TeSys contactor?

                              Issue:
                              LC1D115 / LC2D115 and LC1D150 / LC2D150

                              Product Line:
                              Tesys D line Contactors

                              Environment:
                              North America

                              Resolution:
                              The following list the more common voltage suffix codes for these product lines.  For a more comprehensive list and to determine compatibility with a given product, refer to the catalog below.

                              Note 1: LC1D150 contactors are only available with *7 coil codes.
                              Note 2: Coil Code ending number represents frequency rating as follows:
                              5 = 50 Hertz
                              6 = 60 Hertz
                              7 = 50/60 Hertz

                              AC Volts ___Code                DC Volts ___Code
                              24 ___ B5 or B6 or B7          12 ___ Not Avail.        
                              42 ___ D5 or D7                   24 ___ BD
                              48 ___ E5 or E6 or E7          36 ___ CD
                              110 ___ F5 or F6 or F7         48 ___ ED
                              115 ___ FE5 or FE7             60 ___ ND
                              120 ___ G6 or G7                72 ___ SD
                              127 ___ FC5 or FC7            110 ___ FD
                              208 ___ L6 or LE7               125 ___ GD
                              220 ___ M5 or M6 or M7       220 ___ MD
                              230 ___ P5 or P7                 250 ___ UD
                              240 ___ U5 or U6 or U7        440 ___ RD
                              277 ___ W6 or UE7                
                              380 ___ Q5 or Q6 or Q7                
                              400 ___ V5 or V7                
                              415 ___ N5 or N7                
                              440 ___ R5 or R6 or R7                
                              480 ___ T6 or T7                
                              500 ___ S5 or S7                


                               

                              Will the LAD** time delay auxiliary contact module fit the D2 series pre-Tesys contactors?

                              Issue:
                              Can new accessories be used on older style contactors

                              Product Line:
                              IEC contactors and starters

                              Environment:
                              Products sold and used in the United States

                              Cause:
                              Identifying product compatibility

                              Resolution:
                              Yes, all front mount D2 and Tesys series auxiliary modules are backward forward compatible.


                               

                              What is the part number for a replacement 4 pole 25amp contactor for the LC1D12004B7?

                              The part number for a replacement 4 pole 25amp contactor for the LC1D12004B7 is - LC1DT25B7

                              For further information, visit the link below:-
                              https://www.schneider-electric.com.au/en/search/LC1DT25B7
                              User-added image

                               

                              What is the power terminal lug data for the LC1D40, LC1D50, LC1D65, LP1D40, LP1D50, and LP1D65 contactor?

                              Issue:
                              Identifying power terminal lug data for the D2 style contactors

                              Product Line:
                              Tesys D line contactors

                              Environment:
                              Products sold and used in the United States

                              Cause:
                              Power terminal lug data required

                              Resolution:
                              For contactors with screw clamp terminals:
                              stranded cable w/o cable end : One #10-3 AWG or Two #10-4 AWG per terminal.
                              stranded cable w/cable end: One #10-4 AWG or Two #12-2 AWG per terminal.
                              solid cable: One #10-3 AWG or Two #10-6 AWG per terminal.

                              What is the replacement contactor for the LC1D65004F5?

                              The new code is LC1DT80AF7 which is made to order.

                              Are 208 volt replacement control coils available for LC2D12004?

                              Issue:
                              Looking for a 208 volt replacement control coils available for an LC2D12004.

                              Product Line:
                              Tesys D Contactors

                              Environment:
                              LC2D12004

                              Resolution:
                              This coil is obsolete. Replace the contactor with the new TeSys product, LC2DT25LE7. Note this is a functional equal only. Accessories for the old product may or may not fit the new design. Confirm dimensions.
                               

                              What is the part number for replacement Contactor to LP1D25004BD?

                              Replacement Contactor for the older LP1D25004BD is new LC1DT40BD
                              see link for more details.....
                              https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LC1DT40bd
                               
                              Show More