Package 1 Bare Product Quantity
1
Contactor application
- resistive load
- motor control
[Uc] control circuit voltage
12 V DC
Motor power kW
- 2.2 kW at 220...230 V AC 50/60 Hz (AC-3)
- 4 kW at 380...400 V AC 50/60 Hz (AC-3)
- 4 kW at 415...440 V AC 50/60 Hz (AC-3)
- 5.5 kW at 500 V AC 50/60 Hz (AC-3)
- 5.5 kW at 660...690 V AC 50/60 Hz (AC-3)
- 2.2 kW at 400 V AC 50/60 Hz (AC-4)
- 2.2 kW at 220...230 V AC 50/60 Hz (AC-3e)
- 4 kW at 380...400 V AC 50/60 Hz (AC-3e)
- 4 kW at 415...440 V AC 50/60 Hz (AC-3e)
- 5.5 kW at 500 V AC 50/60 Hz (AC-3e)
- 5.5 kW at 660...690 V AC 50/60 Hz (AC-3e)
Motor power hp
- 1 hp at 230/240 V AC 50/60 Hz for 1 phase motors
- 2 hp at 200/208 V AC 50/60 Hz for 3 phases motors
- 2 hp at 230/240 V AC 50/60 Hz for 3 phases motors
- 5 hp at 460/480 V AC 50/60 Hz for 3 phases motors
- 7.5 hp at 575/600 V AC 50/60 Hz for 3 phases motors
- 0.33 hp at 115 V AC 50/60 Hz for 1 phase motors
Pole contact composition
3 NO
[Ith] conventional free air thermal current
- 25 A (at 60 °C) for power circuit
- 10 A (at 60 °C) for signalling circuit
Irms rated making capacity
- 250 A at 440 V for power circuit conforming to IEC 60947
- 140 A AC for signalling circuit conforming to IEC 60947-5-1
- 250 A DC for signalling circuit conforming to IEC 60947-5-1
Rated breaking capacity
250 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current
- 105 A 40 °C - 10 s for power circuit
- 210 A 40 °C - 1 s for power circuit
- 30 A 40 °C - 10 min for power circuit
- 61 A 40 °C - 1 min for power circuit
- 100 A - 1 s for signalling circuit
- 120 A - 500 ms for signalling circuit
- 140 A - 100 ms for signalling circuit
Associated fuse rating
- 10 A gG for signalling circuit conforming to IEC 60947-5-1
- 25 A gG at <= 690="" v="" coordination="" type="" 1="" for="" power="">=>
- 20 A gG at <= 690="" v="" coordination="" type="" 2="" for="" power="">=>
Average impedance
2.5 mOhm - Ith 25 A 50 Hz for power circuit
Power dissipation per pole
- 1.56 W AC-1
- 0.2 W AC-3
- 0.2 W AC-3e
[Ui] rated insulation voltage
- power circuit: 690 V conforming to IEC 60947-4-1
- power circuit: 600 V CSA certified
- power circuit: 600 V UL certified
- signalling circuit: 690 V conforming to IEC 60947-1
- signalling circuit: 600 V CSA certified
- signalling circuit: 600 V UL certified
[Uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947
Safety reliability level
- B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
- B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Control circuit type
DC standard
Coil technology
built-in bidirectional peak limiting diode suppressor
Control circuit voltage limits
- 0.1...0.25 Uc (-40-70 °C):drop-out DC
- 0.7...1.25 Uc (-40-60 °C):operational DC
- 1...1.25 Uc (60-70 °C):operational DC
Inrush power in W
5.4...5.4 W (at 20 °C)
Hold-in power consumption in W
5.4...5.4 W at 20 °C
Operating time
- 53.55...72.45 ms closing
- 16...24 ms opening
Maximum operating rate
3600 cyc/h 60 °C
Tightening torque
- power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
- power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
- control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
- control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
- control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
- power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
Auxiliary contact composition
1 NO + 1 NC
Auxiliary contacts type
- type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
- type mirror contact 1 NC conforming to IEC 60947-4-1
Signalling circuit frequency
25...400 Hz
Minimum switching voltage
17 V for signalling circuit
Minimum switching current
5 mA for signalling circuit
Non-overlap time
- 1.5 ms on de-energisation between NC and NO contact
- 1.5 ms on energisation between NC and NO contact
Protective treatment
TH conforming to IEC 60068-2-30
Permissible ambient air temperature around the device
- -40...60 °C
- 60...70 °C with derating
Operating altitude
0...3000 m
Fire resistance
850 °C conforming to IEC 60695-2-1
Flame retardance
V1 conforming to UL 94
Mechanical robustness
- vibrations contactor open (2 Gn, 5...300 Hz)
- vibrations contactor closed (4 Gn, 5...300 Hz)
- shocks contactor open (10 Gn for 11 ms)
- shocks contactor closed (15 Gn for 11 ms)
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Unit Type of Package 2
S02
Number of Units in Package 2
15
Package 2 Weight
8.282 kg
Unit Type of Package 3
P06
Number of Units in Package 3
120
Package 3 Weight
99.98 kg