Package 1 Bare Product Quantity
1
Package 2 Bare Product Quantity
15
Package 3 Bare Product Quantity
240
Contactor application
- motor control
- resistive load
[Uc] control circuit voltage
- 24...60 V AC 50/60 Hz
- 24...60 V DC
Motor power kW
- 2.2 kW at 220...230 V AC 50 Hz (AC-3)
- 4 kW at 380...400 V AC 50 Hz (AC-3)
- 4 kW at 415 V AC 50 Hz (AC-3)
- 4 kW at 440 V AC 50 Hz (AC-3)
- 5.5 kW at 500 V AC 50 Hz (AC-3)
- 5.5 kW at 660...690 V AC 50 Hz (AC-3)
- 2.2 kW at 220...230 V AC 50 Hz (AC-3e)
- 4 kW at 380...400 V AC 50 Hz (AC-3e)
- 4 kW at 415 V AC 50 Hz (AC-3e)
- 4 kW at 440 V AC 50 Hz (AC-3e)
- 5.5 kW at 500 V AC 50 Hz (AC-3e)
- 5.5 kW at 660...690 V AC 50 Hz (AC-3e)
Motor power hp
- 0.33 hp at 115 V AC 60 Hz for 1 phase motors
- 1 hp at 230/240 V AC 60 Hz for 1 phase motors
- 2 hp at 200/208 V AC 60 Hz for 3 phases motors
- 2 hp at 230/240 V AC 60 Hz for 3 phases motors
- 5 hp at 460/480 V AC 60 Hz for 3 phases motors
- 7.5 hp at 575/600 V AC 60 Hz for 3 phases motors
Pole contact composition
3 NO
[Ith] conventional free air thermal current
- 10 A (at 60 °C) for signalling circuit
- 25 A (at 60 °C) for power circuit
Irms rated making capacity
- 250 A at 440 V for power circuit conforming to IEC 60947
- 140 A AC for signalling circuit conforming to IEC 60947-5-1
- 250 A DC for signalling circuit conforming to IEC 60947-5-1
Rated breaking capacity
250 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current
- 100 A - 1 s for signalling circuit
- 120 A - 500 ms for signalling circuit
- 140 A - 100 ms for signalling circuit
- 30 A 40 °C - 10 min for power circuit
- 61 A 40 °C - 1 min for power circuit
- 105 A 40 °C - 10 s for power circuit
- 210 A 40 °C - 1 s for power circuit
Associated fuse rating
- 10 A gG for signalling circuit conforming to IEC 60947-5-1
- 25 A gG at <= 690="" v="" coordination="" type="" 1="" for="" power="">=>
- 20 A gG at <= 690="" v="" coordination="" type="" 2="" for="" power="">=>
Average impedance
2.5 mOhm - Ith 25 A 50 Hz for power circuit
Power dissipation per pole
- 1.56 W AC-1
- 0.2 W AC-3
- 0.2 W AC-3e
[Ui] rated insulation voltage
- power circuit: 690 V conforming to IEC 60947-4-1
- signalling circuit: 690 V conforming to IEC 60947-1
[Uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947
Safety reliability level
- B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
- B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Control circuit type
AC/DC at 50/60 Hz AC/DC electronic
Coil technology
built-in bidirectional peak limiting
Control circuit voltage limits
- <= 0.1="" uc="" (-40-70="" °c):drop-out="">=>
- 0.85...1.1 Uc (-40-60 °C):operational AC
- 0.8...1.1 Uc (-40-60 °C):operational DC
- 1...1.1 Uc (60-70 °C):operational AC/DC
Inrush power in VA
15 VA 50/60 Hz (at 20 °C)
Inrush power in W
14 W (at 20 °C)
Hold-in power consumption in VA
0.9...0.9 VA 50/60 Hz (at 20 °C)
Hold-in power consumption in W
0.6...0.6 W at 20 °C
Heat dissipation
0.6...0.6 W at 50/60 Hz
Operating time
- 45...55 ms closing
- 20...90 ms opening
Maximum operating rate
3600 cyc/h 60 °C
Tightening torque
- control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
- control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
- power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
- power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
- power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
- control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
Auxiliary contact composition
1 NO + 1 NC
Auxiliary contacts type
- type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
- type mirror contact 1 NC conforming to IEC 60947-4-1
Signalling circuit frequency
25...400 Hz
Minimum switching voltage
17 V for signalling circuit
Minimum switching current
5 mA for signalling circuit
Non-overlap time
- 1.5 ms on de-energisation between NC and NO contact
- 1.5 ms on energisation between NC and NO contact
Permissible ambient air temperature around the device
- -40...60 °C
- 60...70 °C with derating
Operating altitude
0...3000 m
Fire resistance
850 °C conforming to IEC 60695-2-1
Flame retardance
V1 conforming to UL 94
Mechanical robustness
- vibrations contactor open (2 Gn, 5...300 Hz)
- vibrations contactor closed (4 Gn, 5...300 Hz)
- shocks contactor open (10 Gn for 11 ms)
- shocks contactor closed (15 Gn for 11 ms)
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
5.600 cm
Package 1 Length
12.000 cm
Package 1 Weight
399.000 g
Unit Type of Package 2
S02
Number of Units in Package 2
15
Package 2 Height
15.000 cm
Package 2 Width
30.000 cm
Package 2 Length
40.000 cm
Package 2 Weight
6.275 kg
Unit Type of Package 3
P06
Number of Units in Package 3
240
Package 3 Height
75.000 cm
Package 3 Width
60.000 cm
Package 3 Length
80.000 cm
Package 3 Weight
83.300 kg
WEEE
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Halogen content performance
Halogen free plastic parts & cables product