Specifications

hide show
Range of product
TeSys D
Range
TeSys
Product or component type
auxiliary contact block
Range compatibility
  • TeSys CAD
  • TeSys LC1D
  • TeSys LC1F
  • TeSys CR1F
    • Auxiliary contacts operation
    • make before break 1 NO + 1 NC
    • instantaneous 1 NO + 1 NC
      • Pole contact composition
        2 NO + 2 NC
        Shielding continuity terminal
        without
        Connections - terminals
      • screw clamp terminals 1 cable(s) 1-2.5 mm²flexible with cable end
      • screw clamp terminals 1 cable(s) 1-2.5 mm²flexible without cable end
      • screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
      • screw clamp terminals 2 cable(s) 1-2.5 mm²flexible without cable end
      • screw clamp terminals 1 cable(s) 1-2.5 mm²solid
      • screw clamp terminals 2 cable(s) 1-2.5 mm²solid
        • Mounting location
          front
          [Ui] rated insulation voltage
        • 690 V conforming to IEC 60947-5-1
        • 600 V - certifications CSA
        • 600 V - certifications UL
          • [Ue] rated operational voltage
            690 V AC 25...400 Hz
            [Ith] conventional free air thermal current
            10 A (at 60 °C)
            Irms rated making capacity
          • 140 A AC conforming to IEC 60947-5-1
          • 250 A DC conforming to IEC 60947-5-1
            • Permissible short-time rating
            • 100 A 60 °C 1 s
            • 120 A 60 °C 500 ms
            • 140 A 60 °C 100 ms
              • Protection type
                gG fuse 10 A
                Associated fuse rating
                10 A gG conforming to IEC 60947-5-1
                Mechanical durability
                3 Mcycles
                Minimum switching current
                5 mA
                Minimum switching voltage
                17 V
                Non-overlap time
              • 1.5 ms on de-energisation no overlap between NC and NO contact
              • 1.5 ms on energisation no overlap between NC and NO contact
                • Overlap time
                  1.5 ms
                  Insulation resistance
                  > 10 MOhm
                  Tightening torque
                  1.7 N.m
                  Net weight
                  0.05 kg
                  Environmental characteristic
                  normal environment
                  Standards
                • EN/IEC 60947-5-1
                • UL 60947-5-1
                • CSA C22.2 No 60947-5-1
                • GB/T 14048.5
                  • Specific use
                    general
                    Product certifications
                  • IECEE CB Scheme
                  • UL
                  • CSA
                  • CCC
                  • EAC
                    • IP degree of protection
                      IP20 conforming to IEC 60529
                      Protective treatment
                      TH conforming to IEC 60068
                      Ambient air temperature for operation
                      -5-60 °C
                      Ambient air temperature for storage
                      -60-80 °C
                      Operating altitude
                      3000 m
                      Sustainable offer status
                      Green Premium product
                      REACh Regulation
                      Free of Substances of Very High Concern above the threshold
                      REACh free of SVHC
                      Yes
                      EU RoHS Directive
                      Compliant
                      Toxic heavy metal free
                      Yes
                      Mercury free
                      Yes
                      RoHS exemption information
                      Yes
                      China RoHS Regulation
                       Pro-active China RoHS declaration (out of China RoHS legal scope)
                      Environmental Disclosure
                      ENVPEP110807EN_V1
                      WEEE
                      The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                      Warranty
                      18 months

                      Documents & downloads

                      hide show
                      Filter items
                      • All

                      • CAD Files and Packs

                      • Product Brochures

                      • Technical Data Catalogues

                      • Product Environmental

                      • Installation Instruction

                      Frequently Asked Questions

                      hide show

                      What is the replacement for LA1DN22 ?

                      LADN22

                      What is the replacement AC coil for CAD32 and CAD50 relay?

                      Issue:
                      AC coil replacement for CAD32 and CAD50

                      Product Line:
                      Relays

                      Environment:
                      Tesys CAD Control Relays

                      Cause:
                      Product selection

                      Resolution:
                      Volt = coil part number
                      12 = LXD1J7
                      21 = LXD1Z7
                      24 = LXD1B7
                      32 = LXD1C7
                      36 = LXD1CC7
                      42 = LXD1D7
                      48 = LXD1E7
                      60 = LXD1EE7
                      100 = LXD1K7
                      110 = LXD1F7
                      115 = LXD1FE7
                      120 = LXD1G7
                      127 = LXD1FC7
                      200 = LXD1L7
                      208 = LXD1LL7
                      220/230 = LXD1M7
                      230 595 21 LXD1P7
                      230/240 = LXD1U7
                      277 781 30 LXD1W7
                      380/400 = LXD1Q7
                      400 = LXD1V7
                      415 = LXD1N7
                      440 = LXD1R7
                      480 = LXD1T7
                      600 = LXD1X7
                      690 = LXD1Y7

                       

                      Are the auxiliary contacts on the D line contactors overlapping?

                      Issue:
                      Are the auxiliary contacts on the D line contactors overlapping?
                      Product Line:
                      Tesys D contactors
                      Environment:
                      IEC Contactors
                      Cause:
                      Product Characteristics
                      Resolution:
                      Except for the LADC22, they are non overlapping (break before make). Thus, the normally closed contact opens before the normally open contact closes. The LADC22 has 1NO and 1NC overlapping contact (make before break).

                      In regards to LAD5C11 LAD5C31 LAD5C12 LAD5C32 What is the maximum kW range that TeSys SoLink can be used with motor starter combination?

                      TeSys SoLink is the connection module to connect GV2/GV3 motor circuit breakers to associated contactors and can be used with GV2 / GV3 breakers up to 30kW.
                      For more information please visit the Link provided
                      https://www.schneider-electric.com.au/australia/en/products-services/offer-updates/news-viewer.page?c_filepath=/templatedata/Content/News/data/en/local/automation_control/general_information/2014/10/20141024_tesys_solink_integration_system.xml

                      In regards to LAD5C11 LAD5C31 LAD5C12 LAD5C32 SoLink What is the maximum number of motor starters that can be connected and controlled with each logic controller?

                      Each TM3 I/O module is able to monitor and control up to 4 motor starters and up to 56 motor starters can be connected to logic controller.
                      For more information aboput this range please Visit the Schneider website on the link provided
                      https://www.schneider-electric.com.au/australia/en/products-services/offer-updates/news-viewer.page?c_filepath=/templatedata/Content/News/data/en/local/automation_control/general_information/2014/10/20141024_tesys_solink_integration_system.xml

                      In regards to LAD5C11 LAD5C31 LAD5C12 LAD5C32 SoLink , Can TeSys SoLink be used with AC control supply?

                      TeSys SoLink is suitable for 24VDC control supply; the TM3 I/O module provides the 24V DC control voltage to the motor starter.
                      For more information on this range please visit the Schneider electric web site on the link provided
                      https://www.schneider-electric.com.au/australia/en/products-services/offer-updates/news-viewer.page?c_filepath=/templatedata/Content/News/data/en/local/automation_control/general_information/2014/10/20141024_tesys_solink_integration_system.xml

                      What the difference is between these 2 contact blocks - LADN22 and LADN22G?

                      Issue:
                      Identifying differences in two part numbers

                      Product Line:
                      IEC contactors and starters

                      Environment:
                      Products sold and used in the United States

                      Cause:
                      Determining which part number to order

                      Resolution:
                      They both have 2 normally open (N.O.) and 2 normally closed (N.C.) contacts.
                      The sequence and numbering are different
                      LADN22 from left to right read : N.O. 53 and 54; N.C. 61 and 62; N.C. 71 and 72; N.O. 83 AND 84.

                      LADN22G from left to right read : N.C. 31 and 32; N.C. 41 and 42; N.O. 53 and 54; N.O. 63 and 64.


                       

                      What is the part code for a 320A 3P Contactor 230V interlock aux 2 n/o 2n/c

                      The part codes are LC1F330 coil + LX1FH2402 interlock  + LA9FJ970 aux  = LADN22

                      What is the terminal identification numbers for the LADN22 auxiliary contact module?

                      Issue:
                      What is the terminal identification numbers for the LADN22 auxiliary contact module?

                      Product Line:
                      Tesys Contactors and Overload Relays

                      Environment:
                      All Products

                      Cause:
                      Product Features

                      Resolution:
                      Normally open contacts are 53/54 and 83/84; normally closed contacts are 61/62 and 71/72.

                      Do we have replacement on Siemans part number 3TB4217OBB4?

                      The replacement part number for Siemens part 3TB4217OBB4 will be contactor part LC1D25BD and then the overload part number LADN22. 

                      So the customer needs to buy LC1D25BD + LADN22 to match 3TB4217OBB4.

                      Do we provide the protection rubber kit in different colors ?

                      Yes, ZARC21 (Green), ZARC22 (Red), ZARC23 (Blue), ZARC24 (Yellow) and ZARC25 (Orange).

                      What is the code for an off delay auxiliary contact block for Tesys contactors?

                      The code is LADR2. This is a 0.1-30s off Delay
                      Show More