Specifications

hide show
Range
TeSys
Product or component type
terminal block
Device short name
LAD
Accessory / separate part category
connection accessory
Product compatibility
  • LR9D..
  • LRD..L
  • LR3D..L
    • Quantity per set
      set of 1
      Connections - terminals
      screw terminals
      Height
      85 mm
      Width
      45 mm
      Depth
      87 mm
      Net weight
      0.12 kg
      Compatibility code
      LAD
      Sustainable offer status
      Green Premium product
      REACh Regulation
      Free of Substances of Very High Concern above the threshold
      REACh free of SVHC
      Yes
      EU RoHS Directive
      Compliant
      Toxic heavy metal free
      Yes
      Mercury free
      Yes
      RoHS exemption information
      Yes
      China RoHS Regulation
       Pro-active China RoHS declaration (out of China RoHS legal scope)
      Environmental Disclosure
      ENVPEP111213EN_V1
      WEEE
      The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
      Warranty
      18 months

      Frequently Asked Questions

      hide show

      Is the LAD7B10 a UL and CSA Recognized Component?

      Issue:
      Is the LAD7B10 a UL or CSA recognized component?

      Product Line:
      IEC Overload Mounting Kit

      Environment:
      IEC Contactors

      Cause:
      Clarify CSA and UL listing for IEC components

      Resolution:
      As of 6/30/2016 this device has been UL component recongnized. This device has not been CSA recognized

      Key words LAD7B10, UL, CSA, separate mounting

      Case Subject:
      LAD7B10

      What is the Din rail terminal block to suit the LRD12?

      The LAD7B106 fits the LRD01 to LRD35 range.
       

      What is the difference between the LA7D305 and LAD7305, remote control reset mechanism by flexible cable?

      Issue:
      Identifying differences between two similar part numbers.

      Product Line:
      IEC contactors and starters

      Environment:
      Products sold and used in the United States

      Cause:
      Choosing the correct part number

      Resolution:
      LAD7305 is for use on LRD01 to LRD35 , LR3D01 to LR3D35, and LRD313 to LRD365.
      LA7D305 is for use on all other relays (except LRD01 to LRD35 and LR3D01 to LR3D35).

       

      Will the LAD7B10 or the LAD7B106 work on the Pre-Tesys D line LR2D15*** overload relays?

      Issue:
      Separate mount block needed for older style overload relay

      Product Line:
      IEC contactors and starters

      Environment:
      North American Products

      Resolution:
      No. These are a different design and will not work with the pre - Tesys overload relays.


       

      Will the LA7D1064 fit the new TeSys LRD overload relays?

      Issue:
      Identifying separate mount for newer style LRD overload relays

      Product Line:
      IEC contactors and starters

      Environment:
      Products sold and used in the United States

      Resolution:
      No, they are a different design and will not work with the Tesys overload relays, you will need the LAD7B10 or LAD7B10..

      What is the Difference between LADN206 and LADN20?

      LADN206 has 2N/O Lugs ring terminal
      LADN20 has 2 N/O - screw-clamps terminals
      Rest of the specifications are the same.

      what is new alternative for Code 15961 ?

      Code = A9C20833

      What size cable does a LAD7B10 accept?

      Issue:
      Need to know the size cable accepted by the LAD7B10 block.

      Product Line:
      IEC Contactors and starters

      Environment:
      Products sold and used in the United States

      Cause:
      Identifying cabling requirements.

      Resolution:
      It takes either a 1 flexible cable without cable end size 14-8 AWG or 1 flex cable with cable end size 16-12AWG or 1 solid cable without cable end size 16-10 AWG.


       

      Is the Clipsal 224/2 floor outlet still available

       Obsolete and deleted. Use a SBIP2P-XX  
      The PDL 535F has been obsoleted as well

      What is the temperature range for the ZB5AD range? ZB5AD2 ZB5AD3 ZB5AD4 ZB5AD5 ZB5AD7 ZB5AD8

      Ambient air temperature for storage -40...158 °F (-40 to 70 °C)
      Ambient air temperature for operation -13...158 °F (-25 to 70 °C)

      ETSNZ - How do I wire the BMXDDO3202K discrete IO 24 VDC positive logic module for a M340 PLC?

      BMXDDO3202K wiring the 24 VDC positive logic module as per the diagram:

      What can be done to fix the issue of HOA switch working backwards after ATV58 was replaced with ATV61 drive?

      Issue:
      After replacing the ATV58 with an ATV61 the HOA is working backwards.

      Product Line:
      EconoFlex 58

      Environment:
      All

      Cause:
      Reference analog input programming  need to be changed on the new ATV61 drive.

      Resolution:
      New ATV61 needs to be programmed.
      • Menu 1.6 Command menu
      • Ref 1 = AI2
      • Ref 1 B switching = LI3
      • Ref 1 B channel is AI1
      • Logic input LI3 is low for auto and high for hand.
      Show More