      What is the thread size of the LA9F701 and LA9F702?

      The thread size of the LA9F701 terminal covers is 6mm and the thread size of the LA9F702 is 8mm.

      Data sheets on the items...https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=la9f701 
      ..........................................https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=la9f702

       

      We have some problems with ATV31 and LA9P307. Normally it works well but not in this case: LA9P307 with HUB LU9GC3 and 8 ATV31. RC-Termination is like...

      Goals and Symptoms

      We have some problems with ATV31 and LA9P307. Normally it works well but not in this case: LA9P307 with HUB LU9GC3 and 8 ATV31. RC-Termination is like manual. It works well but when one ATV31 is shut off or disconnect from Modbus the other 7 atv31 are tripping with SLF!

      When it will be switched off it gives for a short time 208 in the ETA

      Facts and Changes

      ATV31 Modbus LA9P307

      Causes and Fixes

      What is the adjusting value of PPO failure ? The problem was solved with Modbus max N adjusted to 2 in place of 7. The signification of 16#0208 in ETA is serial link fault. It was siemens PLC.


      Legacy KB System (APS) Data: RESL162527 V1.0, Originally authored by on , Last Edited by on