Bidirectional Diode Ac D40-D95

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

TeSys D

Range

TeSys

Product or component type

suppressor module

Product compatibility

  • 4P LC1D40008...D80008
  • 3P LC1D80...D95
  • 4P LC1D80004
    • Sustainable offer status

      Green Premium product

      Warranty

      18 months

      Physical

      Mounting mode

      by screws

      Net weight

      0.018 kg

      Ambient air temperature for operation

      -25-55 °C

      Ambient air temperature for storage

      -40-80 °C

      REACh free of SVHC

      Yes

      EU RoHS Directive

      Compliant

      Toxic heavy metal free

      Yes

      Mercury free

      Yes

      RoHS exemption information

      Yes

      China RoHS Regulation

       Pro-active China RoHS declaration (out of China RoHS legal scope)

      Environmental Disclosure

      ENVPEP111253EN

      Others

      Device short name

      LA4D

      Mounting location

      top

      Suppressor technology

      bidirectional peak limiting diode

      [Uc] control circuit voltage

      12...24 V AC 50/60 Hz

      Maximum peak voltage

      2 Uc

      Compatibility code

      LA4D

      Unit Type of Package 1

      PCE

      Number of Units in Package 1

      1

      Package 1 Weight

      15 g

      Package 1 Height

      2.7 cm

      Package 1 width

      4.2 cm

      Package 1 Length

      5 cm

      Unit Type of Package 2

      S01

      Number of Units in Package 2

      32

      Package 2 Weight

      562 g

      Package 2 Height

      15 cm

      Package 2 width

      15 cm

      Package 2 Length

      40 cm

      WEEE

      The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
      Show all specifications

      Documents & downloads

      hide show
      Filter items
      • All

      • CAD Files and Packs

      • Product Brochures

      • Technical Data Catalogues

      • Installation Instruction

      Frequently Asked Questions

      hide show

      What is the LA4DE1U alternative?

      LA4DE1U TeSys D - suppressor module - varistor - 110...250 V AC/DC

      to suit D40-D115 (3P) and D65-115 (4P):
      LA4DE2U TeSys D - suppressor module - varistor - 110...250 V AC
      OR
      LA4DE3U TeSys D - suppressor module - varistor - 110...250 V DC
       

      I have a LC1D12BD contactor and want to fit a LA4DFB to it

       You need to use a LAD4BB adaptor

      What is the replacement AC coil for CAD32 and CAD50 relay?

      Issue:
      AC coil replacement for CAD32 and CAD50

      Product Line:
      Relays

      Environment:
      Tesys CAD Control Relays

      Cause:
      Product selection

      Resolution:
      Volt = coil part number
      12 = LXD1J7
      21 = LXD1Z7
      24 = LXD1B7
      32 = LXD1C7
      36 = LXD1CC7
      42 = LXD1D7
      48 = LXD1E7
      60 = LXD1EE7
      100 = LXD1K7
      110 = LXD1F7
      115 = LXD1FE7
      120 = LXD1G7
      127 = LXD1FC7
      200 = LXD1L7
      208 = LXD1LL7
      220/230 = LXD1M7
      230 595 21 LXD1P7
      230/240 = LXD1U7
      277 781 30 LXD1W7
      380/400 = LXD1Q7
      400 = LXD1V7
      415 = LXD1N7
      440 = LXD1R7
      480 = LXD1T7
      600 = LXD1X7
      690 = LXD1Y7

       

      Part number LA4DFB not fitting on LC1D12 Contactor?

      What is the replacement for LA1DN22 ?

      LADN22

      What the DC current contact ratings for the CAD50, CAD32, CAD503, CAD323, CAD506, and CAD326 relay?

      Issue:
      Checking on the DC current contact ratings for the CAD50, CAD32, CAD503,  CAD323,  CAD506, and  CAD326 relay.

      Product Line:
      CAD Industrial Relays

      Environment:
      Relays and Timers

      Resolution:
      Inductive:
      125V DC - 0.55 Amps make and break, 2.5 Amps cont.
      250V DC - 0.27 Amps make and break, 2.5 amps cont.
      600V DC - 0.10 Amps make and break, 2.5 Amps cont.
      Show More