Quantcast

Timer Delay On

Product Dimensions

Width icon

Width38 mm

Height icon

Height27 mm

Depth icon

Depth38 mm

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

TeSys

Range of product

  • TeSys K control relay
  • TeSys K
    • Product or component type

      time delay auxiliary contact block

      Physical

      Range compatibility

    • TeSys K LC1K
    • TeSys K CA2K
    • TeSys K CA3K
    • TeSys K CA4K
      • [Ue] rated operational voltage

      • 24...48 V AC/DC for control circuit
      • 240 V AC for signalling circuit
        • Standards

        • EN/IEC 60947-5-1
        • UL 60947-5-1
        • CSA C22.2 No 60947-5-1
          • Insulation resistance

            > 10 MOhm

            Connections - terminals

            slip-on terminals

            Height

            27 mm

            Width

            38 mm

            Depth

            38 mm

            Net weight

            0.04 kg

            Environmental characteristic

            normal environment

            IP degree of protection

            IP20 conforming to IEC 60529

            Ambient air temperature for operation

            -10-60 °C

            REACh Regulation

            Free of Substances of Very High Concern above the threshold

            EU RoHS Directive

            Compliant

            Mercury free

            Yes

            RoHS exemption information

            Yes

            China RoHS Regulation

            Product out of China RoHS scope. Substance declaration for your information

            Others

            Product name

            TeSys K

            Device short name

            LA1

            Mounting location

            front

            Pole contact composition

            1 C/O

            Auxiliary contacts operation

            time delay

            Timer type

            on delay

            Time delay range

            1...30 s

            Rated operational voltage limits

            0.85...1.1 Uc

            [Ith] conventional free air thermal current

            2 A for signalling circuit

            Reset time

          • 1.5 s during time delay
          • 0.5 s after time delay
            • Shielding continuity terminal

              without

              Compatibility code

              LA1

              Protective treatment

              TC conforming to IEC 60068

              Unit Type of Package 1

              PCE

              Number of Units in Package 1

              1

              Package 1 Weight

              41 g

              Package 1 Height

              4.8 cm

              Package 1 width

              4.8 cm

              Package 1 Length

              5 cm

              Unit Type of Package 2

              S02

              Number of Units in Package 2

              70

              Package 2 Weight

              3.11 kg

              Package 2 Height

              15 cm

              Package 2 width

              30 cm

              Package 2 Length

              40 cm

              WEEE

              The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
              Show all specifications