TeSys SK - auxiliary contact block - 2 NC
Auxiliary contact block TeSys LA1SK
TeSys SK - auxiliary contact block - 2 NC
Auxiliary contact block TeSys LA1SK

TeSys SK Auxiliary Contact Block, 2 NC

Catalogue Number: LA1SK02
TeSys SK - auxiliary contact block - 2 NC
Auxiliary contact block TeSys LA1SK
TeSys SK - auxiliary contact block - 2 NC
Auxiliary contact block TeSys LA1SK
Retail
$94.24
RRP (Inc. GST)

Specifications

hide show
Range of product
  • TeSys SK
  • TeSys SK control relay
    • Range
      TeSys
      Device short name
      LA1SK
      Product or component type
      auxiliary contact block
      Product compatibility
      LC1SK
      Auxiliary contacts operation
      instantaneous
      Pole contact composition
      2 NC
      Connections - terminals
    • screw clamp terminals 1 cable(s) 1.5-6 mm²solid
    • screw clamp terminals 2 cable(s) 1.5-4 mm²solid
    • screw clamp terminals 1 cable(s) 0.5-6 mm²flexible with cable end
    • screw clamp terminals 2 cable(s) 0.35-2.5 mm²flexible with cable end
    • screw clamp terminals 1 cable(s) 0.35-6 mm²flexible without cable end
    • screw clamp terminals 2 cable(s) 0.35-1.5 mm²flexible without cable end
      • Mounting location
        front side
        [Ui] rated insulation voltage
      • 690 V conforming to IEC 60947
      • 690 V conforming to BS 5424
      • 690 V conforming to VDE 0110 group C
      • 690 V conforming to CSA C22.2 No 14
        • [Ue] rated operational voltage
          690 V AC <= 400 Hz
          [Ith] conventional free air thermal current
          10 A (at 55 °C)
          Associated fuse rating
        • 10 A gL conforming to IEC 60947
        • 10 A gL conforming to VDE 0660
          • Tightening torque
            0.8 N.m - on screw clamp terminals
            Width
            27 mm
            Net weight
            0.022 kg
            Compatibility code
            LA1SK
            Standards
          • VDE 0660
          • BS 5424
          • NF C 63-110
          • IEC 60947
            • Product certifications
            • CSA
            • UL
              • IP degree of protection
                IP2x
                Protective treatment
                TC conforming to IEC 60068
                Ambient air temperature for operation
                -20-50 °C
                Ambient air temperature for storage
                -50-70 °C
                Operating altitude
                2000 m without derating
                Unit Type of Package 1
                PCE
                Number of Units in Package 1
                1
                Package 1 Weight
                28 g
                Package 1 Height
                3.6 cm
                Package 1 width
                4.2 cm
                Package 1 Length
                5.3 cm
                Unit Type of Package 2
                S01
                Number of Units in Package 2
                60
                Package 2 Weight
                1.803 kg
                Package 2 Height
                15 cm
                Package 2 width
                15 cm
                Package 2 Length
                40 cm
                Sustainable offer status
                Green Premium product
                REACh free of SVHC
                Yes
                EU RoHS Directive
                Compliant
                Mercury free
                Yes
                RoHS exemption information
                Yes
                China RoHS Regulation
                Product out of China RoHS scope. Substance declaration for your information
                Environmental Disclosure
                ENVPEP111274EN
                WEEE
                The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                Warranty
                18 months

                Frequently Asked Questions

                hide show

                Why will LA1SK11 adder deck not fit on CA2SK11 relay?

                Issue:
                Why will LA1SK11 adder deck not fit on CA2SK11 relay?

                Product Line:
                Tesys Relays

                Environment:
                All Products

                Cause:
                Product Features

                Resolution:
                No, LA1SK11 mounts only on the CA2SK20 relay.




                CTA-ID : 2014524

                Can the old D-line front mount attachments fit on the new CAD relays?

                Issue: 
                Can the old D-line attachments fit the new CAD relays
                 
                Product Line:
                IEC Contactors

                Environment:
                Tesys D contactors and relays
                 
                Cause:
                Using old accessories with new CAD relays

                Resolution:
                 Yes, the old style front mount latch attachments, timing attachments, and auxiliary contacts will mount on the new Tesys D-line relays.

                What is the replacement for LA1DN22 ?

                LADN22

                What is the thread size of the LA9F701 and LA9F702?

                The thread size of the LA9F701 terminal covers is 6mm and the thread size of the LA9F702 is 8mm.

                Data sheets on the items...https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=la9f701 
                ..........................................https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=la9f702

                 

                What is the replacement for LA1DN04?

                The replacement for LA1DN04 is LADN04

                LADN04 
                TeSys D - auxiliary contact block - 4 NC - screw clamp terminals
                Fore more information see:https://www.schneider-electric.com.au/en/product-range-selector/665-tesys-f/?p_url=http%3A%2F%2Fwww.ops-ecat.schneider-electric.com%2Fecatalogue%2Fbrowse.do%3Fel_typ%3Dproduct%26cat_id%3DBU_POW_665_L3_Z010%26conf%3Dbasket%26prd_id%3DLADN04%26scp_id%3DZ010

                Is it possible to add side instantaneous auxiliary contacts blocks to the TeSys D DC coil contactors and relays?

                No, with the TeSYS D range, the DC coil contactors (both standard and low consumption) only allow front mountable auxiliaries.
                The part numbers LAD8N11, LAD8N20 and LAD8N02 will fit only the contactors with AC coils.

                What is the maximum number of units that can be assembled on an XVP beacon tower?

                It is possible to stack a combination of up to 5 illuminated and audible units (one audible unit maximum) to create an XVP beacon tower. 

                Example 1: 5 illuminated lens units 
                Example 2: 4 illuminated lens units + 1 audible signaling unit

                What terminal protection shrouds fit the LR9F5*63, LR9F5*67, and LR9F5*69 overload relays?

                Issue:
                What terminal protection shrouds fit the LR9F5*63, LR9F5*67, and LR9F5*69 overload relays?

                Product Line:
                TeSys F-Line Contactors

                Environment:
                All Product Lines

                Cause:
                Can not find it in the Digest

                Resolution:
                The LA9F702 protection shrouds fit the LR9F5*63, LR9F5*67, and LR9F5*69 overload relays

                Is it possible to modify the neutral position in Masterpact ACB from left hand side to right hand side.

                The offer for Masterpact Air Circuit Breaker (ACB) with neutral position on the both sides is available. This option has to be selected at the time of ordering of ACB.

                 
                Note:
                It is very difficult to modify the neutral position in existing Masterpact ACB from Left side to Right side because the internal wiring of ACB is different for Left side Neutral and Right side Neutral.  It requires dismantling the complete ACB for such modification. This will also lead to the misbehavior of the Micrologic trip unit in ACB like nuisance tripping, incorrect measurement etc. So, it is not possible to modify the Neutral from Left side to Right side in an existing ACB at site.

                Can the single pole LA1DN and LADN auxiliary contact module be mounted on the TeSys contactors?

                ISSUE
                Can the single pole LA1DN and LADN auxiliary contact module be mounted on the TeSys contactors?
                PRODUCT LINE
                Auxiliary contacts for the Tesys D line
                ENVIRONMENT
                Tesys D-Line and Tesys F
                CAUSE
                Fit
                RESOLUTION
                These contacts will only fit on the following contactors:
                Front mount only for LC1D40 through LC1D115 devices and LC1D40A - LC1D65A.
                Left side mount only to LC1F contactors
                CTA-ID : 2002751

                What is the part number for Side mount auxiliary 2NC and terminal shroud for LC1D1506 contactor?

                The part number for Side mount auxiliary 2NC and terminal shroud for LC1D1506 contactor are LAD8N02 and LA9D115703.
                LAD8N02                                                                                                                                    LA9D115703
                 TeSys D - auxiliary contact block - 2 NC - screw clamp terminals                              shrouds - for 3 poles TeSys model D

                For more information see:

                https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LAD8N02
                https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LA9D115703

                                                                                                                                                                                                                                                                                                                                                                                                                       

                                                            

                What limit switch should I use to monitor the operating direction of a sliding gate?

                In order to monitor the operating direction of a sliding gate (detecting movement to the right or to the left) using a single detector, the best solution is to use a 2-step limit switch.

                There are many models of limit switch, but the standard low-cost model with IP66 degree of protection and an operating temperature between -25°C and + 70°C is available in the XCKJ range.

                Standard XCKJ

                The best solution consists therefore in combining:
                 

                • A ZCKJ404 body/contact assembly
                • A ZCKYxx operating head
                • This ZCKJ404 body is made up of 4 contacts distributed as follows:
                   
                • Two 13-14 and 11/12 contacts for activation on the right
                • Two 23-24 and 21-22 contacts for activation on the left
                Cable entry:


                As standard, cable entry for Pg13, part number ZCKJ404

                • ISO M20x1.5 tapped cable entry, part number ZCKJ404H29
                • 1/2 NPT tapped cable entry, part number ZCKJ404H7

                XCKJ for use at low and high temperatures

                For an operating temperature up to - 40°C, use body part number: ZCKJ4046 (add H29 or H7 according to the cable entry).

                For an operating temperature up to +120°C, use body part number: ZCKJ4045 (add H29 or H7 according to the cable entry).

                Caution: For these non-standard temperatures of - 40°C and + 120°C, the operating heads are different to those used between -25°C and + 70°C (see catalogue).






                 

                Show More