Quantcast

Aux Contact Block

Product Dimensions

Width icon

Width38 mm

Height icon

Height30 mm

Depth icon

Depth35 mm

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

TeSys

Range of product

  • TeSys K
  • TeSys K control relay
    • Product or component type

      auxiliary contact block

      Physical

      Range compatibility

    • TeSys K LC1K
    • TeSys K CA2K
    • TeSys K CA3K
      • [Ue] rated operational voltage

        690 V AC 25...400 Hz

        [Ie] rated operational current

      • 6 A at 120 V AC-15
      • 1.04 A at 690 V AC-15
      • 0.55 A at 125 V DC-13
      • 0.1 A at 600 V DC-13
        • Standards

        • EN/IEC 60947-5-1
        • UL 60947-5-1
        • CSA C22.2 No 60947-5-1
        • GB/T 14048.5
          • Product certifications

          • IECEE CB Scheme
          • UL
          • CSA
          • CCC
            • Insulation resistance

              > 10 MOhm

              Connections - terminals

            • screw clamp terminals 1 cable(s) 0.34-1.5 mm²flexible with cable end
            • screw clamp terminals 1 cable(s) 0.75-4 mm²flexible without cable end
            • screw clamp terminals 1 cable(s) 1.5-4 mm²rigid
            • screw clamp terminals 2 cable(s) 0.34-1.5 mm²flexible with cable end
            • screw clamp terminals 2 cable(s) 0.75-4 mm²flexible without cable end
            • screw clamp terminals 2 cable(s) 1.5-4 mm²rigid
              • Height

                30 mm

                Width

                38 mm

                Depth

                35 mm

                Net weight

                0.045 kg

                Environmental characteristic

                normal environment

                IP degree of protection

                IP20 conforming to IEC 60529

                Ambient air temperature for storage

                -50-80 °C

                Ambient air temperature for operation

                -25-50 °C

                REACh Regulation

                Free of Substances of Very High Concern above the threshold

                REACh free of SVHC

                Yes

                EU RoHS Directive

                Compliant

                Toxic heavy metal free

                Yes

                Mercury free

                Yes

                RoHS exemption information

                Yes

                China RoHS Regulation

                 Pro-active China RoHS declaration (out of China RoHS legal scope)

                Others

                Product name

                TeSys K

                Device short name

                LA1

                Mounting location

                front

                Pole contact composition

                4 NO

                Auxiliary contacts operation

                instantaneous

                [Ui] rated insulation voltage

              • 690 V conforming to IEC 60947-5-1
              • 600 V conforming to UL 60947-5-1
              • 600 V conforming to CSA C22.2 No 60947-5-1
                • [Ith] conventional free air thermal current

                  10 A (at 50 °C)

                  Irms rated making capacity

                  110 A at <= 690 V AC conforming to IEC 60947

                  Permissible short-time rating

                • 80 A 1 s
                • 60 A 500 ms
                • 110 A 100 ms
                  • Associated fuse rating

                    10 A gG at <= 690 V conforming to IEC 60947

                    Minimum switching current

                    5 mA

                    Minimum switching voltage

                    17 V

                    Non overlap distance

                    0.5 mm

                    Tightening torque

                    1.3 N.m - with screwdriver Philips No 2

                    Shielding continuity terminal

                    without

                    Compatibility code

                    LA1

                    Protective treatment

                    TC conforming to IEC 60068

                    Operating altitude

                    2000 m

                    Unit Type of Package 1

                    PCE

                    Number of Units in Package 1

                    1

                    Package 1 Weight

                    40 g

                    Package 1 Height

                    4 cm

                    Package 1 width

                    4 cm

                    Package 1 Length

                    3.8 cm

                    Unit Type of Package 2

                    S02

                    Number of Units in Package 2

                    100

                    Package 2 Weight

                    4.555 kg

                    Package 2 Height

                    15 cm

                    Package 2 width

                    30 cm

                    Package 2 Length

                    40 cm

                    WEEE

                    The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                    Show all specifications

                    Documents & downloads

                    hide show
                    Filter items
                    • All

                    • CAD Files and Packs

                    • Product Brochures

                    • Technical Data Catalogues

                    • Installation Instruction

                    • Technical Drawing

                    • Declaration of Conformity