Quantcast

Aux Contact Block

Aux Contact Block

Aux Contact Block

Item Number: LA1KN02

Product Dimensions

Width icon

Width38 mm

Height icon

Height30 mm

Depth icon

Depth35 mm

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Sustainable offer status

Green Premium product

Range

TeSys

Range of product

  • TeSys K
  • TeSys K control relay

Product or component type

auxiliary contact block

Physical

Insulation resistance

> 10 MOhm

Connections - terminals

  • screw clamp terminals 1 cable(s) 0.34-1.5 mm²flexible with cable end
  • screw clamp terminals 1 cable(s) 0.75-4 mm²flexible without cable end
  • screw clamp terminals 1 cable(s) 1.5-4 mm²rigid
  • screw clamp terminals 2 cable(s) 0.34-1.5 mm²flexible with cable end
  • screw clamp terminals 2 cable(s) 0.75-4 mm²flexible without cable end
  • screw clamp terminals 2 cable(s) 1.5-4 mm²rigid

Height

30 mm

Width

38 mm

Depth

35 mm

Net weight

0.045 kg

Environmental characteristic

normal environment

IP degree of protection

IP20 conforming to IEC 60529

Ambient air temperature for storage

-50...80 °C

Ambient air temperature for operation

-25...50 °C

REACh Regulation

Free of Substances of Very High Concern above the threshold

REACh free of SVHC

Yes

EU RoHS Directive

Compliant

Toxic heavy metal free

Yes

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

 Pro-active China RoHS declaration (out of China RoHS legal scope)

Environmental Disclosure

ENVPEP2106022_V1

Range compatibility

  • TeSys K LC1K
  • TeSys K CA2K
  • TeSys K CA3K
  • TeSys K CA4K

[Ue] rated operational voltage

690 V AC 25...400 Hz

Standards

  • EN/IEC 60947-5-1
  • UL 60947-5-1
  • CSA C22.2 No 60947-5-1
  • GB/T 14048.5

Product certifications

  • IECEE CB Scheme
  • UL
  • CSA
  • CCC
  • UKCA

Others

Irms rated making capacity

110 A at <= 690="" v="" ac="" conforming="" to="" iec="">

Permissible short-time rating

  • 80 A 1 s
  • 60 A 500 ms
  • 110 A 100 ms

Associated fuse rating

10 A gG at <= 690="" v="" conforming="" to="" iec="">

Minimum switching current

5 mA

Minimum switching voltage

17 V

Non overlap distance

0.5 mm

Tightening torque

  • 1.3 N.m - with screwdriver Philips No 2
  • 1.3 N.m - with screwdriver pozidriv No 2

Shielding continuity terminal

without

Compatibility code

LA1

Protective treatment

TC conforming to IEC 60068

Operating altitude

2000 m

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Weight

32.0 g

Package 1 Height

3.5 cm

Package 1 width

4 cm

Package 1 Length

3.5 cm

Unit Type of Package 2

S02

Number of Units in Package 2

100

Package 2 Weight

3.695 kg

Package 2 Height

15 cm

Package 2 width

30 cm

Package 2 Length

40 cm

WEEE

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

Product name

TeSys K

Device short name

LA1

Mounting location

front

Pole contact composition

2 NC

Auxiliary contacts operation

instantaneous

[Ui] rated insulation voltage

  • 690 V conforming to IEC 60947-5-1
  • 600 V conforming to UL 60947-5-1
  • 600 V conforming to CSA C22.2 No 60947-5-1

[Ith] conventional free air thermal current

10 A (at 50 °C)
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • CAD Files and Packs

  • Product Brochures

  • Technical Data Catalogues

  • Product Environmental

  • Installation Instruction

  • Technical Drawing

  • Declaration of Conformity

  • Certificates (MSDS)