Max 4 Neutral Active Meter Links, 8 Hole, Link Less Cover

Max 4 Neutral Active Meter Links, 8 Hole, Link Less Cover

Max 4 Neutral Active Meter Links, 8 Hole, Link Less Cover

Item Number: L8A

Retail
N/A
RRP (Inc. GST)

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Product brand

Clipsal

Range of product

Blue Point

Product or component type

neutral link

Physical

[In] rated current

100 A

[Ue] rated operational voltage

500 V

Connector type

screw terminals

EU RoHS Directive

Compliant

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

Product out of China RoHS scope. Substance declaration for your information

Others

Cable cross section

16-16 mm²

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Weight

66 g

Package 1 Height

27 mm

Package 1 width

34 mm

Package 1 Length

80 mm
Show all specifications

Frequently Asked Questions

hide show

How many mounting inches are needed for an I-LINE Powerpact L frame?

Product Line:
Circuit Breakers

Environment:
Powerpact L, I-line version

Resolution:
The I-line version of the Powerpact L Circuit Breaker requires 6 inches of bus. This is sometimes referred to as the "mounting inch requirement".

What is the AC3 rating of the LC1D18***

 The rating is 18A

Difference between LUA contact blocks and LUF contact blocks in a TeSysU

Issue:
What is the difference between the LUA contact blocks and the LUF contact blocks on a TeSysU motor starter?

Product Line:
TeSysU Simple Motor Starters

Environment:
US Product

Resolution:
The LUA contact blocks are for signalling and will change state depending on mode or fault condition(s). These consist of one "Ready Condition" contact that operates with the handle and one "Fault Condition" contact that operates only when a fault is seen.  The LUF contact blocks are standard contact blocks and will change state with the poles.

What is needed to replace a Model 85 Temperature Controller with a Model 98A Retrofit Kit ?

Issue
Retrofit of a Model 85 Temperature Controller.

Product Line
Medium Voltage Dry Type Transformers

Resolution
Use a kit part # 24806-001-50 for Indoor Xfmer or  24806-001-51 for Outdoor Xfmer. Kit comes with K thermocouples to replace existing thermistors . Include serial # of transformer so the controller can be set for correct temperature rise otherwise 80C is default .
 
Attached is the document "Instructions for Field Retrofit of a Model 98A Digital Temperature Controller in place of a Model 85 Temperature Controller" 24806-003-01 Rev 0
This document contains a set of instructions for retrofitting a Model 98A Digital Temperature controller in place of an existing Model 85 Temperature controller.

Model 98A Retrofit Instruction Bulletin.pdf
 

What is the Schneider Electric replacement for a Berger Lahr stepping motor type VRDM368/50LHA with ID number 52024045000 ?

The Schneider Electric reference number of BRS368H130AAA is now used to order the exact replacement motor for Berger Lahr type VRDM368/50 LHA with ID number 52024045000.


rev 1-24-18

Does Schneider Electric offer a suitable replacement for Berger Lahr stepping motor VRDM397/50LNA with ID number 52025015000 ?

Yes, the exact replacement for VRDM397/50 LNA OOIP41 with ID number 52025015000 can be ordered using the new Schneider Electric ordering number of BRS397NS0010

 

what does it mean A1, B1, C1 position ?

It is the position of the RI operating mechanism on SF1 circuit breakers fixed version.
You will find the explanations in the document (ppt) attached

What is the amperage rating of the power distribution block 9080LBA365212, 9080LBA265212, and 9080LBA165212?

Issue:
Checking on the power distribution block 9080LBA365212, 9080LBA265212, and 9080LBA165212 amperage rating.

Product Line:
9080LB

Environment:
9080LBA365212, 9080LBA265212, and 9080LBA165212

Resolution:
It is 620 amps for aluminum wire and 760 amps for copper wire.

 

How can you get to level 2 parameters in the Altivar ATV18?

Issue: How can you get to level 2 parameters in the Altivar ATV18?
 
Product Line: ATV18
 
Environment: All
 
Cause: N/A
 
Resolution: You have to use the arrow key to get to the L2A parameter which you then change to yes and then access is permitted.


 

How do you factory reset the Altivar ATV18 unit?

Issue: How do you factory reset the Altivar ATV18 unit?
 
Product Line: ATV18
 
Environment: All
 
Cause: Factory reset
 
Resolution: First, set parameter L2A to YES so that you can access level 2. Then set parameter FCS to Yes to program the unit for Total factory settings


 

Which driver should be used for the Model 98A in SPM and PME?

Issue
Schneider Electric has 2 temperature controllers:
Model 98 - Black face plate.
Model 98A - Green and white face plate (newer model) 

Which driver is required to communicate to the Model 98A. Can the same driver used for the Model 98 be used for the Model 98A?

Product Line
Model 98
Model 98A
ION Enterprise
StruxureWare Power Monitoring (SPM)
Power Monitoring Expert (PME)

Environment
Management Console
Driver

Resolution
The Model 98A uses the same driver as the Model 98. Please reference the below links for the Model 98 driver.

SPM 7.x and ION 6.0 Model 98 driver
PME 8.0 and PME 8.1 Model 98/98A driver
PME 8.2 and PME 9.0 Model 98/98A driver
 

Do the HV circuit breakers and contactors work at 60 Hz ?

The HV circuit breakers and contactors work as well as 50 Hz and 60 Hz.
IEC 62271 is applicable to a.c. circuit-breakers designed for indoor or outdoor installation and
for operation at frequencies of 50 Hz and 60 Hz on systems having voltages above 1 000 V.

 

Show More