Max 4 Neutral Active Meter Links, 7 Hole, Bar Only

Max 4 Neutral Active Meter Links, 7 Hole, Bar Only

Max 4 Neutral Active Meter Links, 7 Hole, Bar Only

Item Number: L7P

Retail
$57.75
RRP (Inc. GST)

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Product brand

Clipsal

Range of product

Blue Point

Product or component type

link bar

Physical

[In] rated current

100 A

[Ue] rated operational voltage

500 V

Connector type

screw terminals

EU RoHS Directive

Compliant

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

Product out of China RoHS scope. Substance declaration for your information

Others

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Weight

44 g

Package 1 Height

13 mm

Package 1 width

16 mm

Package 1 Length

57 mm
Show all specifications

Frequently Asked Questions

hide show

Do we do the Lup adaptor ?

no it is now discontinued
LUP_ADAPTOR

Part number for a C clip to suit prestige range?

The part name is 154/2

What is the difference in handle length on a LAL36400MB vs a LAL36400?

Issue:  
What is the difference between LA36400 and LA36400MB?  

Product Line:  
Molded Case Circuit Breakers  

Environment:  
Legacy LA, LAL, LH, LHL circuit breakers  

Resolution:  
The MB breaker has a shorter handle, so that it will not interfere with the door closing on a panel.  

Note:  
The MB suffix has a handle that is .325 inches shorter than the standard handle.  

How to program an ATV18 drive for 2 wire control and low speed as speed reference?

Issue:
ATV18 driveset up for 2 wire control and low speed as speed reference.

Product Line:
ATV18, Altivar 18.

Environment:
All.

Cause:
Programming and setup.

Resolution:
2 wire control for ATV18 drive will be between LI1 and +24V terminals.  A maintained dry contact or a jumper can act as a run command. 
Low speed can be used to control the drive locally. 
The low speed parameter can be programmed by hitting down arrow key on the drive until LSP is shown. 
Once LSP shows up press data and use the up and down arrow keys to adjust setting.  Once satisfied with speed press enter to save the setting. 

Where can I find a copy of the ATV61 Installation Manual?

Issue:
Installation manual needed for an Altivar 61 Drive

Product line:
Altivar 61

Environment:
All models, all serial numbers

Cause
Installation manual is not shipped with the drive.

Resolution:
There are two Installation manuals for the ATV61 drives, Low HP (up to 100HP) and High HP (above 100HP).

The installation manual for the Altivar 61 drives up to and including 100 Horsepower can be found at this link: https://www.schneider-electric.us/en/download/document/1760643/
The installation manual for the Altivar 61 drives above 100 Horsepower can be found by following this link: https://www.schneider-electric.us/en/download/document/1760655/

Video: How do you remove the bottom cover on the ATV61 and ATV71?

Issue:
Removal of bottom cover on ATV61 and ATV71.

Product Line:
Altivar ATV61 and ATV71 LHP units only or under 90KW

Environment:
All

Cause:
They can not get the the bottom cover off to check the power terminals.

Resolution:
1st Turn off all power make sure the drive is not powered up and the DC bus is discharged before starting.
You will need to turn the set screw counter clockwise on the control terminal pod.  Next use a flat head screw drive to pry the corners on each side the cover to see if you can work it loose.  Then pull  down cover to remove it.

This procedure is demonstrated in the video below:
Show More