Quantcast

Clipsal C-Bus Dimmer DIN Rail Mounted, Leading Edge, 240V AC, 8 Channel, 1A, With C-Bus Power Supply

Clipsal C-Bus Dimmer DIN Rail Mounted, Leading Edge, 240V AC, 8 Channel, 1A, With C-Bus Power Supply

Clipsal C-Bus Dimmer DIN Rail Mounted, Leading Edge, 240V AC, 8 Channel, 1A, With C-Bus Power Supply

Item Number: L5508D1A

Product Dimensions

Width icon

Width215 mm

Height icon

Height85 mm

Depth icon

Depth65 mm

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Sustainable offer status

Green Premium product

Range

C-Bus

Product brand

Clipsal

Product or component type

dimmer

Device application

control

Physical

[Ue] rated operational voltage

  • 220...240 V AC for dimmer
  • 15...36 V DC for C-Bus

Communication network type

C-Bus

Local signalling

LED

Number of channels

8

Connector type

  • RJ45 for C-Bus
  • RJ45 for remote override

Mounting support

DIN rail

Clamping connection capacity

  • 1 x 2.5 mm²
  • 2 x 1.5 mm²

Width

215 mm

Height

85 mm

Depth

65 mm

Net weight

675 g

Ambient air temperature for operation

0...45 °C

Relative humidity

10...95 %

REACh Regulation

Free of Substances of Very High Concern above the threshold

REACh free of SVHC

Yes

EU RoHS Directive

Compliant

Toxic heavy metal free

Yes

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

 Pro-active China RoHS declaration (out of China RoHS legal scope)

Environmental Disclosure

ENVPEP111268EN

Circularity Profile

ENVEOLI111254EN

Device presentation

basic element

Load type

  • incandescent
  • low voltage lamp with electronic transformer

Dimmer type

leading edge

Others

Standby consumption

10 W

Power supply output current

200 mA

Network frequency

  • 47...53 Hz
  • 57...63 Hz

Maximum number of supported devices

10 per network

Input impedance

50 kOhm at 1-1 kHz

Isolation voltage

3.75 kV from C-Bus to mains

Starting time

5 s

Time delay range

0...33.5 min

Software function

  • select network clock
  • select network burden
  • select time delay range

Number of modules

12

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Weight

786.0 g

Package 1 Height

9.6 cm

Package 1 width

11 cm

Package 1 Length

22.8 cm

WEEE

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

Load current

1 A per channel
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • Product Brochures

  • CAD Files and Packs

  • Technical Data Catalogues

  • Technical Leaflet

  • Installation Instruction

  • Operating Manuals

  • Specifications

  • Application Solutions

  • Declaration of Conformity

  • Certificates (MSDS)

  • Corporate Marketing

  • Software - Archive

  • Software - Release

Frequently Asked Questions

hide show

What to do when C-Bus dimmer channel will not turn off ?

- Initially check that the programming is correct.

- If using LED lights, the LED may stay on when the channel is off, this is due to the leakage current being enough to power the LED, use of a 31LCDA may resolve this issue.

- If using Halogen and  the channel will not turn off, there may be damage to the electronics on this channel - Electricians only to perform this check, disconnect the Active's , Neutral and Earth from the unit, remove the cable for the load on that channel then with a multimeter check between the Neutral and that suspect channel output, if you see a low resistance the Triac has shorted.

- Advise not to use this channel and label as faulty, other channels on this dimmer should still be ok to use as per normal, alternatively you could return this unit for a quote on repair, note a repair may not be possible.

My lights won't dim correctly on a C-Bus Leading Edge Dimmer?

Does this installation have 3 Phase power??

If so, check that the 'Control' side and the 'Switching' Side of the Leading Edge Dimmer are connected on the same voltage phase! You are not able to have a separate voltage phase on either of these connections as this unit is not internally connected...

See, Notes: on page 5 of the linked document