relay c-bus 4 ch 20a din learn

C-Bus DIN Rail Mounted, 250V, 20A, 4 Channel, 12M Modules, 200mA, Power Supply

Catalogue Number: L5504RVF20
relay c-bus 4 ch 20a din learn
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Range of product
C-Bus
Range
C-Bus
Product brand
Clipsal
[Us] rated supply voltage
15...36 V DC
Device composition
socket-outlet
Connector type
screw terminals
Width
215 mm
Height
85 mm
Depth
65 mm
REACh Regulation
Free of Substances of Very High Concern above the threshold
REACh free of SVHC
Yes
EU RoHS Directive
Compliant
Toxic heavy metal free
Yes
Mercury free
Yes
RoHS exemption information
Yes
China RoHS Regulation
 Pro-active China RoHS declaration (out of China RoHS legal scope)

Documents & downloads

hide show
Filter items
  • All

  • CAD Files and Packs

  • Product Brochures

  • Technical Data Catalogues

  • Technical Leaflet

  • Installation Instruction

  • Specifications

  • Application Solutions

  • Corporate Marketing

  • Software - Released

Frequently Asked Questions

hide show

What is the Maximum current which can be drawn through a single channel on a relay

L5504RVF, L5508RVF and L5512RVF are rated for 10A for either resistive, inductive or fluorescent loads

The L5504RVF20 is rated for 20A for either resistive, inductive or flourescent loads

 

What are the C-BUS Relay part numbers?

You have several options for relays, Catalogue numbers and information below.

L5504RVF, L5504RVFP** - 4 Channel voltage free relay - 10amps per channel
L5508RVF, L5508RVFP** - 8 Channel voltage free relay - 10amps per channel
L5512RVF, L5512RVFP** - 12 Channel voltage free relay - 10amps per channel

L5504RVF20, L5504RVF20P** - 4 Channel voltage free relay - 20amps per channel

L5508RELVP - 8 Channel Extra Low Voltage Relay

5101R - Single and Two Channel 250v AC 10amp relay
5102RVF - Single and Two Channel 250v AC 10amp Voltage Free Relay

** Any part number that has a 'P' after the part number for Din Rail mount units does NOT include a C-Bus 200ma Power Supply.

What are the codes for 4 channel, 10A, CBus relays?

L5504RVF - DIN rail mounted 4 channel 10A relay with power supply
L5504RVFP - DIN rail mounted 4 channel 10A relay without CBus power supply

What is the code for a CBus 4 channel relay without power supply

 Part code L5504RVFP

What is the Load Rate of C-Bus 4 Channel Voltage Free Relay (L5504RVF or L5504RVFP)?

C-Bus 4 Channel Voltage Free Relay (L5504RVF or L5504RVFP) Load Rate are Up to 10A for Resistive, Inductive and Fluorescent, Up to 2A for Motor (refer to its Installation Instruction Section 4.0 Compatible Loads, Page 3) 

 

What is the difference between L5508RVFP and L5508RVF?

L5508RVFP and L5508RVF are C-Bus DIN Rail Mounted Relay Units, 250V AC 10A 8 Channel, 12M modules wide. The only difference between the two is L5508RVFP does not come with C-Bus Power Supply and L5508RVF is with 200mA C-Bus internal Power Supply.
For further information, please visit:
https://www.clipsal.com/Trade/Products/ProductDetail?catno=L5508RVFP
https://www.clipsal.com/Trade/Products/ProductDetail?catno=L5508RVF

User-added image
User-added image

Does the L5504RVF have it's own power supply?

Yes it has a 200mA power supply..
For further information , visit link below:-
https://www.clipsal.com/Trade/search-results?q=L5504RVF
User-added image
 

What is the part code for 8 channel relay with power supply for CBUS

 The part code is L5508RVF

What is the Load Rate of C-Bus 8 Channel Voltage Free Relay (L5508RVF or L5508RVFP)?

C-Bus 8 Channel Voltage Free Relay (L5508RVF or L5508RVFP) Load Rate are Up to 10A for Resistive, Inductive and Fluorescent, Up to 2A for Motor (refer to its Installation Instruction Section 4.0 Compatible Loads, Page 3) 

 

What is the replacement for 5101R,1 Channel C-Bus Relay 250V AC 10A inductive load?

Unfortunately we do not have a direct replacement for 5101R. L5504RVFP would be an alternate.
 

Key Features

  • 220 - 240 V AC supply voltage
  • 47 - 53 Hz and 57 - 63 Hz supply frequency
  • Single phase
  • Voltage free, magnetically latched contact type
  • Greater than 60,000 switching operations
  • Compatible with resistive, inductive, incandescent and fluorescent loads up to 10 A
  • 2 x 1.5 mm² or 1 x 2.5 mm² terminals
  • 0˚C - 45˚C operating temperature
  • 10 - 95% RH, humidity range
  • 8 DIN modules
  • DIN mounted
  • 2 x RJ45 sockets connection

For further information, please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=L5504RVFP

Why can't I purchase Schneider Electric US Lighting Control products any more?

Issue:
As of March 1, 2015 all US Lighting Control products (EXCEPT Powerlink and MVP panels) will enter their obsolescence phase and will no longer be purchasable for new orders. Management of the Prosumer Business has made a strategic decision to stop the Lighting Control initiative and concentrate our effort in new businesses with higher growth potential – Connected Home, Building Control in small buildings, and Electric Vehicle solutions.

Product Line:
All US Lighting Control product except Powerlink and MVP panels are affected. CBus, Occupancy Sensors, Low Voltage Switches, Relay Panels, Emergency Lighting Control Panels, Schneider Electric branded Current Limiting Panels, and Architectural Dimming Panels.

Environment:
US Lighting Control products

Cause:
Management of the Prosumer Business has made a strategic decision to stop the Lighting Control initiatives.

Resolution:
See cross reference sheet attached for available completive cross references.
 

What is the part number for a 20A relay?

The part number for a 20A relay is a L5504RVF20.
Some of the key features are:
  • 220 - 240 V AC nominal supply voltage
  • 47 - 53 Hz and 57 - 63 Hz frequency range
  • a.c input impedance 50 ohm at 1 kHz A maximum of 10 units may be connected on a single C-Bus Network
  • Electrical Isolation 3.75 kV RMS from C-Bus to mains
  • Maximum Number of Units on a Single C-Bus Network 10
  • Contact Type Voltage free, magnetically latched
  • Switch Operations Greater than 60,000 operations
  • Quiescent Power 4 W
  • Warm-up Time 5 s
  • Restart Delay 0 s - 42 min and 30 s
  • Network Clock and Network Burden Software selectable
  • Remote switch input can be daisy chained to a maximum of 10 units and a maximum of 1000m of cable
  • Mains Terminals accommodates 2 x 1.5 mm² or 1 x 2.5 mm²
  • C-Bus Connections 2 x RJ45 sockets
  • Operating Temperature Range 0 - 45°C
  • Operating Humidity Range 10 - 95% RH
For further information please visit www.clipsal.com/Trade/Products/ProductDetail?CatNo=L5504RVF20





 
Show More