Clipsal MAX4 Mini Neutral link 100 A 500 V 18 hole with cover Black

Clipsal MAX4 Mini Neutral link 100 A 500 V 18 hole with cover Black

Clipsal MAX4 Mini Neutral link 100 A 500 V 18 hole with cover Black

Item Number: L18

Retail
$192.50
RRP (Inc. GST)

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Product brand

Clipsal

Range of product

Blue Point

Product or component type

neutral link

Physical

[In] rated current

100 A

[Ue] rated operational voltage

500 V

Connector type

screw terminals

REACh Regulation

Free of Substances of Very High Concern above the threshold

EU RoHS Directive

Compliant

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

Product out of China RoHS scope. Substance declaration for your information

Others

Cable cross section

16-16 mm²

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Weight

142 g

Package 1 Height

36 mm

Package 1 width

56 mm

Package 1 Length

84 mm
Show all specifications

Frequently Asked Questions

hide show

What is part number for lockable door kit to suit L18S?

The part number for lockable door kit to suit L18S is MGL18DL.

What distribution board is required for the CH25843 chassis?

For the customized distribution board for 72 pole (18 mm) and 12 pole (27 mm) chassis, you need to submit request for a quote to "au.estimating@schneider-electric.com". Our Standard distribution board only goes up to 60 pole (18 mm) and 12 pole (27 mm).

Are the 593/15 and 593/20 the same size?

No, the 593/15 is 118 x 25 x 15mm and the
593/20 is 130 x 27 x 16.5mm.

For further information please visit https://www.clipsal.com/Trade/search-results?q=593

What is the wire size and torque specs for C60 Multi 9 circuit breakers with lugs?

Issue:
Wire size for Multi 9

Product Line:
Circuit breakers

Environment:
Multi 9 MCB

Cause:
Torque and wire size is marked on the breaker, but users often want this information before they receive the product.

Resolution:
Wire size and torque are as noted below.  Always confirm with markings on the circuit breaker. Only one wire can be installed per terminal. There are no replacement lug kits available for the Multi 9 breakers. The wire strip length is 14 mm.

UL 1077 Supplementary Protectors
0.5 to 25 A: #18 to #4 AWG (1 to 25 mm2) cables; torque 22 lb-in (2.49 N•m)
30 to 63 A: #18 to #2 AWG (1 to 35 mm2) cables; torque 31 lb-in (3.50 N•m)

UL 489 240 Vac
0.5–25 A: #14 to #4 AWG (2–25 mm2) cables; torque to 22 lb-in. (2.48 N•m)
30–35 A: #14 to #2 AWG (1–35 mm2) cables; torque to 31 lb-in. (3.52 N•m)

UL 489 Listed 480 Vac
All amperages: #18 to #16 AWG (1–1.5 mm2), Cu only stranded wire; torque to 7 lb-in (0.68 N•m); #14 to #10 AWG (2–5 mm2), Cu only solid or stranded wire; torque to 14 lb-in (1.6 N•m)

IEC Rated C60 C60N/H/L Except C60L-MA
0.5–25 A: #18 to #4 AWG (1–25 mm2) Cu only cables; torque to 22 lb-in (2.5 N•m)
30–63 A: #18 to #2 AWG (1–35 mm2) Cu only cables; torque to 31 lb-in (3.5 N•m)

Changing Power Flow Sign remotely on a Compact NSX

For remote sites there is a way of connecting remotely to a Micrologic unit to change the Power Flow Sign.
 
On page 118 of the following user guide is talks about Power Flow Sign and has a command code of 47240. This configures the power flow sign.

https://www.schneider-electric.com/en/download/document/DOCA0091EN/

Page 138 of the same guide explains how to do this configuration.

 

How can I check that the input rectifiers are okay on an ATV212 or ATV21 drive?

Issue:
Checking to see if the input rectifiers are okay on an ATV212 or ATV21 drive

Product Line:
Altivar ATV212

Environment:
All models and serial numbers.

Cause:
No power.

Resolution:
Static Diode Test Procedure ATV212:
The following tests are to be performed with NO power to the drive. 
Select diode mode on the meter.
1. To test the diodes on the positive DC bus
    a. Place the black lead of meter on PA+ and the Red lead on L1.  The meter should read about 0.3V
    b. Reverse the meter leads so the black is on L1 and the red is on PA+.  The meter should read OL
    c. Repeat this on L2 and L3
2. To test the diodes on the negative DC bus
    a. Place the black lead of the meter on PC- and the red lead on L1.  The meter should read OL
    b. Reverse the meter leads so the black is on L1 and the red is on PC-.  The meter should read .3V
    c. Repeat this on L2 and L3

Diodes can fail in either shorted or open condition.
 