Quantcast

Clipsal MAX4 Maxi Neutral link 370 A 500 V 13 hole with cover front wiring Black

Clipsal MAX4 Maxi Neutral link 370 A 500 V 13 hole with cover front wiring Black

Clipsal MAX4 Maxi Neutral link 370 A 500 V 13 hole with cover front wiring Black

Item Number: L13/150

Retail
$412.50
RRP (Inc. GST)

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Product brand

Clipsal

Range of product

Blue Point

Product or component type

link bar

Physical

[In] rated current

370 A

[Ue] rated operational voltage

500 V

Connector type

screw terminals

REACh Regulation

Free of Substances of Very High Concern above the threshold

EU RoHS Directive

Compliant

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

Product out of China RoHS scope. Substance declaration for your information

Others

Cable cross section

150-150 mm²

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Weight

705 g

Package 1 Height

60 mm

Package 1 width

60 mm

Package 1 Length

165 mm
Show all specifications

Frequently Asked Questions

hide show

What is the length of the bell mouth 288/150


 The length is 290mm long.
please see following website for catalogue information as well as Technical specifications
https://www.clipsal.com/Trade/Products/ProductDetail?catno=288/150

Can the single pole LA1DN and LADN auxiliary contact module be mounted on the TeSys contactors?

ISSUE
In which contactors can the LA1DN and LADN auxiliary contacts be mounted?

PRODUCT LINE
Auxiliary contacts for the Tesys D line

ENVIRONMENT
Tesys D-Line and Tesys F

RESOLUTION
These contacts will only fit on the following contactors:
Front mount only for LC1D40 through LC1D115 devices and LC1D40A - LC1D65A.
Left side mount only to LC1F contactors

How do I set-up an EGX100 in Slave mode?

Follow the attached document instructions:

How to connect an EGX100 Gateway to an APC UPS Building Management Card on RS232

See Attached Document.

What is the frequency rating of the LX9FF110 coil for a TeSys F LC1F150 contactor?

The LX9FF110 coils have a rating of rating of  110...115 V AC 40...400 Hz  

The older coils LX1FF110 that may be in older catalogues had a fixed frequency of 50 Hertz.

What is the reference for the separate mounting kit for LRD4369 overload relay

The LRD43xx type of thermal overload relays are directly mounted to the contactors LC1D115 & LC1D150 only. There is no separate mounting kit for the LRD43xx.

If a separate mounting is required for the contactors LC1D115 or LC1D150 type, then LRD336xx shall be selected as these range of overload relays have indepentdent mounting and have similar setting range and are of Class 10A.
 