link neutral 12hole

Max 4 Neutral Active Meter Links, 12 Hole Neutral Link

Catalogue Number: L12
link neutral 12hole
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Product brand
Clipsal
Range of product
Blue Point
Product or component type
neutral link
Cable cross section
16-16 mm²
[In] rated current
100 A
[Ue] rated operational voltage
500 V
Connector type
screw terminals
REACh Regulation
Free of Substances of Very High Concern above the threshold
EU RoHS Directive
Compliant
Mercury free
Yes
RoHS exemption information
Yes
China RoHS Regulation
Product out of China RoHS scope. Substance declaration for your information

Frequently Asked Questions

hide show

What is the diameter of part number 412?

Diameter for part number 412 is 47mm.

Varlogic R12 controller options

The only option is the NR12 - part number 52449

What is the diameter for part number 412?

The diameter for part number 412 is 47mm.

Where can I find the User Manual for the VarPlus Logic VL controller?

Issue
User needs the User Manual for the VarPlus Logic VL6 or VL12 controller

Product Line
VarPlus Logic PF Correction Controllers

Environment
Documentation

Resolution
The User Manual for the VarPlus Logic VL6 and VarPlus Logic VL12 controllers is attached

What does the 412 suffix mean on the ATV312 drives?

Issue:
What does the 412 suffix mean on the ATV312 drives?

Product Line:
Altivar 312

Environment:
All models

Cause:
Cannot find source in the USA

Resolution:
Suffix 412 indicates a special ATV312 for solar photovoltaic applications.
It is not marketed in the USA.  Please contact your OEM for suggested replacements.

Is it possible to order the Finger Contacts and Arms of LF2 breaker separately.

The Finger contacts can be ordered separately. Reference for the Finger Contacts Kit for LF2 Breaker is AAV48765. The kit contains 6 sets of Finger Clusters.

 

The arms are not sold separately as it requires industrial control jig to verify the perpendicularity. Hence these are not ordered separately.

What is the new F12 fault error on 5.51 Lexium firmware?

The F12 fault is used to detect whether the motor is connected to the drive power output. ( X9 connector).
To disable this feature, set the parameter CPHASE to zero.


Legacy KB System (APS) Data: RESL156769 V1.0, Originally authored by on , Last Edited by on
Related ranges: Lexium MHD

What is the elbowed female M12 5 meter long connecting cable

 You can use a XZCP1241L5

Is the contactor, LC1D09 available for sale without the coil?

Our LC1D09 to LC1D1506 have to be ordered with a coil voltage. They are not sold less coil. Coil voltages can be found on H12 in the A4 Catalogue.

Is there a neutral bar which has 14 to 16 holes?

Yes we have a Neutral bar with both 14 and 16 holes. The part number for a 14 hole neutral bar is L14 and The part number for a 16 hole neutral bar is L16.

Some of the key features for the L14 are :
  • Two screw In 8 Tunnel and One Screw In 6 Tunnel
  • 2 tunnel, 6.3 mm Diameter accommodate 1 x 16 sq mm cable
  • 6 Tunnel, 5.5 mm Diameter accommodate 1 x 16 sq mm cable
  • 6 Tunnel, 4.5 mm Diameter accommodate 1 x 16 sq mm cable
  • Dimensions: 86 x 57 x 40 mm
  • 100A Rated


Some of the key features for the L16 are:
  • Two screw in 6 tunnels and one screw in 10 tunnel
  • 2 tunnels, 6.3 mm Diameter accommodate 1 x 16 sq mm cable
  • 4 Tunnels, 5.5 mm Diameter accommodate 1 x 16 sq mm cable
  • 10 Tunnels, 4.5 mm Diameter accommodate 1 x 10 sq mm cable
  • Dimensions: 86 x 57 x 40 mm
  • 100A rated


For further information please visit https://www.clipsal.com/Trade/search-results?q=Neutral%20Link

 

What are the available condiut entries for a XCKD, XCKP, or XCKT limit switch?

Issue:
Identifying characteristics from part numbers

Product Line:
XCKD, XCKD, XCKT limit switches
ZCD, ZCP, ZCT limit switches

Environment:
US Product

Cause:
It is necessary to have the appropiate conduit entry on a limit switch

Resolution:
For a complete limit switch (XC devices) use the following suffixes:
P16 - ISO M16
P20 - ISO M20
G11 - Pg11
G13 - PG 13.5
N12 - 1/2" NPT
F12 - PF 1/2" NPSF
D44 - Deutch Connector

For the adapter to fit with a metallic limit switch body (ZCD devices) order the following pieces:
ZCDEP16 - ISO M16
ZCDEP20 - ISO M20
ZCDEG11 - Pg11
ZCDEG13 - PG 13.5
ZCDEN12 - 1/2" NPT
ZCDEF12 - PF 1/2" NPSF

For the adapter to fit with a plastic limit switch body (ZCP, ZCT devices) order the following pieces:
ZCPEP16 - ISO M16
ZCPEP20 - ISO M20
ZCPEG11 - Pg11
ZCPEG13 - PG 13.5
ZCPEN12 - 1/2" NPT
ZCPEF12 - PF 1/2" NPSF
ZCPED44 - Deutch Connector

 

What are the Spare Reference Numbers of Finger Contacts and Arms of LF2 (SF6 Breaker).

The spare reference number of Finger Contacts of LF2 (SF6 Breaker) is AAV48765. A single kit contains 6 sets of Finger clusters.

However, the Arm is not available as spare reference, as it requires industrial control jig to verify the perpendicularity during mounting and this is not possible at Site. Moreover it does not get deteriorated in service and thus is not required to be sold as spare part.

What is the amount of SF6 gas in 24 kV SF Circuit Breaker range.

In 24 KV SF Circuit Breaker range, the weight of the SF6 gas per pole for different Circuit Breakers is as follows:
 
  1. SF1 Type 1 – 49 grams 
     
  2. SF1 Type 2 – 112 grams
     
  3. SF2 – 240 grams

Are there any metal cover plates to suit the PDL 617BT2/2?

Yes, the 612 cover plate suits the PDL 617BT2/2. There are Polished Brass (MPB), Brushed Bronze (MBBZ) and Stainless Steel (MSS).

Code example (617BT2/2 cover in Polish Brass): PDL 612MPB

What is the connector to fit the XUM2AKCNM8T proximity switch

The connector is an M8 4 pin female connector
XZCPV0941L2 for a straight connector with PVC cable
XZCPV1041L2 for an angled connector with PVC cable
XZCP0941L2 for a straight connector with PUR cable for severe environments
XZCPA0941L2 for a straight connector for food & beverage applications
(change L2 to L5 or L10 for 5 or 10m cables)
See attached data sheet

What is the part number for the 512 Mb CF card for the smart and Compact iPCs?

The part number for the 512 Mb Compact Flash card is MPCYN00CFE00N


Legacy KB System (APS) Data: RESL174338 V1.0, Originally authored by on , Last Edited by on
Related ranges: Magelis Smart iPC

Does Schneider Electric offer prefabricated communication cables for Lexium Integrated Drives with industrial cover that have Ethernet communication?

Schneider does offer pre-made cables with M12 on device side and RJ45 on Ethernet switching port side.
The model TCSECL1M3M10S2 is a 10 meter long cable.  (see attached data-sheet)

The connectors that mate to the drive can also be ordered separate using reference number VW3L5K000

VW3L5K000 is a kit and will come with 2 males connectors M12 4 pin D coded and 1 M12 protective cap ( used to terminate last device in network ), for building your own comunication cables.

What is nrdY status on an ATS22 soft starter?

Issue:  
What is nrdY status on an ATS22 soft starter?

Product Line:
Altistart ATS22

Environment:
All

Cause:
nrdY status

Resolution:
There are 2 possibilities.
A stop command is present, with line and control power ON. This means:
LI1 = 0 and LI2 = 1 when in 2 wire control
LI1 = 1 and LI2 = 1 at power up when in 3 wire control

Or
The main line power is not applied to L1, L2, L3.
 

Why is my Conext CL showing an alarm code: 712 & 713 (AC & DC Int Config Fit Service Alarm)

Issue: 
Customer is calling to confirm alarm codes: 712 & 713 (AC&DC Int Config Fit Service Alarm)

Product Line: 
Conext CL 18000NA Conext CL 25000NA Conext 20000E Conext CL 25000E

Environment:  
On site troubleshooting

Cause:
Internal configuration on control processor is incorrect (firmware issue)

Resolution: 
Reset by turning off DC and AC 
Upgrade the firmware (2.6.4 or newer)
Ensure Bootloader (Control Boot) firmware is 2.02.03 or newer

What is the part code for a 5 meter cable for a XS1M12PAW01D Inductive Proximity Sensor?

This proximity Sensor requires a 4 pin M12 female connector, the item required will depend on the environment.
The part code for a 4 pin M12 pre wired female straight connector with PVC flex is XZCPV1141L5 (angled option = XZCPV1241L5)
The part code for a 4 pin M12 pre wired female straight connector with PUR flex for severe environments is XZCP1141L5
The part code for a 4 pin M12 pre wired female straight connector for food & beverage applications is XZCPA1141L5 (ANGLED OPTION = XZCPA1164L5)
2 or 10m options may also be available
See attached data sheet

What are the causes of the Trip Circuit Fault or CB Control Fault on a SEPAM relay and how may it be cleared?

Issue
A trip circuit fault is displayed on the front face of the SEPAM.

Product Line      
SEPAM 20, 40, 50, 80

Environment    
SEPAM programming

Cause
The trip circuit fault on a SEPAM relay is caused by:
1. Circuit breaker control is enabled but the contacts I11 and I12 are not connected, or are connected incorrectly.
2. Circuit breaker control is enabled but the contacts I11 and I12 don't transfer within 200ms.
3. Circuit breaker control is disable but contacts I11 and I12 are assigned to the open and closed status from the breaker.
Note: If SEPAM 80 Series is being used I11 = I101 and I12 = I102.



Resolution
To correct the issue, connect to the relay using SFT2841 then:
Case 1. Wire the breaker status contacts to I11 and I12 or wire these contacts correctly.
Case 2. Go to the program logic screen in SFT2841 and reassign I11 and I12 to either customized use if they are being used, or to not used if the contacts are not wired

Note: Until the fault has been cleared, the relay will continue to show the Trip Circuit Fault on the front display.
To clear the fault from the front display, do the following:
1. Press the Alarm button.
2. Press the Enter key.
3. Press the Clear button to clear the fault.

To clear the fault using SFT2841, do the following:
1. Connect to the relay
2. Click the Alarm button
3. Click the Reset button

 

What is the part numbers for Masterpact NT/NW finger clusters and grease?

Product Line:
Circuit Breakers
Masterpact NT/NW

Environment:
Electrical Distribution Equipment

Resolution:
Finger Cluster (Each) S33166
Cluster Grease (12 oz. Tube) S48899
 

What is the ``solid red`` only knob that can be used on the 9001KR9R or 9001SKR9R push-pull operator?

Issue:
Is there a part number for a solid red knob used on our push pull operators?

Product Line:
Harmony Push Button

Environment:
Harmony 30mm

Resolution:
The 9001R20 (1-3/8`` red mushroom) or the 9001R21 (2-1/4`` red mushroom) can be used for ``solid red`` buttons only.
When used on 9001KR9R or 9001SRK9R operators, 9001R20 and 9001R21 mushroom knobs must be used in conjunction with adapter ring 9001K54 which is available for the purpose at no charge.``)

The ATV71 has LI2 assigned for run reverse. Why does the drive continue to run forward when LI2 goes high?

Issue:
ATV71 has run reverse command assigned to LI2 but the drive continues to run forward when LI2 is activated, 2 wire control.

Product Line:
Altivar 61, Altivar 71.

Environment:
All models, All serial numbers.

Cause:
Drive is not responding to the command to run reverse.

Resolution:
In 2 wire control, logic input LI1 is assigned to run forward. LI1 must be removed when switching to run reverse.  If the drive receives a run reverse command without removing the run forward command, it will continue to run forward.  The same logic holds true when switching from reverse to forward.

How is single phase power connected to ATV320 drives?

Issue:
How is single phase power connected to ATV320 drives?

Product line:
ATV320, Altivar 320

Environment:
all

Cause:
Customer wants to know where to land the single phase wires for line power on ATV320

Resolution:
Per the Installation manual, document NVE41289, a single phase supply is connected to terminals L1 and L2.

Is there a Possibility of displaying L1, L2, L3 permanently? for Tesys T - LTMCU Display

Basically the HMI can not display L1, L2 and L3 at the same time. It can show only one parameter. So in this case it may require scrolling display to show all the values. Option would be to configure the display using Somove to only show L1, L2 and L3 activate scroll to see all the 3 values.

What is the difference between the 140XTS00206 and the 140XTS01206?


140-XTS-002-xx cable is rated for .5 Amps per point (read as point 5 Amps)
140-XTS-012-xx cable is rated for 2 Amps per point (read as 2 Amps)

The following table outlines the different Cablefast cables, their description, and rating:

140 XTS 002 03 3 foot cable with sub "D" connector Standard power .5 Amps
140 XTS 012 03 3 foot cable with sub "D" connector High power 2 Amps
140 XTS 002 06 6 foot cable with sub "D" connector Standard power .5 Amps
140 XTS 012 06 6 foot cable with sub "D" connector High power 2 Amps
140 XTS 002 09 9 foot cable with sub "D" connector Standard power .5 Amps
140 XTS 012 09 9 foot cable with sub "D" connector High power 2 Amps
140 XTS 002 12 12 foot cable with sub "D" connector Standard power .5 Amps
140 XTS 012 12 12 foot cable with sub "D" connector High power 2 Amps
140 XTS 102 06 6 foot cable with pigtail leads High power 2 Amps
140 XTS 102 15 15 foot cable with pigtail leads High power 2 Amps




R-82117


Note: the quantum line will be going obsolete 12/31/2018 and the M580 is the recommended replacement.

How to connect the XUSL4E curtain with the obsolete pre-wired connectors used in the obsolete XUSLD/B curtain range?

XUSL4E type 4 safety light curtains and obsolete XUSLD/B light curtains use similar M12 connectors with the same pin number, on each part of the light curtain. Both side of the obsolete cabling accessories need to be changed for the new curtain XUSL4E connection. Attached document precising how to re-use the obsolete XSZBCT/R pre-wired M12 connectors with the new XUSL4E safety curtain.
 

How to connect the XUSL4E curtain with the obsolete pre-wired connectors used in the obsolete XUSLP equivalent curtain range, for its replacement?

XUSL4E type 4 safety light curtains and obsolete XUSLP equivalent light curtains use similar M12 connectors with the same pin number, on each part of the light curtain. Both side of the obsolete cabling accessories need to be changed for the new curtain XUSL4E connection. Attached document precising how to re-use the obsolete XSZPCT/R pre-wired M12 connectors with the new XUSL4E safety curtain.

How long is the cord on the E12-EO RCD/ MCB switched twin socket outlet?

The cord on the E12 RCD/ MCB switched twin socket outlet is 3 meters long.
Some of its key features are:
  • Overload protection
  • Amber power available neon
  • 3 metre power cord
  • In-built indicator to indicate whether an RCD or MCB fault has occurred
  • In-built test facility
  • 10 mA trip current
  • Trip Time: < 40ms
  • Operating Temperature Range: -10 to 55 deg C
For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=E12
 

How to determine the relay output assignments on the ATV66?

Issue: 
How to determine the relay output assignments on the ATV66?
 
Product Line:
Altivar 66
 
Environment:
All serial number
 
Cause:
N/A
 
Resolution:
Go to the I/O map (Menu 2.0), then 2.3 Logic Output Map.  Here is listed the relay and logic output assignments and the current state (0 or 1) of each.

Do you do the 56K1SW220 with a common key?

Yes, place CK on the end of the part number and the switch will be provided with a 60103 Low and Fletcher Key.

Some of the key features are:

  • Standard security KSW
  • 107 mm Height x 101 mm Width x 112 mm Depth
  • M250 rating
  • 25 - 10 AWG conductor terminal
  • Less enclosure
  • For Locking In Only The Off Position
  • Dust-resistant, hoseproof and UV resistant
  • Safety in operation
For further information please visit www.clipsal.com/Trade/Products/ProductDetail?catno=56K1SW220

 

How to wire power to the Magelis enclosed PC?

Issue:
How to wire power to the Magelis enclosed PC?

Product Line:
HMIPEP

Environment:


Cause:


Resolution:
On the M12 connector for power, jumper 1&2 to the - (negative) and jumper 3&4 to the + (positive)  24V of the power supply.  
 

What is the part number for a replacement for the XSZBCT05?

The Extender XSZBCT05 Transmitter is substitutable by: - XZCP1164L5 - Transmitter Extender - M12 - 5 Pin - Straight - 5m - or XZCP1264L5 - Transmitter Extender - M12 - 5 Pin - Angled - 5m

For further information , visit link below:-
https://www.schneider-electric.com.au/en/search/XZCP1164L5
https://www.schneider-electric.com.au/en/search/XZCP1264L5

User-added image
User-added image

 

Why does my ATV312 drive run in reverse when I trigger my preset speed on LI2?

Issue:
My ATV312 drive runs forward when I trigger LI1, but when I trigger my preset speed on LI2, the drive switches to reverse.

Product Line:
ATV312 series drives.

Environment:
All models, All serial numbers.

Cause:
Run Reverse is assigned to LI2 as factory default.

Resolution:
On the ATV312 drive, the LI2 terminal has "run reverse" assigned to it from the factory.  When using LI2 for another function, including preset speed, you must first un-assign run reverse from this input.

From RDY, Press ENTER and scroll to I_O- menu.  
Press ENTER then scroll to RRS parameter.
Press ENTER then change this parameter to NO and press Enter once more.
ESC back to RDY.  The system should not work properly.
 

What is the recommended distance between control and power cables of VSD?

If using conduit, do not lay the motor, power supply and control cables in the same conduit. Keep metal conduit containing power supply cables at least 8 cm (3 in.) away from metal conduit containing control cables.
Keep non-metal conduits or cable ducts containing power supply cables at least 31 cm (12 in.) away from metal conduits containing control cables.
Keep non-metal conduits or cable ducts containing power supply cables at least 55 cm (12 in.) away from non-metal conduits containing control cables.
If it is necessary for control and power cables to cross each other, be sure they cross at right angles.

 

MSDS Material Safety Data Sheet for cluster grease S48899

Issue:
Where is the MSDS for S48899?

Product Line:
Masterpact NW and NT

Environment:
Cluster grease S48899  (12 oz. Tube)

Cause:
Maintenance

Resolution:
Please see atttached MSDS.

What is the part number for the bus bar to suit the 4RCBE216/30S slim line RCBO ?

The combination Busbars to suit the slim line RCBO's are the  21501 (12 pole) or 21503 (24 pole)
For more information on this product range please visit the Clipsal web site on the link provided.
https://www.clipsal.com/Trade/search-results?q=4rcbe210/30s
 

What is the minimum opening time & closing time for the LF Circuit Breaker.

Schneider Make Circuit Breakers are designed on mean opening time or closing time.
 
The value is same for LF1 or LF2 or LF3 Circuit Breakers. It is linked to the operating mechanism RI used for all the LF Circuit Breaker. 
  1. Mean opening time at Un : 48 ms.
  2. Mean Closing time at Un: 65 ms.

Where Un = Nominal Voltage
 
The minimum opening time and closing time values cannot be defined as these depend on the adjustment made during the short-circuit breaking tests.

On an ATS48, what functions are available for the logic outputs?

Issue:
On an ATS48, what functions are available for the logic outputs?  

Product line:
ATS48, Altistart 48

Environment:
all

Cause:
n/a

Resolution:
Default assignment for LO1 is Motor thermal alarm, tAl.  Default assignment for LO2 is motor powered, rnl.
Available assignments are:
no - not assigned
- tAl - Motor Thermal alarm
- rnl - motor powered
- AIL - motor current alarm
- AUL - motor underload alarm
- APC - motor PTC probe alarm
- AS2 - second set of motor parameters activated.

What is the replacement for XS1N18PA340D Proximity?

The replacement for XS1N18PA340D Proximity is XS518B1PAM12
XS518B1PAM12 inductive sensor XS5 M18 - L50mm - brass - Sn 5mm - 12..24VDC - M12 connector

 

What Unity version installs 140NOC77101 EIP Master DTM V3.6.8 ?


Title
140NOC77101 EIP Master DTM V3.6.8
 
Issue
140NOC77101 EIP Master DTM V3.6.8
 
Product Line
Quantum
 
Environment
Unity Pro
 
Cause
N/A
 
Resolution
 The 140NOC77101 EIP Master DTM V3.6.8 is installed with Unity Pro XL V12 with all its hotfixes. 
A Unity project .ZEF file that uses 140NOC77101 EIP Master DTM V3.6.8 will require the use of either Unity 13 or Unity Pro XL V12 with all its hotfixes.

 

what are the dimensions of the ATV312HU40N4?

Height 184 mm
Width 142 mm
Depth 152 mm

Video: Creating Write_Var Function for FC15 Write Multiple Coils in Unity

This procedure is prepared with Unity Pro v12 software and covers creating a FBD logic section for the M340 Write_Var function block performing a FC15 Write Multiple Coils operation from the BMXNOE0100 ethernet module to an ethernet slave device which supports a Modbus FC15 operation.

 

Video: Configuring MBP_MSTR Function to Explicit Read Quantum PLC over Modbus

This procedure has been created with Unity Pro v12 software. It will cover the configuration and setup for the MBP_MSTR function block to perform an explicit read operation from a node on a Modbus Plus network through the Quantum 140NOM21200 module.

 

Video: Configuring MBP_MSTR Function to Explicit Read Quantum PLC via Native Modbus Plus Port

This procedure has been created with Unity Pro v12 software. It will cover the configuration and setup for the MBP_MSTR function block performing an explicit read operation from a node on a Modbus Plus network through the native Modbus Plus port of a Quantum 140CPU65160 processor.

 

Video: Configuring MBP_MSTR Function Explicit Read Between Quantum 140CPU65160 PLC Native Ethernet Port & Other ModbusTCP Device

This procedure has been created with Unity Pro v12 software. It will cover the configuration and setup for the MBP_MSTR function block to perform an explicit read operation between the Quantum native ethernet port and another supported ModbusTCP device over ethernet.

 

I have an LC1D TeSys D-Line contactor. Which are the coil terminals?

Issue:
I have an LC1D TeSys D-Line contactor.  Which are the coil terminals?

Product Line:
D Line contactors.

Environment:
Products sold in the United States.

Cause:
Product features.

Resolution:
The coil terminals are the ones labelled A1 and A2.


CTA-ID : 2011973

R030_Nuisance tripping on TeSys GV and LRD

Goals and Symptoms

Use this troubleshooting guide if you experience nuisance tripping on TeSys GV and TeSys LRD

Facts and Changes

Nuisance tripping, LRD, GV2, GV3, GV7

Causes and Fixes

Use this troubleshooting guide if you experience nuisance tripping on TeSys GV and TeSys LRD

Attachments

(Removed File URL: 191721_5CB2/R030_How_to_trouble_Shoot_a_Nuisance_tripping_on_GV_and_LRD.pdf)(Removed Image URL: /PubResEXPORT.nsf/2b87ee90be777fc085257c28006ee4ef/92d280a779478116c125757d00422c40/fl_block_5/0.5A8?OpenElement&FieldElemFormat=gif)


Legacy KB System (APS) Data: RESL191721 V3.0, Originally authored by MiFo on 04/21/2008, Last Edited by MiFo on 03/18/2009
Related ranges: TeSys GV2, TeSys GV7, TeSys LR.D, TeSys LR2 K, TeSys GV3

Is "remote reset" function available for GV2 / GV3 / GV7 circuit breakers?

No remote reset  is available for GV2/GV3/GV7 circuit breakers. Remote tripping, using shunt trips, is available but no reset.

Remote resets are available for DT40, C60 and C12 circuit breakers. For these two products use TM60 or TM20 remote control modules.  

Compact NS, Masterpact:

These two product families have optional or native remote reset mechanisms, depending on the part number.
Show More