Max 4 Neutral Active Meter Links, 11 Hole, Suit 25mm� Cables, Front Wiring

Max 4 Neutral Active Meter Links, 11 Hole, Suit 25mm� Cables, Front Wiring

Max 4 Neutral Active Meter Links, 11 Hole, Suit 25mm� Cables, Front Wiring

Item Number: L11/25R

Retail
$151.25
RRP (Inc. GST)

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Product brand

Clipsal

Range of product

Blue Point

Product or component type

active link

Physical

[In] rated current

110 A

[Ue] rated operational voltage

500 V

Connector type

screw terminals

Number of poles

1

EU RoHS Directive

Compliant

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

Product out of China RoHS scope. Substance declaration for your information

Others

Cable cross section

25-25 mm²

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Weight

173 g

Package 1 Height

55 mm

Package 1 width

62 mm

Package 1 Length

108 mm
Show all specifications

Frequently Asked Questions

hide show

What are the part numbers for neutral and active links that take 25mm cable?

The part numbers are L11/25 for the neutral link and L11/25R for the active link.

Is there an active link that can house a 35mm cable available?

Yes the part number is L10/35R

Do we have a neutral link bar with 13 holes and 2 at 25 mm each?

Yes, we have the L13/25.

Is the 801/20R retractable lead still available?

This retractable lead is no longer in our product range and there is no alternative available.

Do we have a replacement for retractable cabel reel 801/20R?

No. Unfortunately, 801/20R is discontinued and there is no replacement.

What is the part number for a 24VAC coil for a LC1D25?

The part number for a 24VAC coil for a LC1D25 is LXD1B7.

what tunnel sizes does the L10/35a have ?

 
 
3 x 9mm diameter to suit 35mm2 and 7 tunnels at 6mm to suit 16mm2
 
 

What is the part number for the spacer used with the LC*D09 through LC*D32 Contactor and the GV2AF3 combination block when the GV2 Motor Circuit Protector is mounted on din rail and the contactor hangs below it?

Issue:
Identifying the spacer part number for use with a LC*D, GV2AF3, and GV2 device combination

Product Line:
Contactors and Starters IEC

Environment:
Tesys D contactors and GV manual starters

Cause:
Spacer required

Resolution:
Compensation plate catalog number GV1F03, requires 2 pieces snap together.

What is the coil burden for the standard DC control coil for the LC*D09__ through LC*D38__ TeSys contactors?

Issue:
LC*D09-38 coil consumption

Product Line:
Contactors and Overload Relays

Environment:
TeSys™ D Contactors and Overload Relays

Resolution:
The standard DC coil is 5.4 watts of consumption.

What is the color scheme of the Tesys D-Line contactors?

Issue:
Looking for different color scheme of the Tesys D-Line contactors.

Product Line:
Tesys D Contactors

Environment:
LC1D contactors

Resolution:
Beige and dark gray.
 

Are the D-Line contactors rated to break DC voltages?

Issue: 
Can the TeSys D line be used to control DC loads? 

Product Line:
Tesys D contactors

Environment:
Products sold and used in the United States
 
Cause:
 DC power circuit
 
Resolution:
 
Yes, 75 VDC (125 VDC for D115 & D150) per pole which means that through a four pole device breaking 300 VDC is possible by wiring all four power poles in series. However, be aware that the device current ratings will differ according to the number of poles in series and the type of application.

Devices are suitable but not UL Listed for DC applications.

More information on their DC ratings can be found in the current TeSys Motor Control and Protection Compentns catalog: https://www.schneider-electric.us/en/download/document/MKTED210011EN/


 

What are the stand alone short circuit current ratings on the LC1D** contactors?

Issue:
Tesys D SCCR

Product Line:
Contactors and Overload Relays

Environment:
TeSys™ D Contactors and Overload Relays
 
Resolution:
The contactors have a stand alone withstand rating that has been established by UL and is based on the maximum horsepower rating for a given device. However, only combination type starters are supplied with short circuit protective devices having a short circuit current rating.

They are as follows:
Horsepower SCCR (A)

0 thru 1 1,000
1 thru 50 5,000
51 thru 200 10,000
201 thru 400 18,000
401 thru 600 30,000
601 thru 900 42,000
901 thru 1600 85,000
1601+ 100,000
Show More