Max 4 Neutral Active Meter Links, 11 Hole, Suit 25mm² Cables, Back Wiring

Max 4 Neutral Active Meter Links, 11 Hole, Suit 25mm² Cables, Back Wiring

Max 4 Neutral Active Meter Links, 11 Hole, Suit 25mm² Cables, Back Wiring

Item Number: L11/25BW

Retail
$185.63
RRP (Inc. GST)

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Product brand

Clipsal

Range of product

Blue Point

Product or component type

neutral link

Physical

[In] rated current

110 A

[Ue] rated operational voltage

500 V

Connector type

screw terminals

Number of poles

1

EU RoHS Directive

Compliant

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

Product out of China RoHS scope. Substance declaration for your information

Others

Cable cross section

25-25 mm²

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Weight

175 g

Package 1 Height

60 mm

Package 1 width

60 mm

Package 1 Length

108 mm
Show all specifications

Frequently Asked Questions

hide show

What are the part numbers for neutral and active links that take 25mm cable?

The part numbers are L11/25 for the neutral link and L11/25R for the active link.

What is the inrush current for the LC1D25B7 Contactor?

The inrush current of the LC1D25B7 will be 70VA..or 2.92 Amps
see technical data sheet on coil...
https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=lxd1b7
 

What is the part number of the spare coil for LC1D25B7 contactor?

LXD1B7 is the part number of the spare coil to suit LC1D25B7 contactor. For further information on the coil, please refer to the attached datasheet.
 

What is the complete part number for a 25A 11Kw 3P Contactor with 24VDC coil?

LC1D25BD is the correct part number

What is the difference between the LAD4TB and LAD4TBDL bi-directional peak limiting diode?

Issue:
Identifying the difference between LAD4TB and LAD4TBDL

Product Line:
IEC contactors and starters

Environment:
Products sold and used in the United States

Cause:
Identifying the difference between two similar part numbers

Resolution:
The LAD4TB is for 24V AC coils for the Tesys Series LC1D09 through LC1D38 contactors when supplied with G7 voltage code. The LAD4TBDL is 24 vdc bi-directional diode offered as a replacement if for some reason the diode supplied with the Tesys LC1D09 through LC1D38 contactors when ordered with BD or BL voltage code breaks or is no longer working.


 

What is the altitude derating for a TeSys D-Line contactor?

Issue:​
What is the altitude derating for a TeSys D-Line contactor?

Product Line:
Digest 177 Section 18 : Contactors and Starters, IEC

Environment:
North American Products

Resolution:
The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

Voltage
3500m x 0.90
4000m x 0.80
4500m x 0.70
5000m x 0.60

Current
3500m x 0.92
4000m x 0.90
4500m x 0.88
5000m x 0.86

For example, an LC1D80 at 5000 meters:
- The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
- The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



 
Show More