Specifications

Design

Product brand

Clipsal

Range of product

Blue Point

Product or component type

active link

Physical

[In] rated current

100 A

[Ue] rated operational voltage

500 V

Connector type

screw terminals

EU RoHS Directive

Compliant

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

Product out of China RoHS scope. Substance declaration for your information

Others

Cable cross section

16-16 mm²

Package 1 Weight

0.001 kg
Show all specifications

Frequently Asked Questions

hide show

What input is designed for a bipolar -10v to +10v input on the ATV32 drives?

Issue:
Analog Input designed for a bipolar -10v to +10v input on the ATV32 drives

Product Line:
Altivar ATV32

Environment:
All

Cause:
AI2 is default for -10v to +10v input.

Resolution:
IO menu AI2 set up

 Bipolar analog input 0 ± 10 V (maximum voltage ± 30 V)

The + or - polarity of the voltage on AI2 affects the direction of the set point and therefore the direction of operation.

• Impedance 30 kU
• Resolution: 10 bits
• Precision ±0.5% in 50/60 Hz for 25 °C, ±0.2% in 50/60 Hz for –10 to +60 °C at Ae = 60°C,
• Linearity ± 0.2% (max. ± 0.5%), of max. value
• Sampling time 2 ms

What is the bolt hole size of the 31100 INS250-100?

The bolt hole size is M10 for the INS250-100....INS250-250

see attachment

Whats are the dimensions of the T200, T200FA, T200F, T200X, T200L, T200S

 210 x 158 x 112mm (L x D x W) 

How do I configure my ATV312 drive for forward and reverse direction using +10/-10V speed reference?

Issue:
ATV312 configuration for forward and reverse using +10/-10V speed reference

Product Line:
Altivar 312 series drives.

Environment:
All models, All serial numbers.

Cause:
Customer needs to control the drive forward and reverse with a single run command and +10 to -10V input for speed/direction control.

Resolution:
AI2 input can be used for +10 to -10V input.   Configure parameter FR1 to AI2 under the CTL menu to have the drive look at AI2 as the primary speed reference.  Connect your +10/-10V speed reference between AI2 and COM on the drive.
 

What is the Com'X 510 Default Username and Password?

The Default Password and Username for ComX 510 are:
User = admin
Password = admin
See link for further Product information:https://www.se.com/au/en/product/EBX510/comx-510---energy-server---ul---sdram4-go/
EBX510 Product picture

Can the Altivar ATV312 Drives do single phase 110 VAC input?

Issue:
ATV312 single phase 110 VAC input

Product Line:
ATV312 Drives

Environment:
All serial numbers for ATV312 Drives

Cause:
N/A

Resolution:
No it cannot. The drive can only do 208/230 VAC single-phase on the single phase input rated drives that have the M2 suffix..