Clipsal MAX4 Mini Neutral link 100 A 500 V 10 hole with cover Black

Clipsal MAX4 Mini Neutral link 100 A 500 V 10 hole with cover Black

Clipsal MAX4 Mini Neutral link 100 A 500 V 10 hole with cover Black

Item Number: L10

Retail
$36
RRP (Inc. GST)

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

MAX9

Product brand

Clipsal

Range of product

Blue Point

Product or component type

active link

Physical

[In] rated current

100 A

[Ue] rated operational voltage

500 V

Connector type

screw terminals

REACh Regulation

Free of Substances of Very High Concern above the threshold

EU RoHS Directive

Compliant

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

Product out of China RoHS scope. Substance declaration for your information

Others

Cable cross section

16-16 mm²

Number of mounting holes

10

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Weight

58 g

Package 1 Height

30 mm

Package 1 width

50 mm

Package 1 Length

78 mm
Show all specifications

Frequently Asked Questions

hide show

Multi-9 C60 Breakers: Values for Watts Loss and Voltage Drop per pole

Issue:
Power Loss
Watts Loss
Contact Resistance
Voltage Drop

Product Line:
Circuit Breakers

Environment:
Applies to Multi-9, C60 Circuit Breakers (UL489 and UL1077)

Resolution:
The attached document gives the Power Loss (Watts Loss) and Voltage Drop per pole, at rated current of the breaker (nominal current). For example, a 1A breaker would be expected to have a Watts Loss per pole of 2.3 W, at rated current of 1A. This information can be used to calculate voltage drop when used at other than nominal current.

Can Multi-9 C60 breakers be continuously loaded to 100% of their rating?

Issue:
Can Multi-9 C60 breakers be continuously loaded to 100% of their rating?

Product Line:
Multi 9 C60 MCB's

Resolution:
UL 489 Listed Multi 9 C60 circuit breakers may be loaded to no more than 80% if used with continuous loads.
UL 1077 recognized supplementary protectors may be operated at 100% of their rating.
IEC 60947-2 C60 breakers may be operated at 100% of their rating.

What is the meaning of the B, C, D, K, and Z curves for C60 Multi-9 circuit breakers?

Issue:  
What do the B curve, C curve, D curve, K curve and Z curve designations mean on Multi 9 breakers?

Product Line:
Circuit Breakers

Resolution:
For C60 Multi-9 devices, AC rated, the following is the meaning of the trip curves (in reference to instantaneous trip rating):
B curve: 3.2 - 4.8 times amp rating for UL489 and UL1077 (3 - 5 times amp rating for IEC)
C curve: 7 - 10 times amp rating
D curve: 10 - 14 times amp rating
K curve: 10 - 14 times amp rating
Z curve: 2.4 to 3.6 times amp rating
Trip curves are included in the 0860CT0201 catalog.

What is the time settings for a PDL100MPIR sensor ?

10 secs to 15 mins.

Please go to the link for more information:
https://productspec.co.nz/media/okvnvun0/installation-and-operating-instructions-for-100mir-modular-passive-infrared-sensor.pdf

What is the minimum Load for a WDL10?

 None, (N/O relay contacts)

Please go to the link below for more information.
https://updates.clipsal.com/clipsalonline/Files/Brochures/W0001160.pdf

How do you mount a R9 rod onto a L100 limit switch?

Issue:
How do you mount a R9 rod onto a L100 limit switch

Product Line:
Limit Switches

Environment:
Type L100

Cause:
The need to know if another part is needed.

Resolution:
It will require a hub R6
Show More