Key Features & Specifications

hide show
  • 3.6 kA permissible rated peak current
  • 10 and 16 A rated tap-off units current
  • 690 V rated insulating voltage
  • Number of conductors: 2 or 4 + PE
  • Centre to centre distance between tap-off units: 1.2m to 3 m
  • Modular, economic and upgradeable system
  • Quick and easy assembly
  • Flexible: access points available wherever they are required
  • Compact: easy to fit in a hanging celling or raised floor
  • Halogen free: canalis does not emit any fumes or toxic gases in the event of fire
  • Dismantled, re-used and entirely recyclable
  • Distribution length
  • 4 kV Rated impulse withstand voltage
  • L2 + L1 + L3 + N + PE Busbar trunking polarity
  • 1500 mm Tap-off Unit Interval
  • For use in lighting power socket distribution
  • 3 phase
Range
Canalis
Range of product
Canalis
Product or component type
busbar trunking
Device short name
KDP
Product compatibility
KDP
Busbar description
flexible bar
Device application
  • lighting
  • power socket distribution
    • [Ue] rated operational voltage
      230...400 V
      [Uimp] rated impulse withstand voltage
      4 kV
      [Ui] rated insulation voltage
      690 V
      [Ie] rated operational current
      20 A at 35 °C
      [Icw] rated short-time withstand current
      0.34 kA
      [Ipk] rated peak withstand current
      3.6 kA
      Network frequency
      50/60 Hz
      Maximum radiated magnetic field
      2 pT
      THDI
    • 0-15 % 20 A
    • 15-33 % 16 A
    • 33-100 % 14 A
      • Maximum voltage drop
      • <0.72 V with power factor = 1 at 50 Hz with 1A for 100 m long
      • <0.65 V with power factor = 0.9 at 50 Hz with 1A for 100 m long
      • <0.58 V with power factor = 0.8 at 50 Hz with 1A for 100 m long
      • <0.5 V with power factor = 0.7 at 50 Hz with 1A for 100 m long
        • Linear resistance
        • 6.8 mΩ/m R20 20 °C phase conductor
        • 0.85 mΩ/m X0 20 °C symmetrical components method Ph/PE
        • 27.22 mΩ/m Z0 20 °C symmetrical components method Ph/PE
        • 13.61 mΩ/m Rb0 20 °C impedance method Ph/Ph
        • 13.61 mΩ/m Rb0 20 °C impedance method Ph/N
        • 13.61 mΩ/m Rb0 20 °C impedance method Ph/PE
        • 16.6 mΩ/m Rb1 35 °C at Inc with impedance method Ph/Ph
        • 16.6 mΩ/m Rb1 35 °C at Inc with impedance method Ph/N
        • 16.6 mΩ/m Rb1 35 °C at Inc with impedance method Ph/PE
        • 0.04 mΩ/m Xb 35 °C at Inc and 50 Hz with impedance method Ph/Ph
        • 0.04 mΩ/m Xb 35 °C at Inc and 50 Hz with impedance method Ph/N
        • 8.3 mΩ/m R1 35 °C at Inc and 50 Hz phase conductor
        • 0.04 mΩ/m Xb 35 °C at Inc and 50 Hz with impedance method Ph/PE
        • 0.02 mΩ/m X1 35 °C at Inc and 50 Hz phase conductor
        • 8.3 mΩ/m Z1 35 °C at Inc and 50 Hz phase conductor
        • 7.25 mΩ/m 20 °C protective conductor
        • 27.21 mΩ/m R0 20 °C symmetrical components method Ph/N
        • 0.85 mΩ/m X0 20 °C symmetrical components method Ph/N
        • 27.22 mΩ/m Z0 20 °C symmetrical components method Ph/N
        • 27.21 mΩ/m R0 20 °C symmetrical components method Ph/PE
          • Busbar trunking polarity
            L2 + L1 + L3 + N + PE
            Tap-off unit interval
            3000 mm
            Type of packing
            spool
            Standards
          • EN/IEC 60439-2
          • EN/IEC 61439-6
            • Length
              23 m
              Net weight
              7.68 kg
              IP degree of protection
              IP55 conforming to IEC 60529
              IK degree of protection
              IK07 conforming to IEC 62262
              Ambient air temperature for operation
            • 35-40 °C (93 % of In)
            • 40-45 °C (85 % of In)
            • 45-50 °C (76 % of In)
            • 50-55 °C (66 % of In)
            • 0-35 °C (100 % of In)
              • EU RoHS Directive
                Pro-active compliance (Product out of EU RoHS legal scope)
                Environmental Disclosure
                ENVPEP061103EN
                Warranty
                18 months

                Documents & downloads

                hide show
                Filter items
                • All

                • Product Brochures

                • Technical Data Catalogues

                • Technical Leaflet

                • Product Environmental

                • Installation Instruction

                • Specification for Tender

                • Application Solutions

                • Certificates (MSDS)

                • Corporate Marketing