MASTER YOUR CASTLE with your new build or reno project
Enter competition
KBB40ED22305

KBB40ED22305

Discontinued

Canalis Straight Distribution Lengths, 40A, 3M

KBB40ED22305
Colour:
Colour: Per UOM Std.
  • 1 PCE
Added to cart
Successfully added, you can view your cart here

Key Features & Specifications

hide show
  • 10 A and 16 A rated tap-off units current
  • 690 V rated insulating voltage
  • Number of circuits: 1 circuit (2 or 4 conductors)
  • Modular and upgradeable system
  • Quick and easy assembly
  • Flexible: possibility to install a light right where it is needed
  • Halogen free: canalis does not emit any fumes or toxic gases in the event of fire
  • Dismantled, re-used and entirely recyclable
Range
Canalis
Range of product
Canalis
Product or component type
busbar trunking
Device short name
KBB
Product compatibility
KBB
Device application
  • lighting
  • power socket distribution
    • Maximum radiated magnetic field
      2 pT
      [Ue] rated operational voltage
      230...400 V
      [Uimp] rated impulse withstand voltage
      4 kV
      [Ui] rated insulation voltage
      690 V
      [Ie] rated operational current
      40 A at 35 °C
      Network frequency
      50/60 Hz
      [Icw] rated short-time withstand current
      0.94 kA
      [Ipk] rated peak withstand current
      9.6 kA
      Thermal stress limit
      900 kA².s
      THDI
    • 0-15 % 40 A
    • 15-33 % 32 A
    • 33-100 % 28 A
      • Maximum voltage drop
      • <0.3 V with power factor = 1 at 50 Hz with 1A for 100 m long
      • <0.28 V with power factor = 0.9 at 50 Hz with 1A for 100 m long
      • <0.25 V with power factor = 0.8 at 50 Hz with 1A for 100 m long
      • <0.22 V with power factor = 0.7 at 50 Hz with 1A for 100 m long
        • Linear resistance
        • 0.02 mΩ/m X1 35 °C at Inc and 50 Hz phase conductor
        • 5.68 mΩ/m Rb0 20 °C impedance method Ph/N
        • 0.9 mΩ/m Xb 35 °C at Inc and 50 Hz with impedance method Ph/Ph
        • 0.9 mΩ/m Xb 35 °C at Inc and 50 Hz with impedance method Ph/N
        • 17.28 mΩ/m R0 20 °C symmetrical components method Ph/N
        • 5.25 mΩ/m X0 20 °C symmetrical components method Ph/N
        • 18.06 mΩ/m Z0 20 °C symmetrical components method Ph/N
        • 6.92 mΩ/m Rb0 20 °C impedance method Ph/PE
        • 6.92 mΩ/m Rb1 35 °C at Inc with impedance method Ph/Ph
        • 6.92 mΩ/m Rb1 35 °C at Inc with impedance method Ph/N
        • 7.14 mΩ/m Rb1 35 °C at Inc with impedance method Ph/PE
        • 0.8 mΩ/m protective conductor
        • 1.85 mΩ/m Xb 35 °C at Inc and 50 Hz with impedance method Ph/PE
        • 2.83 mΩ/m R20 20 °C phase conductor
        • 3.46 mΩ/m R1 35 °C at Inc and 50 Hz phase conductor
        • 3.46 mΩ/m Z1 35 °C at Inc and 50 Hz phase conductor
        • 13.83 mΩ/m R0 20 °C symmetrical components method Ph/PE
        • 0.73 mΩ/m X0 20 °C symmetrical components method Ph/PE
        • 13.85 mΩ/m Z0 20 °C symmetrical components method Ph/PE
        • 5.68 mΩ/m Rb0 20 °C impedance method Ph/Ph
          • Mounting mode
            by screws
            Busbar description
            straight length
            Busbar trunking polarity
            L + N + PE
            Number of circuits
            2
            Number of tap-off outlets
            5
            Control type
            without
            Standards
          • EN/IEC 60439-2
          • EN/IEC 61439-6
            • Width
              3100 mm
              Depth
              51 mm
              Height
              60 mm
              Length
              3 m
              Net weight
              5.2 kg
              Quantity per set
              set of 6
              IP degree of protection
              IP55 conforming to EN/IEC 60529
              IK degree of protection
              IK06 conforming to EN/IEC 62262
              Ambient air temperature for operation
            • 0-35 °C (100 % of In)
            • 35-40 °C (96 % of In)
            • 40-45 °C (93 % of In)
            • 45-50 °C (89 % of In)
            • 50-55 °C (85 % of In)
              • Sustainable offer status
                Green Premium product
                EU RoHS Directive
                Pro-active compliance (Product out of EU RoHS legal scope)
                Environmental Disclosure
                ENVPEP061102EN
                Warranty
                18 months

                Documents & downloads

                hide show
                Filter items
                • All

                • Product Brochures

                • CAD Files and Packs

                • Technical Data Catalogues

                • Technical Leaflet

                • Product Environmental

                • Installation Instruction

                • Specifications

                • Certificates (MSDS)

                • Declaration of Conformity