Quantcast

Canalis KBA, Straight length, Canalis KBA, 40A, 1 circuit 3L+N+PE, 3 tap-off units, 3m

Canalis KBA, Straight length, Canalis KBA, 40A, 1 circuit 3L+N+PE, 3 tap-off units, 3m

Canalis KBA, Straight length, Canalis KBA, 40A, 1 circuit 3L+N+PE, 3 tap-off units, 3m

Item Number: KBA40ED4303

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

Canalis

Range of product

Canalis

Product compatibility

KBA

Product or component type

busbar trunking

Device application

  • lighting
  • power socket distribution

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

[Ie] rated operational current

40 A at 35 °C

[Ue] rated operational voltage

230...400 V

Control type

without

Mounting mode

by clips

Standards

  • EN/IEC 61439-6
  • EN/IEC 61439-1

Width

30 mm

Height

46 mm

Length

3 m

Net weight

3.1 kg

IP degree of protection

IP55 conforming to EN/IEC 60529

IK degree of protection

IK06 conforming to EN/IEC 62262

Ambient air temperature for operation

  • 0...35 °C (100 % of In)
  • 35...40 °C (96 % of In)
  • 40...45 °C (93 % of In)
  • 45...50 °C (89 % of In)
  • 50...55 °C (85 % of In)

REACh free of SVHC

Yes

EU RoHS Directive

Compliant

Toxic heavy metal free

Yes

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

X

Environmental Disclosure

ENVPEP061101EN

Others

Device short name

KBA

Busbar description

straight length

Network frequency

50/60 Hz

Busbar trunking polarity

3L + N + PE

Number of circuits

1

Number of tap-off outlets

3

[Uimp] rated impulse withstand voltage

4 kV

[Ui] rated insulation voltage

690 V

[Icw] rated short-time withstand current

0.94 kA

[Ipk] rated peak withstand current

9.6 kA

Thermal stress limit

900 kA².s

Maximum radiated magnetic field

2 pT

THDI

  • 0...15 % 40 A
  • 15...33 % 32 A
  • 33...100 % 28 A

Maximum voltage drop

  • <0.3 v="" with="" power="" factor="1" at="" 50="" hz="" with="" 1a="" for="" 100="" m="">
  • <0.28 v="" with="" power="" factor="0.9" at="" 50="" hz="" with="" 1a="" for="" 100="" m="">
  • <0.25 v="" with="" power="" factor="0.8" at="" 50="" hz="" with="" 1a="" for="" 100="" m="">
  • <0.22 v="" with="" power="" factor="0.7" at="" 50="" hz="" with="" 1a="" for="" 100="" m="">

Linear resistance

  • 0.02 mΩ/m X1 35 °C at Inc and 50 Hz phase conductor
  • 2.83 mΩ/m R20 20 °C phase conductor
  • 3.46 mΩ/m R1 35 °C at Inc and 50 Hz phase conductor
  • 3.46 mΩ/m Z1 35 °C at Inc and 50 Hz phase conductor
  • 13.83 mΩ/m R0 20 °C symmetrical components method Ph/PE
  • 0.73 mΩ/m X0 20 °C symmetrical components method Ph/PE
  • 13.85 mΩ/m Z0 20 °C symmetrical components method Ph/PE
  • 5.68 mΩ/m Rb0 20 °C impedance method Ph/Ph
  • 5.68 mΩ/m Rb0 20 °C impedance method Ph/N
  • 0.9 mΩ/m Xb 35 °C at Inc and 50 Hz with impedance method Ph/Ph
  • 0.9 mΩ/m Xb 35 °C at Inc and 50 Hz with impedance method Ph/N
  • 1.57 mΩ/m protective conductor
  • 0.035 mΩ/m Xb 35 °C at Inc and 50 Hz with impedance method Ph/PE
  • 19.4 mΩ/m R0 20 °C symmetrical components method Ph/N
  • 0.38 mΩ/m X0 20 °C symmetrical components method Ph/N
  • 19.41 mΩ/m Z0 20 °C symmetrical components method Ph/N
  • 7.66 mΩ/m Rb0 20 °C impedance method Ph/PE
  • 6.91 mΩ/m Rb1 35 °C at Inc with impedance method Ph/Ph
  • 6.91 mΩ/m Rb1 35 °C at Inc with impedance method Ph/N
  • 8.7 mΩ/m Rb1 35 °C at Inc with impedance method Ph/PE

Unit Type of Package 1

PCE

Number of Units in Package 1

1

WEEE

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

Halogen content performance

Halogen free product
Show all specifications