Gv2 GV3 Undervolt Trip 415V Rhs Mt

Gv2 GV3 Undervolt Trip 415V Rhs Mt

Gv2 GV3 Undervolt Trip 415V Rhs Mt

Item Number: GVAU415

Retail
$229.01
RRP (Inc. GST)

Product Dimensions

Width icon

Width18 mm

Height icon

Height89 mm

Depth icon

Depth66 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

  • TeSys GV2
  • TeSys GV3
    • Range

      TeSys

      Product or component type

      undervoltage release

      Sustainable offer status

      Green Premium product

      Warranty

      18 months

      Physical

      Range compatibility

    • GV2ME
    • GV2LE
    • GV2L
    • GV2P
    • GV3L
    • GV3P
      • Connections - terminals

      • screw clamp terminals 1 cable(s) 1-2.5 mm²solid
      • screw clamp terminals 2 cable(s) 1-2.5 mm²solid
      • screw clamp terminals 1 cable(s) 0.75-2.5 mm²flexible without cable end
      • screw clamp terminals 2 cable(s) 0.75-2.5 mm²flexible without cable end
      • screw clamp terminals 1 cable(s) 0.75-1.5 mm²flexible with cable end
      • screw clamp terminals 2 cable(s) 0.75-1.5 mm²flexible with cable end
        • Mechanical durability

        • 10000 cycles with GV3P and GV3L
        • 30000 cycles with GV2ME and GV2P
          • Quantity per set

            set of 10

            Height

            89 mm

            Width

            18 mm

            Depth

            66 mm

            Net weight

            0.105 kg

            REACh free of SVHC

            Yes

            EU RoHS Directive

            Compliant

            Toxic heavy metal free

            Yes

            Mercury free

            Yes

            RoHS exemption information

            Yes

            China RoHS Regulation

            X

            Environmental Disclosure

            ENVPEP111252EN

            Others

            Device short name

            GVAU

            [Uc] control circuit voltage

          • 415...440 V AC 50 Hz
          • 480 V AC 60 Hz
            • Control circuit voltage limits

              0.85...1.1 Un

              [Ui] rated insulation voltage

            • 690 V AC conforming to IEC 60947-1
            • 600 V AC conforming to UL 60947-4-1
            • 600 V AC conforming to CSA C22.2 No 60947-4-1
              • Threshold tripping voltage

                0.7...0.35 Un

                Inrush power in VA

                12-12 VA AC

                Inrush power in W

                8 W

                Hold-in power consumption in VA

                3.5-3.5 VA AC

                Hold-in power consumption in W

                1.1-1.1 W

                Operating time

                10...15 ms conforming to IEC 60947-1

                On-load factor

                100 %

                Tightening torque

                < 1.4 N.m on screw clamp terminals

                Compatibility code

                GVAU

                Package 1 Weight

                0.115 kg

                Package 1 Height

                0.83 dm

                Package 1 width

                0.36 dm

                Package 1 Length

                0.91 dm

                WEEE

                The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                Show all specifications

                Documents & downloads

                hide show
                Filter items
                • All

                • CAD Files and Packs

                • Product Brochures

                • Technical Data Catalogues

                • Product Environmental

                • Installation Instruction

                • eTechPub

                Frequently Asked Questions

                hide show

                Can GVAU225 operate on 60 HZ?

                What is the length of the shaft in the GV3APN02 kit?

                 The shaft included in the GV3APN02 kit is a GVAPA1. It has a length of 315 mm.
                 

                What does Pitch refer to in regards to the GV2G busbar system?

                Issue: 
                Need to know what 45mm, 54mm, and 72mm pitch means

                Product Line:
                GV2 Manual Starters

                Environment:
                IEC Contactors and Starters

                Resolution:
                The pitch is the spacing between slots. In order to select the correct pitch, total up the width of the device, plus any side mounted auxiliaries. Use the total width for selecting the proper pitch. The busbar pitch selection must be the same or greater than the sum of device and auxiliaries.