Quantcast

Gv2 GV3 Undervolt Trip 24V Rhs Mt

Gv2 GV3 Undervolt Trip 24V Rhs Mt

Gv2 GV3 Undervolt Trip 24V Rhs Mt

Item Number: GVAU025

Retail
$229.01
RRP (Inc. GST)

Product Dimensions

Width icon

Width18 mm

Height icon

Height89 mm

Depth icon

Depth66 mm

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

  • TeSys GV2
  • TeSys GV3
    • Range

      TeSys

      Product or component type

      undervoltage release

      Sustainable offer status

      Green Premium product

      Warranty

      18 months

      Physical

      Range compatibility

    • GV2ME
    • GV2LE
    • GV2L
    • GV2P
    • GV3L
    • GV3P
      • Connections - terminals

      • screw clamp terminals 1 cable(s) 1-2.5 mm²solid
      • screw clamp terminals 2 cable(s) 1-2.5 mm²solid
      • screw clamp terminals 1 cable(s) 0.75-2.5 mm²flexible without cable end
      • screw clamp terminals 2 cable(s) 0.75-2.5 mm²flexible without cable end
      • screw clamp terminals 1 cable(s) 0.75-1.5 mm²flexible with cable end
      • screw clamp terminals 2 cable(s) 0.75-1.5 mm²flexible with cable end
        • Mechanical durability

        • 10000 cycles with GV3P and GV3L
        • 30000 cycles with GV2ME and GV2P
          • Quantity per set

            set of 10

            Height

            89 mm

            Width

            18 mm

            Depth

            66 mm

            Net weight

            0.105 kg

            REACh Regulation

            Free of Substances of Very High Concern above the threshold

            REACh free of SVHC

            Yes

            EU RoHS Directive

            Compliant

            Toxic heavy metal free

            Yes

            Mercury free

            Yes

            RoHS exemption information

            Yes

            China RoHS Regulation

            X

            Environmental Disclosure

            ENVPEP111252EN

            California proposition 65

            WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov

            Others

            Number of Units in Package 1

            1

            Number of Units in Package 2

            42

            Package 1 width

            8.3 cm

            Package 2 Height

            15 cm

            Package 2 Length

            40 cm

            Package 1 Height

            3.5 cm

            Package 1 Length

            9.2 cm

            Package 2 width

            30 cm

            Unit Type of Package 1

            PCE

            Unit Type of Package 2

            S02

            Device short name

            GVAU

            [Uc] control circuit voltage

            24 V AC 50 Hz

            Control circuit voltage limits

            0.85...1.1 Un

            [Ui] rated insulation voltage

          • 690 V AC conforming to IEC 60947-1
          • 600 V AC conforming to UL 60947-4-1
          • 600 V AC conforming to CSA C22.2 No 60947-4-1
            • Threshold tripping voltage

              0.7...0.35 Un

              Inrush power in VA

              12-12 VA AC

              Inrush power in W

              8 W

              Hold-in power consumption in VA

              3.5-3.5 VA AC

              Hold-in power consumption in W

              1.1-1.1 W

              Operating time

              10...15 ms conforming to IEC 60947-1

              On-load factor

              100 %

              Tightening torque

              < 1.4 N.m on screw clamp terminals

              Compatibility code

              GVAU

              Package 1 Weight

              115 g

              Package 2 Weight

              5.324 kg

              WEEE

              The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
              Show all specifications

              Documents & downloads

              hide show
              Filter items
              • All

              • CAD Files and Packs

              • Product Brochures

              • Technical Data Catalogues

              • Product Environmental

              • Installation Instruction

              • eTechPub

              Frequently Asked Questions

              hide show

              Can GVAU225 operate on 60 HZ?

              What is the catalog number for an external rotary handle for a GV7 manual starter ?

              Issue:
              GV7 Manual starter handle kit

              Product Line:
              Motor Starters and Protectors

              Environment:
              TeSys™ GV Manual Starters and Protectors

              Resolution:
              Use the GV7AP01 for a black handle with black legend or a GV7AP02 for a red handle with yellow legend.

              What is the equivalent of GV2AP01 and GV2AP02 rotary handle

              The equivalent of GV2AP01 and GV2AP02 rotary handles are GV2APN01          
               and GV2APN02 respectively.Refer attached file for more details

              Do we offer a cable operated handle mechanism for the GV7 starters?

              Issue:
              They need to mount the GV7 back inside the enclosure and need a handle mechanism with a cable to operate. 

              Product line:
              Manual Starters and Protectors

              Environment:
              Tesys GV7 manual motor controller

              Resolution:
              The GV7 do not offer a cable operator.  Consider switching to a Powerpact circuit breaker which offers the cable mechanism kits.

              What are the wire or cable sizes required for the GV7RE and GV7RS starters?

              Issue:
              For GV7RE and GV7RS starters, what is the wire size recommendation?

              Product Line:
              Manual starters and protectors

              Environment:
              Tesys GV2,GV3 and GV7

              Cause:
              Wiring and installation of starters

              Resolution:
              For the GV7R*20 thru R*150 use a mechanical lug kit / clip-on connectors for 1 #14-3/0 GV7AC021 (sold in lots of 3) . For the GV7R*220 use a kit for 1 #14-350mcm GV7AC022 (sold in lots of 3).

              Will the accessories used for the GV3ME06 through GV3ME63 work with the GV3ME80?

              Product Line:
              GV3 manual motor starters, IEC

              Resolution:
              The standard GV3 accessories will work on this device.
              Show More