Quantcast

Gv2 GV3 Undervolt Trip 115V Rhs Mt

Gv2 GV3 Undervolt Trip 115V Rhs Mt

Gv2 GV3 Undervolt Trip 115V Rhs Mt

Item Number: GVAS115

Product Dimensions

Width icon

Width18 mm

Height icon

Height89 mm

Depth icon

Depth66 mm

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Sustainable offer status

Green Premium product

Warranty

18 months

Range of product

  • TeSys GV2
  • TeSys GV3
  • TeSys Deca

Range

  • TeSys
  • TeSys Deca

Product or component type

shunt trip release

Physical

Range compatibility

  • GV2ME
  • GV2LE
  • GV2L
  • GV2P
  • GV3L
  • GV3P

Connections - terminals

  • screw clamp terminals 1 cable(s) 1-2.5 mm²solid
  • screw clamp terminals 2 cable(s) 1-2.5 mm²solid
  • screw clamp terminals 1 cable(s) 0.75-2.5 mm²flexible without cable end
  • screw clamp terminals 2 cable(s) 0.75-2.5 mm²flexible without cable end
  • screw clamp terminals 1 cable(s) 0.75-1.5 mm²flexible with cable end
  • screw clamp terminals 2 cable(s) 0.75-1.5 mm²flexible with cable end

Mechanical durability

  • 10000 cycles with GV3P and GV3L
  • 30000 cycles with GV2ME and GV2P

Quantity per set

set of 10

Height

89 mm

Width

18 mm

Depth

66 mm

Net weight

0.105 kg

REACh Regulation

Free of Substances of Very High Concern above the threshold

REACh free of SVHC

Yes

EU RoHS Directive

Compliant

Toxic heavy metal free

Yes

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

 Pro-active China RoHS declaration (out of China RoHS legal scope)

Environmental Disclosure

ENVPEP111252EN

Others

[Uc] control circuit voltage

  • 127 V AC 60 Hz
  • 110...115 V AC 50 Hz

Control circuit voltage limits

0.7...1.1 Un

[Ui] rated insulation voltage

  • 690 V AC conforming to IEC 60947-1
  • 600 V AC conforming to UL 60947-4-1
  • 600 V AC conforming to CSA C22.2 No 60947-4-1

Threshold tripping voltage

0.75...0.2 Un

Inrush power in VA

14 VA AC

Inrush power in W

10.5 W

Hold-in power consumption in VA

5 VA AC

Hold-in power consumption in W

1.6...1.6 W

Operating time

10...15 ms conforming to IEC 60947-1

On-load factor

100 %

Tightening torque

< 1.4="" n.m="" on="" screw="" clamp="">

Compatibility code

GVAS

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Weight

116.0 g

Package 1 Height

3.6 cm

Package 1 width

8.3 cm

Package 1 Length

9.1 cm

Unit Type of Package 2

S01

Number of Units in Package 2

16

Package 2 Weight

2.042 kg

Package 2 Height

15 cm

Package 2 width

15 cm

Package 2 Length

40 cm

WEEE

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

Device short name

GVAS
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • CAD Files and Packs

  • Product Brochures

  • Technical Data Catalogues

  • Installation Instruction

  • Product Environmental

  • Technical Drawing

  • eTechPub