Quantcast

Side Mount Auxiliary 2Nc

Side Mount Auxiliary 2Nc

Side Mount Auxiliary 2Nc

Item Number: GVAN20

Retail
$89.64
RRP (Inc. GST)

Product Dimensions

Width icon

Width9.3 mm

Height icon

Height89 mm

Depth icon

Depth66 mm

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

  • TeSys GV3
  • TeSys GV2
    • Range

      TeSys

      Product or component type

      auxiliary contact block

      Product compatibility

    • GV2ME
    • GV3P
    • GV2RT
    • GV2LE
    • GV2L
    • GV3L
    • GV2P
      • Sustainable offer status

        Green Premium product

        Warranty

        18 months

        Physical

        [Ue] rated operational voltage

      • 48...690 V AC
      • 24...240 V DC
        • Protection type

        • GB2CB... circuit breaker
        • gG fuse 10 A
          • Mechanical durability

            100000 cycles

            Height

            89 mm

            Width

            9.3 mm

            Depth

            66 mm

            Net weight

            0.05 kg

            Environmental characteristic

            normal environment

            REACh Regulation

            Free of Substances of Very High Concern above the threshold

            REACh free of SVHC

            Yes

            EU RoHS Directive

            Compliant

            Toxic heavy metal free

            Yes

            Mercury free

            Yes

            RoHS exemption information

            Yes

            China RoHS Regulation

            X

            Environmental Disclosure

            ENVPEP111252EN

            California proposition 65

            WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov

            Others

            Device short name

            GVAN

            Mounting location

            left side

            Pole contact composition

            2 NO

            [Ui] rated insulation voltage

          • 600 V conforming to UL 508
          • 690 V conforming to IEC 60947-1
          • 600 V conforming to CSA C22.2 No 14
            • [Ith] conventional free air thermal current

              6 A

              Minimum switching current

              5 mA

              Minimum switching voltage

              17 V

              Rated operational power in VA

            • 300 VA at 48-48 V AC-15 - electrical durability: 100000 cycles
            • 414 VA at 690-690 V AC-15 - electrical durability: 100000 cycles
            • 500 VA at 110-127 V AC-15 - electrical durability: 100000 cycles
            • 500 VA at 500-500 V AC-15 - electrical durability: 100000 cycles
            • 650 VA at 440-440 V AC-15 - electrical durability: 100000 cycles
            • 720 VA at 230-240 V AC-15 - electrical durability: 100000 cycles
            • 850 VA at 380-415 V AC-15 - electrical durability: 100000 cycles
              • Rated operational power in W

              • 120 W at 240 V DC-13 - electrical durability: 100000 cycles
              • 140 W at 110 V DC-13 - electrical durability: 100000 cycles
              • 140 W at 24 V DC-13 - electrical durability: 100000 cycles
              • 180 W at 60 V DC-13 - electrical durability: 100000 cycles
              • 240 W at 48 V DC-13 - electrical durability: 100000 cycles
                • Tightening torque

                  1.4 N.m - on screw clamp terminals

                  Compatibility code

                  GVAN

                  Unit Type of Package 1

                  PCE

                  Number of Units in Package 1

                  1

                  Package 1 Weight

                  44 g

                  Package 1 Height

                  1.9 cm

                  Package 1 width

                  12.8 cm

                  Package 1 Length

                  14 cm

                  Unit Type of Package 2

                  BAG

                  Number of Units in Package 2

                  1

                  Package 2 Weight

                  44 g

                  Package 2 Height

                  1.9 cm

                  Package 2 width

                  12.8 cm

                  Package 2 Length

                  14 cm

                  Unit Type of Package 3

                  BB1

                  Number of Units in Package 3

                  10

                  Package 3 Weight

                  504 g

                  Package 3 Height

                  9.5 cm

                  Package 3 width

                  10 cm

                  Package 3 Length

                  15.5 cm

                  WEEE

                  The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                  Show all specifications

                  Documents & downloads

                  hide show
                  Filter items
                  • All

                  • CAD Files and Packs

                  • Product Brochures

                  • Technical Data Catalogues

                  • Product Environmental

                  • Installation Instruction

                  • Technical Drawing

                  • Certificates (MSDS)

                  • eTechPub

                  Frequently Asked Questions

                  hide show

                  What is the IP rating of GVAE20? Would the IP rating of GV2P circuit breaker (IP20) get affected by the addition of Aux contact GVAE20?

                  The IP rating of GVAE20 is IP 20.

                  The IP rating of GV2* with GVAE20 is then IP20. It would not get affected by the addition of the Auxiliary 

                  Can GVAE1, GVAE11 or GVAE20 be used with GV3 starters?

                  Issue:
                  Are the front mount auxiliary contacts GVAE1, GVEA11 and GVAE20 be used for GV3M devices?
                   
                  Product Line:

                  Tesys GV Manual Starter and Protectors

                  Environment:
                  TeSys GV, GVA, GV2, GV3P

                  Resolution:
                  These auxiliary contacts can only be used with the rotary handled GV3P devices. They cannot be applied with the pushbutton GV3M devices.

                  How many of GVAN11 side Auxiliary can be put on GV3 circuit breakers?

                  Maximum of 2 sides mounted Auxiliary can be used with GV3 circuit breaker.
                   

                  Can the GV* starters be used on 50 hertz applications?

                  Issue:
                  GV* Starter for 50/60hz application

                  Product Line:
                  Motor Starters and Protectors

                  Environment:
                  PowerPact™ Manual Starters

                  Resolution:
                  Yes, these starters are rated for 50/60 hertz.

                  This applies to all GV2M, GV2ME, GV2P, GV3M, GV3ME devices.