Instantaneous auxiliary contact block for GV2

Side Mount Auxiliary 2Nc

Catalogue Number: GVAN20
Instantaneous auxiliary contact block for GV2
Retail
$89.64
RRP (Inc. GST)

Specifications

hide show
Range of product
  • TeSys GV3
  • TeSys GV2
    • Range
      TeSys
      Device short name
      GVAN
      Product or component type
      auxiliary contact block
      Product compatibility
    • GV2ME
    • GV3P
    • GV2RT
    • GV2LE
    • GV2L
    • GV3L
    • GV2P
      • Mounting location
        left side
        Pole contact composition
        2 NO
        Connections - terminals
      • screw clamp terminals 1 cable(s) 1-2.5 mm²solid
      • screw clamp terminals 2 cable(s) 1-2.5 mm²solid
      • screw clamp terminals 1 cable(s) 0.75-2.5 mm²flexible without cable end
      • screw clamp terminals 2 cable(s) 0.75-2.5 mm²flexible without cable end
      • screw clamp terminals 2 cable(s) 0.75-1.5 mm²flexible with cable end
      • screw clamp terminals 1 cable(s) 0.75-1.5 mm²flexible with cable end
        • [Ui] rated insulation voltage
        • 600 V conforming to UL 508
        • 690 V conforming to IEC 60947-1
        • 600 V conforming to CSA C22.2 No 14
          • [Ue] rated operational voltage
          • 48...690 V AC
          • 24...240 V DC
            • [Ith] conventional free air thermal current
              6 A
              Protection type
            • GB2CB... circuit breaker
            • gG fuse 10 A
              • Mechanical durability
                100000 cycles
                Minimum switching current
                5 mA
                Minimum switching voltage
                17 V
                Rated operational power in VA
              • 300 VA at 48-48 V AC-15 - electrical durability: 100000 cycles
              • 414 VA at 690-690 V AC-15 - electrical durability: 100000 cycles
              • 500 VA at 110-127 V AC-15 - electrical durability: 100000 cycles
              • 500 VA at 500-500 V AC-15 - electrical durability: 100000 cycles
              • 650 VA at 440-440 V AC-15 - electrical durability: 100000 cycles
              • 720 VA at 230-240 V AC-15 - electrical durability: 100000 cycles
              • 850 VA at 380-415 V AC-15 - electrical durability: 100000 cycles
                • Rated operational power in W
                • 120 W at 240 V DC-13 - electrical durability: 100000 cycles
                • 140 W at 110 V DC-13 - electrical durability: 100000 cycles
                • 140 W at 24 V DC-13 - electrical durability: 100000 cycles
                • 180 W at 60 V DC-13 - electrical durability: 100000 cycles
                • 240 W at 48 V DC-13 - electrical durability: 100000 cycles
                  • Tightening torque
                    1.4 N.m - on screw clamp terminals
                    Height
                    89 mm
                    Width
                    9.3 mm
                    Depth
                    66 mm
                    Net weight
                    0.05 kg
                    Compatibility code
                    GVAN
                    Environmental characteristic
                    normal environment
                    Unit Type of Package 1
                    PCE
                    Number of Units in Package 1
                    1
                    Package 1 Weight
                    44 g
                    Package 1 Height
                    1.9 cm
                    Package 1 width
                    12.8 cm
                    Package 1 Length
                    14 cm
                    Unit Type of Package 2
                    BAG
                    Number of Units in Package 2
                    1
                    Package 2 Weight
                    44 g
                    Package 2 Height
                    1.9 cm
                    Package 2 width
                    12.8 cm
                    Package 2 Length
                    14 cm
                    Unit Type of Package 3
                    BB1
                    Number of Units in Package 3
                    10
                    Package 3 Weight
                    504 g
                    Package 3 Height
                    9.5 cm
                    Package 3 width
                    10 cm
                    Package 3 Length
                    15.5 cm
                    Sustainable offer status
                    Green Premium product
                    REACh free of SVHC
                    Yes
                    EU RoHS Directive
                    Compliant
                    Toxic heavy metal free
                    Yes
                    Mercury free
                    Yes
                    RoHS exemption information
                    Yes
                    China RoHS Regulation
                    X
                    Environmental Disclosure
                    ENVPEP111252EN
                    WEEE
                    The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                    California proposition 65
                    WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov
                    Warranty
                    18 months

                    Documents & downloads

                    hide show
                    Filter items
                    • All

                    • CAD Files and Packs

                    • Product Brochures

                    • Technical Data Catalogues

                    • Product Environmental

                    • Installation Instruction

                    • Certificates (MSDS)

                    • eTechPub

                    Frequently Asked Questions

                    hide show

                    What is the IP rating of GVAE20? Would the IP rating of GV2P circuit breaker (IP20) get affected by the addition of Aux contact GVAE20?

                    The IP rating of GVAE20 is IP 20.

                    The IP rating of GV2* with GVAE20 is then IP20. It would not get affected by the addition of the Auxiliary 

                    Can GVAE1, GVAE11 or GVAE20 be used with GV3 starters?

                    Issue:
                    Are the front mount auxiliary contacts GVAE1, GVEA11 and GVAE20 be used for GV3M devices?
                     
                    Product Line:

                    Tesys GV Manual Starter and Protectors

                    Environment:
                    TeSys GV, GVA, GV2, GV3P

                    Resolution:
                    These auxiliary contacts can only be used with the rotary handled GV3P devices. They cannot be applied with the pushbutton GV3M devices.

                    Can the GV* starters be used on 50 hertz applications?

                    Issue:
                    GV* Starter for 50/60hz application

                    Product Line:
                    Motor Starters and Protectors

                    Environment:
                    PowerPact™ Manual Starters

                    Resolution:
                    Yes, these starters are rated for 50/60 hertz.

                    This applies to all GV2M, GV2ME, GV2P, GV3M, GV3ME devices.

                    How many of GVAN11 side Auxiliary can be put on GV3 circuit breakers?

                    Maximum of 2 sides mounted Auxiliary can be used with GV3 circuit breaker.
                     

                    What is the part name for the side mount auxiliary contacts 1 N/C , 1N/O for GV3P40?

                    The part name for the side mount auxiliary contacts is - GVAN11.

                    Can a GV2AF3 or GV2AF4 interconnection block work on a contactor with a DC coil?

                    Issue:
                    Mounting adaptor for GV2 and LC1D contactor

                    Product Line:
                    Motor Starters and Protectors

                    Environment:
                    TeSys GV Manual Starter and Protectors
                    Tesys D Contactors
                     
                    Resolution:
                    The GV2AF3 clip has to be moved to the DC position to accommodate the contactor with a DC coil.

                    Are explosion proof enclosures available for GV manual motor starters.

                    Issue:
                    NEMA 7/9 rated enclosure for GV manual motor starters

                    Product Line:
                    Tesys GV Motor Starters and Protectors

                    Environment:
                    TeSys™ GV Manual Starters and Protectors

                    Resolution:
                    No hazardous duty enclosures are available for the GV product line.
                    For explosion proof applications consider the Class 2510 Type M or Type T offering.

                    Will GVAN11 give fault indication?

                    No, the GVAN11 will only give status of "off" or "on" of the Breaker, but no indication of "fault".

                    The GVAD1010 and GVAD0110 will give fault indication and status of "off" or "on" of the breaker.

                    The GVAM11 will give short circuit contact signaling .

                    For further information please visit https://www.schneider-electric.com.au.

                    Will the accessories used for the GV3ME06 through GV3ME63 work with the GV3ME80?

                    Product Line:
                    GV3 manual motor starters, IEC

                    Resolution:
                    The standard GV3 accessories will work on this device.

                    What type of battery could I use with the Galaxy VS UPS?

                    Issue:
                    What kind of external batteries does the Galaxy VS 3-Phase UPS support?

                    Product line:
                    Galaxy VS

                    Environment:
                    All models, all serial numbers

                    Cause:
                    External Battery Options
                     
                    Resolution:
                    Available with both classic VRLA battery solutions (lead-acid) as well as long-life lithium-ion (Li-ION) battery*.
                     
                    Benefits of Li-ion batteries:
                    • Compact and reliable energy storage
                    • Restore backup time quickly
                    • Protect your load even during repeated power interruptions
                    • Longer lifetime than classic battery solutions- matches service life of Galaxy VS UPS
                    • Higher predictability and manageability thanks to the built-in battery monitoring system
                    (*) contact your local sales representative for availability

                     
                     

                    Is a padlocking device available for the GV2MC** type enclosures?

                    Issue:
                    Padlocking device for GV2MC Enclosures

                    Product Line:
                    TeSys GV2 Manual Starters and Protectors

                    Environment:
                    n/a

                    Resolution:
                    Yes, use the GV2V01. When this is padlocked, the starter is automatically in and will remain in the OFF position.

                    GV2P disconnect options

                    Issue:
                    What is the product number for a complete through-the-door disconnect device for a GV2P

                    Product Line:
                    GV2P Manual Starters and Protectors

                    Environment:
                    US product

                    Cause:
                    Digest 176 is unclear as to what is a complete mechanism with shaft and handle

                    Resolution:
                    There are three devices which include mechanism, shaft and handle:
                    GV2APN01 has a NEMA 1, 12 rating and is black
                    GV2APN02 has a NEMA 1, 12 rating and is red/yellow
                    GV2APN04 has a NEMA 3R, 4, 4X rating and is red/yellow

                    Show More