Quantcast

Side Mount Auxiliary No/Nc

Side Mount Auxiliary No/Nc

Side Mount Auxiliary No/Nc

Item Number: GVAN11

Retail
$89.64
RRP (Inc. GST)

Product Dimensions

Width icon

Width9.3 mm

Height icon

Height89 mm

Depth icon

Depth66 mm

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Sustainable offer status

Green Premium product

Warranty

18 months

Range of product

  • TeSys GV2
  • TeSys GV3
    • Range

      TeSys

      Product or component type

      auxiliary contact block

      Product compatibility

    • GV2ME
    • GV2RT
    • GV2L
    • GV3P
    • GV3L
    • GV2LE
    • GV2P
      • Physical

        California proposition 65

        WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov

        Environmental Disclosure

        ENVPEP111252EN

        Mercury free

        Yes

        REACh free of SVHC

        Yes

        REACh Regulation

        Free of Substances of Very High Concern above the threshold

        China RoHS Regulation

        X

        EU RoHS Directive

        Compliant

        RoHS exemption information

        Yes

        Toxic heavy metal free

        Yes

        Connections - terminals

      • screw clamp terminals 1 cable(s) 1-2.5 mm²solid
      • screw clamp terminals 2 cable(s) 1-2.5 mm²solid
      • screw clamp terminals 1 cable(s) 0.75-2.5 mm²flexible without cable end
      • screw clamp terminals 2 cable(s) 0.75-2.5 mm²flexible without cable end
      • screw clamp terminals 2 cable(s) 0.75-1.5 mm²flexible with cable end
      • screw clamp terminals 1 cable(s) 0.75-1.5 mm²flexible with cable end
        • [Ue] rated operational voltage

        • 48...690 V AC
        • 24...240 V DC
          • Protection type

          • GB2CB... circuit breaker
          • gG fuse 10 A
            • Mechanical durability

              100000 cycles

              Height

              89 mm

              Width

              9.3 mm

              Depth

              66 mm

              Net weight

              0.05 kg

              Environmental characteristic

              normal environment

              Others

              Number of Units in Package 1

              1

              Number of Units in Package 2

              10

              Number of Units in Package 3

              60

              Package 1 Height

              1.5 cm

              Package 1 Length

              9 cm

              Package 1 Weight

              46 g

              Package 1 width

              7 cm

              Package 2 Height

              9.5 cm

              Package 2 Length

              15.2 cm

              Package 2 Weight

              510 g

              Package 2 width

              10 cm

              Package 3 Height

              15 cm

              Package 3 Length

              40 cm

              Package 3 Weight

              3.36 kg

              Package 3 width

              30 cm

              Unit Type of Package 1

              PCE

              Unit Type of Package 2

              BB1

              Unit Type of Package 3

              S02

              WEEE

              The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

              Device short name

              GVAN

              Mounting location

              left side

              Pole contact composition

              1 NO + 1 NC

              [Ui] rated insulation voltage

            • 600 V conforming to UL 508
            • 690 V conforming to IEC 60947-1
            • 600 V conforming to CSA C22.2 No 14
              • [Ith] conventional free air thermal current

                6 A

                Minimum switching current

                5 mA

                Minimum switching voltage

                17 V

                Rated operational power in VA

              • 300 VA at 48-48 V AC-15 - electrical durability: 100000 cycles
              • 414 VA at 690-690 V AC-15 - electrical durability: 100000 cycles
              • 500 VA at 110-127 V AC-15 - electrical durability: 100000 cycles
              • 500 VA at 500-500 V AC-15 - electrical durability: 100000 cycles
              • 650 VA at 440-440 V AC-15 - electrical durability: 100000 cycles
              • 720 VA at 230-240 V AC-15 - electrical durability: 100000 cycles
              • 850 VA at 380-415 V AC-15 - electrical durability: 100000 cycles
                • Rated operational power in W

                • 120 W at 240 V DC-13 - electrical durability: 100000 cycles
                • 140 W at 110 V DC-13 - electrical durability: 100000 cycles
                • 140 W at 24 V DC-13 - electrical durability: 100000 cycles
                • 180 W at 60 V DC-13 - electrical durability: 100000 cycles
                • 240 W at 48 V DC-13 - electrical durability: 100000 cycles
                  • Tightening torque

                    1.4 N.m - on screw clamp terminals

                    Compatibility code

                    GVAN
                    Show all specifications

                    Documents & downloads

                    hide show
                    Filter items
                    • All

                    • CAD Files and Packs

                    • Product Brochures

                    • Technical Data Catalogues

                    • Product Environmental

                    • Installation Instruction

                    • Certificates (MSDS)

                    • eTechPub

                    Frequently Asked Questions

                    hide show

                    How many of GVAN11 side Auxiliary can be put on GV3 circuit breakers?

                    Maximum of 2 sides mounted Auxiliary can be used with GV3 circuit breaker.
                     

                    What is the part name for the side mount auxiliary contacts 1 N/C , 1N/O for GV3P40?

                    The part name for the side mount auxiliary contacts is - GVAN11.

                    Can GVAE1, GVAE11 or GVAE20 be used with GV3 starters?

                    Issue:
                    Are the front mount auxiliary contacts GVAE1, GVEA11 and GVAE20 be used for GV3M devices?
                     
                    Product Line:

                    Tesys GV Manual Starter and Protectors

                    Environment:
                    TeSys GV, GVA, GV2, GV3P

                    Resolution:
                    These auxiliary contacts can only be used with the rotary handled GV3P devices. They cannot be applied with the pushbutton GV3M devices.

                    Will GVAN11 give fault indication?

                    No, the GVAN11 will only give status of "off" or "on" of the Breaker, but no indication of "fault".

                    The GVAD1010 and GVAD0110 will give fault indication and status of "off" or "on" of the breaker.

                    The GVAM11 will give short circuit contact signaling .

                    For further information please visit https://www.schneider-electric.com.au.

                    What is the part number to get 2 extra N/C auxillary contacts on to a GV Motor C/B?

                    The part numbers to get 2 extra N/C auxillary contacts on to a GV Motor C/B are - GVAE11 & GVAN11
                    For further information , visit links below:-
                    https://www.schneider-electric.com.au/en/search/GVAE11
                    https://www.schneider-electric.com.au/en/search/GVAN11
                     

                    What is the power consumption of the GVAE1?

                    no power consumption....but contacts are rated to 2.5 amps.....see data sheet
                    https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=gvae1
                    User-added image
                    Show More