MASTER YOUR CASTLE with your new build or reno project
Enter competition
GV4PEM02N

GV4PEM03S

Motor Breaker GV4PE Mul 3.5A 100kA Everlink Terminal

GV4PEM02N
Colour:
Colour: Per UOM Std.
  • 1 PCE
Added to cart
Successfully added, you can view your cart here

Key Features & Specifications

hide show
  • Everlink power connections with patented creep-compensation technology
  • One size up to 55KW at 415 VAC
  • Wide overload setting for easy selection and reducing the stock
  • 3 level short circuit breaking capacity (25KA, 50KA and 100KA)
  • Robust Rotary handle (Direct, side and extended)
  • Green Premium ecoLabel
Range
TeSys
Product name
TeSys GV4
Device short name
GV4PEM
Product or component type
multifunction circuit breaker
Device application
motor
Protection type
  • jam
  • long start
  • locked rotor
  • short-circuit
  • short time short-circuit protection
  • overload
  • phase unbalance
  • phase loss
  • ground fault protection
    • Utilisation category
      category A
      Suitability for isolation
      yes conforming to IEC 60947-1
      Poles description
      3P
      [Ue] rated operational voltage
      690 V AC 50/60 Hz conforming to IEC 60947-2
      [In] rated current
      3.5 A
      Trip unit technology
    • electronic
    • thermal-magnetic
      • Thermal protection adjustment range
        1.4-3.5 A
        Motor tripping class
      • 10
      • 20
        • Breaking capacity
        • Icu 120 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
        • Icu 100 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
        • Icu 70 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
        • Icu 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
        • Icu 18 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
        • 100 kA at 208Y/120 V AC 50/60 Hz conforming to UL 60947
        • 100 kA at 240 V AC 50/60 Hz conforming to UL 60947
        • 65 kA at 480Y/277 V AC 50/60 Hz conforming to UL 60947
        • Icu 10 kA at 660...690 V AC 50/60 Hz conforming to IEC 60947-2
        • 25 kA at 600Y/347 V AC 50/60 Hz conforming to UL 60947
          • [Ics] rated service breaking capacity
          • 120 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
          • 100 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
          • 70 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
          • 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
          • 18 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
          • 2.5 kA at 660...690 V AC 50/60 Hz conforming to IEC 60947-2
            • [Uimp] rated impulse withstand voltage
              8 kV conforming to IEC 60947-2
              [Ui] rated insulation voltage
              800 V conforming to IEC 60947-2
              Mechanical durability
              40000 cycles
              Electrical durability
            • 40000 cycles for AC-3 at 440 V In/2
            • 40000 cycles for AC-3 at 440 V In
              • Motor power kW
              • 0.55-0.55 kW at 400...415 V AC 50/60 Hz
              • 0.75-0.75 kW at 400...415 V AC 50/60 Hz
              • 0.75-0.75 kW at 500 V AC 50/60 Hz
              • 1.1-1.1 kW at 500 V AC 50/60 Hz
              • 1.1-1.1 kW at 660...690 V AC 50/60 Hz
              • 1.5-1.5 kW at 660...690 V AC 50/60 Hz
              • 1.5-1.5 kW at 500 V AC 50/60 Hz
              • 2.2-2.2 kW at 660...690 V AC 50/60 Hz
              • 1.1-1.1 kW at 400...415 V AC 50/60 Hz
              • 1.5-1.5 kW at 400...415 V AC 50/60 Hz
                • Control type
                  toggle
                  Number of slots
                • 1 slot(s) for alarm switch for fault signalling contact, plug-in
                • 1 slot(s) for voltage release for electrical remote tripping, plug-in
                • 1 slot(s) for auxiliary switch for open/close contact, plug-in
                  • Local signalling
                    presence of auxiliary contacts: flag (green)
                    Communication port protocol
                    NFC
                    Standards
                  • EN/IEC 60947-2
                  • EN/IEC 60947-4-1
                  • UL 60947-4-1
                  • CSA C22.2 No 60947-4-1
                    • Quality labels
                      CE
                      Mounting mode
                    • by clips
                    • by screws
                      • Mounting support
                      • plate
                      • 75 mm symmetrical DIN rail
                      • 35 mm symmetrical DIN rail
                        • Connections - terminals
                        • top 1 EverLink BTR screw connectors wire size 1.5-70 mm², solid
                        • top 1 EverLink BTR screw connectors wire size 1.5-50 mm², flexible
                        • bottom 1 EverLink BTR screw connectors wire size 2.5-95 mm², solid
                        • bottom 1 EverLink BTR screw connectors wire size 2.5-70 mm², flexible
                          • Connection pitch
                            27 mm
                            Wire stripping length
                            20 mm
                            Tightening torque
                          • 9-9 N.m for 16-95 mm²
                          • 5-5 N.m for 1.5-10 mm²
                            • Width
                              81 mm
                              Height
                              155 mm
                              Depth
                              116 mm
                              Net weight
                              1.45 kg
                              Product certifications
                              IEC
                              Ambient air temperature for storage
                              -50-85 °C
                              Ambient air temperature for operation
                              -25-70 °C
                              Operating altitude
                            • 0...2000 m without derating
                            • 2000...5000 m with derating
                              • IP degree of protection
                                IP40 front face conforming to IEC 60529
                                IK degree of protection
                                IK07 conforming to IEC 62262
                                Pollution degree
                                3 conforming to IEC 60947-1
                                Tropicalisation
                                2 conforming to IEC 68-2
                                Mechanical robustness
                              • vibrations: +/- 1 mm 2...13.2 Hz conforming to IEC 60068-2-6
                              • vibrations: 0.7 gn 13.2...100 Hz conforming to IEC 60068-2-6
                              • shocks: 15 gn 11 ms conforming to IEC 60068-2-27
                                • Sustainable offer status
                                  Green Premium product
                                  REACh Regulation
                                  Reference contains Substances of Very High Concern above the threshold
                                  EU RoHS Directive
                                  Pro-active compliance (Product out of EU RoHS legal scope)
                                  Mercury free
                                  Yes
                                  RoHS exemption information
                                  Yes
                                  China RoHS Regulation
                                  Product out of China RoHS scope. Substance declaration for your information
                                  Environmental Disclosure
                                  ENVPEP1704004EN
                                  Circularity Profile
                                  ENVEOLI1704004EN
                                  WEEE
                                  The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                                  Warranty
                                  18 months