TeSys GV4P - thermal magnetic motor breaker 2A to 115A - lug connection - toggle

Motor Breaker GV4PE Thermal/Magnetic 25A 25kA Lug Terminal

Catalogue Number: GV4PE25B6
TeSys GV4P - thermal magnetic motor breaker 2A to 115A - lug connection - toggle
Retail
$1710.45*
RRP (Inc. GST)

Specifications

hide show
Range
TeSys
Product name
TeSys GV4
Device short name
GV4PE
Product or component type
circuit breaker
Device application
motor protection
Protection type
  • overload
  • phase unbalance
  • ground fault protection
  • short-circuit
  • phase loss
  • short time short-circuit protection
    • Utilisation category
      category A
      Suitability for isolation
      yes conforming to IEC 60947-1
      Poles description
      3P
      [Ue] rated operational voltage
      690 V AC 50/60 Hz conforming to IEC 60947-2
      [In] rated current
      25 A
      Trip unit technology
    • thermal-magnetic
    • electronic
      • Magnetic tripping current
        425-425 A
        [Isd] short-time pick-up adjustment range
        13 x Ir
        Thermal protection adjustment range
        10-25 A
        Motor tripping class
      • 10
      • 20
        • Phase failure sensitivity
          yes conforming to IEC 60947-4-1
          Breaking capacity
        • Icu 50 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
        • Icu 25 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
        • Icu 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
        • Icu 10 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
        • 35 kA at 208Y/120 V AC 50/60 Hz conforming to UL 60947
        • 35 kA at 240 V AC 50/60 Hz conforming to UL 60947
        • 18 kA at 480Y/277 V AC 50/60 Hz conforming to UL 60947
        • 14 kA at 600Y/347 V AC 50/60 Hz conforming to UL 60947
          • [Ics] rated service breaking capacity
          • 50 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
          • 25 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
          • 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
          • 10 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
            • [Uimp] rated impulse withstand voltage
              [Ui] rated insulation voltage
              800 V conforming to IEC 60947-2
              Mechanical durability
              40000 cycles
              Electrical durability
            • 40000 cycles for AC-3 at 440 V In/2
            • 20000 cycles for AC-3 at 440 V In
              • Motor power kW
              • 7.5-7.5 kW at 660...690 V AC 50/60 Hz
              • 5.5-5.5 kW at 400...415 V AC 50/60 Hz
              • 7.5-7.5 kW at 500 V AC 50/60 Hz
              • 9-9 kW at 660...690 V AC 50/60 Hz
              • 11-11 kW at 660...690 V AC 50/60 Hz
              • 7.5-7.5 kW at 400...415 V AC 50/60 Hz
              • 9-9 kW at 400...415 V AC 50/60 Hz
              • 11-11 kW at 400...415 V AC 50/60 Hz
              • 9-9 kW at 500 V AC 50/60 Hz
              • 11-11 kW at 500 V AC 50/60 Hz
              • 15-15 kW at 500 V AC 50/60 Hz
              • 15-15 kW at 660...690 V AC 50/60 Hz
              • 18.5-18.5 kW at 660...690 V AC 50/60 Hz
                • Control type
                  toggle
                  Rotary handle padlocking
                  with a lock accessory
                  Number of slots
                • 1 slot(s) for alarm switch for fault signalling contact, plug-in
                • 1 slot(s) for voltage release for electrical remote tripping, plug-in
                • 1 slot(s) for auxiliary switch for open/close contact, plug-in
                  • Local signalling
                  • flashing LED (green)ready:
                  • LED (red)alarm (T° >95%):
                  • green indicatorpresence of auxiliary contacts:
                    • Standards
                    • EN/IEC 60947-4-1
                    • UL 60947-4-1
                    • CSA C22.2 No 60947-4-1
                    • EN/IEC 60947-2
                      • Product certifications
                      • IEC
                      • UL
                      • CSA
                      • CCC
                      • EAC
                      • ATEX
                      • EU-RO MR
                        • Quality labels
                          CE
                          Mounting mode
                        • by clips
                        • by screws
                          • Mounting support
                          • 35 mm symmetrical DIN rail
                          • plate
                          • 75 mm symmetrical DIN rail
                            • Connections - terminals
                              lugs-ring terminals
                              Connection pitch
                              27 mm
                              Tightening torque
                            • 9-9 N.m for 16-95 mm²
                            • 5-5 N.m for 1.5-10 mm²
                              • Width
                                81 mm
                                Height
                                155 mm
                                Depth
                                116 mm
                                Net weight
                                1.45 kg
                                Ambient air temperature for storage
                                -50-85 °C
                                Ambient air temperature for operation
                                -25-70 °C
                                Operating altitude
                              • 0...2000 m without derating
                              • 2000...5000 m with derating
                                • IP degree of protection
                                  IP40 front face conforming to IEC 60529
                                  IK degree of protection
                                  IK07 conforming to IEC 62262
                                  Pollution degree
                                  3 conforming to IEC 60947-1
                                  Tropicalisation
                                  2 conforming to IEC 68-2
                                  Mechanical robustness
                                • vibrations: +/- 1 mm 2...13.2 Hz conforming to IEC 60068-2-6
                                • vibrations: 0.7 gn 13.2...100 Hz conforming to IEC 60068-2-6
                                • shocks: 15 gn 11 ms conforming to IEC 60068-2-27
                                  • Sustainable offer status
                                    Green Premium product
                                    EU RoHS Directive
                                    Compliant
                                    Mercury free
                                    Yes
                                    RoHS exemption information
                                    Yes
                                    China RoHS Regulation
                                    Product out of China RoHS scope. Substance declaration for your information
                                    Environmental Disclosure
                                    ENVPEP1704004EN
                                    Circularity Profile
                                    ENVEOLI1704004EN
                                    WEEE
                                    The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                                    Warranty
                                    18 months

                                    Frequently Asked Questions

                                    hide show

                                    What is the part number for the spacer used with the LC*D09 through LC*D32 Contactor and the GV2AF3 combination block when the GV2 Motor Circuit Protector is mounted on din rail and the contactor hangs below it?

                                    Issue:
                                    Identifying the spacer part number for use with a LC*D, GV2AF3, and GV2 device combination

                                    Product Line:
                                    Contactors and Starters IEC

                                    Environment:
                                    Tesys D contactors and GV manual starters

                                    Cause:
                                    Spacer required

                                    Resolution:
                                    Compensation plate catalog number GV1F03, requires 2 pieces snap together.

                                    How many auxiliary contact modules can be installed on the GV3ME__ manual starter?

                                    Issue:
                                    GV2 and GV3 number of aux switches?

                                    Product Line:
                                    Manual Starters

                                    Environment: 
                                    GV2 GV3 manual motor starters, IEC

                                    Resolution:
                                    One right side mount instantaneous auxiliary module and one internal mount fault signaling auxiliary module.

                                    Can the GV* starters be used on 50 hertz applications?

                                    Issue:
                                    GV* Starter for 50/60hz application

                                    Product Line:
                                    Motor Starters and Protectors

                                    Environment:
                                    PowerPact™ Manual Starters

                                    Resolution:
                                    Yes, these starters are rated for 50/60 hertz.

                                    This applies to all GV2M, GV2ME, GV2P, GV3M, GV3ME devices.

                                    Are explosion proof enclosures available for GV manual motor starters.

                                    Issue:
                                    NEMA 7/9 rated enclosure for GV manual motor starters

                                    Product Line:
                                    Tesys GV Motor Starters and Protectors

                                    Environment:
                                    TeSys™ GV Manual Starters and Protectors

                                    Resolution:
                                    No hazardous duty enclosures are available for the GV product line.
                                    For explosion proof applications consider the Class 2510 Type M or Type T offering.