TeSys GV4P - thermal magnetic motor breaker 2A to 115A - lug connection - rotary handle

Motor Breaker GV4P Thermal/Magnetic 115A 25kA Lug Terminal

Catalogue Number: GV4P115B6
TeSys GV4P - thermal magnetic motor breaker 2A to 115A - lug connection - rotary handle
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Range
TeSys
Product name
TeSys GV4
Device short name
GV4P
Product or component type
circuit breaker
Device application
motor protection
Protection type
  • short-circuit
  • phase loss
  • overload
  • phase unbalance
  • ground fault protection
  • short time short-circuit protection
    • Utilisation category
      category A
      Suitability for isolation
      yes conforming to IEC 60947-1
      Poles description
      3P
      [Ue] rated operational voltage
      690 V AC 50/60 Hz conforming to IEC 60947-2
      [In] rated current
      115 A
      Trip unit technology
    • electronic
    • thermal-magnetic
      • Magnetic tripping current
        1955-1955 A
        [Isd] short-time pick-up adjustment range
        13 x Ir
        Thermal protection adjustment range
        65-115 A
        Motor tripping class
      • 10
      • 20
        • Phase failure sensitivity
          yes conforming to IEC 60947-4-1
          Breaking capacity
        • Icu 50 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
        • Icu 25 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
        • Icu 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
        • Icu 10 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
        • 35 kA at 208Y/120 V AC 50/60 Hz conforming to UL 60947
        • 35 kA at 240 V AC 50/60 Hz conforming to UL 60947
        • 18 kA at 480Y/277 V AC 50/60 Hz conforming to UL 60947
        • 14 kA at 600Y/347 V AC 50/60 Hz conforming to UL 60947
          • [Ics] rated service breaking capacity
          • 50 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
          • 25 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
          • 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
          • 10 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
            • [Uimp] rated impulse withstand voltage
              [Ui] rated insulation voltage
              800 V conforming to IEC 60947-2
              Mechanical durability
              40000 cycles
              Electrical durability
            • 10000 cycles for AC-3 at 440 V In/2
            • 5000 cycles for AC-3 at 440 V In
              • Motor power kW
              • 37-37 kW at 400...415 V AC 50/60 Hz
              • 45-45 kW at 400...415 V AC 50/60 Hz
              • 55-55 kW at 400...415 V AC 50/60 Hz
              • 45-45 kW at 500 V AC 50/60 Hz
              • 55-55 kW at 500 V AC 50/60 Hz
              • 75-75 kW at 500 V AC 50/60 Hz
              • 75-75 kW at 660...690 V AC 50/60 Hz
              • 90-90 kW at 660...690 V AC 50/60 Hz
              • 110-110 kW at 660...690 V AC 50/60 Hz
                • Control type
                  rotary handle
                  Rotary handle padlocking
                  padlock in OFF or ON position
                  Number of slots
                • 1 slot(s) for alarm switch for fault signalling contact, plug-in
                • 1 slot(s) for voltage release for electrical remote tripping, plug-in
                • 1 slot(s) for auxiliary switch for open/close contact, plug-in
                  • Local signalling
                  • flashing LED (green)ready:
                  • LED (red)alarm (T° >95%):
                  • green indicatorpresence of auxiliary contacts:
                    • Standards
                    • EN/IEC 60947-4-1
                    • EN/IEC 60947-2
                    • UL 60947-4-1
                    • CSA C22.2 No 60947-4-1
                      • Product certifications
                      • IEC
                      • UL
                      • CSA
                      • CCC
                      • EAC
                      • ATEX
                      • EU-RO MR
                        • Quality labels
                          CE
                          Mounting mode
                        • by screws
                        • by clips
                          • Mounting support
                          • plate
                          • 35 mm symmetrical DIN rail
                          • 75 mm symmetrical DIN rail
                            • Connections - terminals
                              lugs-ring terminals
                              Connection pitch
                              27 mm
                              Tightening torque
                            • 9-9 N.m for 16-95 mm²
                            • 5-5 N.m for 1.5-10 mm²
                              • Width
                                81 mm
                                Height
                                155 mm
                                Depth
                                165 mm
                                Net weight
                                1.6 kg
                                Ambient air temperature for storage
                                -50-85 °C
                                Ambient air temperature for operation
                                -25-70 °C
                                Operating altitude
                              • 0...2000 m without derating
                              • 2000...5000 m with derating
                                • IP degree of protection
                                  IP40 front face conforming to IEC 60529
                                  IK degree of protection
                                  IK07 conforming to IEC 62262
                                  Pollution degree
                                  3 conforming to IEC 60947-1
                                  Tropicalisation
                                  2 conforming to IEC 68-2
                                  Mechanical robustness
                                • vibrations: +/- 1 mm 2...13.2 Hz conforming to IEC 60068-2-6
                                • vibrations: 0.7 gn 13.2...100 Hz conforming to IEC 60068-2-6
                                • shocks: 15 gn 11 ms conforming to IEC 60068-2-27
                                  • Sustainable offer status
                                    Green Premium product
                                    EU RoHS Directive
                                    Compliant
                                    Mercury free
                                    Yes
                                    RoHS exemption information
                                    Yes
                                    China RoHS Regulation
                                    Product out of China RoHS scope. Substance declaration for your information
                                    Environmental Disclosure
                                    ENVPEP1704004EN
                                    Circularity Profile
                                    ENVEOLI1704004EN
                                    WEEE
                                    The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                                    Warranty
                                    18 months

                                    Frequently Asked Questions

                                    hide show

                                    What is the part number for the spacer used with the LC*D09 through LC*D32 Contactor and the GV2AF3 combination block when the GV2 Motor Circuit Protector is mounted on din rail and the contactor hangs below it?

                                    Issue:
                                    Identifying the spacer part number for use with a LC*D, GV2AF3, and GV2 device combination

                                    Product Line:
                                    Digest 177 Section 18 : Contactors and Starters IEC

                                    Environment:
                                    Products sold and used in the United States

                                    Cause:
                                    Spacer required

                                    Resolution:
                                    Compensation plate catalog number GV1F03, requires 2 pieces snap together.
                                     

                                    What is the part code for a contact block for GV3P40 n/o n/c to fit the left side of the Motor Starter?

                                    The Part code is GVAN11
                                    See link for data sheet:
                                    https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=GVAN11

                                    What is the part number to get 2 extra N/C auxillary contacts on to a GV Motor C/B?

                                    The part numbers to get 2 extra N/C auxillary contacts on to a GV Motor C/B are - GVAE11 & GVAN11
                                    For further information , visit links below:-
                                    https://www.schneider-electric.com.au/en/search/GVAE11
                                    https://www.schneider-electric.com.au/en/search/GVAN11
                                     

                                    What is the part number for a left side mount contact block with 1 N/C & 1 N/O contacts to go with motor start C/B ,GV2ME08?

                                    The part  number for a left side mount contact block with 1 N/C & 1 N/O contacts to go with motor start C/B , GV2ME08 is - GVAN11
                                    For further information , visit link below:-
                                    https://www.schneider-electric.com.au/en/search/GVAN11
                                    User-added image

                                    Will the Compact NSX breaker be for sale in the USA or Canada?

                                    Issue:
                                    Where can I buy a Compact NSX breaker?

                                    Product Line:
                                    Circuit Breakers

                                    Cause:
                                    This breaker is popular overseas and there is interest in the US

                                    Resolution:
                                    There are no plans for a general release of the Compact NSX breaker line in North America, since the NSX is not UL Listed to UL489. (UL 489 is the standard commonly required in the US.) In the US, the Powerpact Circuit Breakers should be used (Powerpact breakers are UL, CSA and IEC-rated).

                                    If an existing piece of equipment has an NSX breaker which needs replacing, we have made a few catalog numbers available for sale in the US. The list of numbers will vary based upon need. Contact your local authorized Schneider Electric distributor for assistance on your specific NSX catalog number.

                                    For support on these breakers, Please see the following link to Global Operations where you can select other Countries:
                                    https://www2.schneider-electric.com/sites/corporate/en/support/operations/local-operations/local-operations.page

                                    What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

                                    Issue:
                                    Identifying maximum power voltage of an LC1D contactor

                                    Product Line:
                                    Digest 177 Section 18: IEC Contactors

                                    Environment:
                                    Products sold and used in the United States

                                    Cause:
                                    Identifying ratings per UL and CSA

                                    Resolution: