Quantcast

Motor Breaker GV4LE Magnetic 80A 25kA Lug Terminal

Motor Breaker GV4LE Magnetic 80A 25kA Lug Terminal

Motor Breaker GV4LE Magnetic 80A 25kA Lug Terminal

Item Number: GV4LE80B6

Retail
$992.10
RRP (Inc. GST)

Product Dimensions

Width icon

Width81 mm

Height icon

Height155 mm

Depth icon

Depth116 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

TeSys

Product or component type

circuit breaker

Device application

motor protection

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

Protection type

short-circuit

[In] rated current

80 A

Control type

toggle

[Ue] rated operational voltage

690 V AC 50/60 Hz conforming to IEC 60947-2

Mounting mode

  • by clips
  • by screws
    • Mounting support

    • 35 mm symmetrical DIN rail
    • 75 mm symmetrical DIN rail
    • plate
      • Mechanical durability

        40000 cycles

        Electrical durability

      • 14000 cycles for AC-3 at 440 V In/2
      • 7000 cycles for AC-3 at 440 V In
        • Local signalling

          green indicatorpresence of auxiliary contacts:

          Connections - terminals

          lugs-ring terminals

          Standards

        • EN/IEC 60947-4-1
        • EN/IEC 60947-2
          • Height

            155 mm

            Width

            81 mm

            Depth

            116 mm

            Net weight

            1.5 kg

            Product certifications

          • IEC
          • CCC
          • EAC
          • EU-RO MR
            • IP degree of protection

              IP40 front face conforming to IEC 60529

              IK degree of protection

              IK07 conforming to IEC 62262

              Ambient air temperature for operation

              -25-70 °C

              Ambient air temperature for storage

              -50-85 °C

              EU RoHS Directive

              Compliant

              Mercury free

              Yes

              RoHS exemption information

              Yes

              China RoHS Regulation

              Product out of China RoHS scope. Substance declaration for your information

              Environmental Disclosure

              ENVPEP1704004EN

              Circularity Profile

              ENVEOLI1704004EN

              Others

              Product name

              TeSys GV4

              Device short name

              GV4L

              Poles description

              3P

              Utilisation category

              category A

              Trip unit technology

            • magnetic
            • electronic
              • Breaking capacity

              • Icu 50 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
              • Icu 25 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
              • Icu 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
              • Icu 10 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
                • [Ics] rated service breaking capacity

                • 50 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
                • 25 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
                • 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
                • 10 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
                  • Trip unit rating

                    480-1120 A

                    Motor power kW

                  • 37-37 kW at 400...415 V AC 50/60 Hz
                  • 45-45 kW at 500 V AC 50/60 Hz
                  • 55-55 kW at 500 V AC 50/60 Hz
                  • 22-22 kW at 400...415 V AC 50/60 Hz
                  • 30-30 kW at 500 V AC 50/60 Hz
                  • 37-37 kW at 660...690 V AC 50/60 Hz
                  • 45-45 kW at 660...690 V AC 50/60 Hz
                  • 55-55 kW at 660...690 V AC 50/60 Hz
                  • 30-30 kW at 400...415 V AC 50/60 Hz
                  • 37-37 kW at 500 V AC 50/60 Hz
                    • [Uimp] rated impulse withstand voltage

                      [Ui] rated insulation voltage

                      800 V conforming to IEC 60947-2

                      Suitability for isolation

                      yes conforming to IEC 60947-1

                      Number of slots

                    • 1 slot(s) for alarm switch for fault signalling contact, plug-in
                    • 1 slot(s) for voltage release for electrical remote tripping, plug-in
                    • 1 slot(s) for auxiliary switch for open/close contact, plug-in
                      • Connection pitch

                        27 mm

                        Tightening torque

                      • 9-9 N.m for 16-95 mm²
                      • 5-5 N.m for 1.5-10 mm²
                        • Quality labels

                          CE

                          Tropicalisation

                          2 conforming to IEC 68-2

                          Pollution degree

                          3 conforming to IEC 60947-1

                          Mechanical robustness

                        • vibrations: +/- 1 mm 2...13.2 Hz conforming to IEC 60068-2-6
                        • vibrations: 0.7 gn 13.2...100 Hz conforming to IEC 60068-2-6
                        • shocks: 15 gn 11 ms conforming to IEC 60068-2-27
                          • Operating altitude

                          • 0...2000 m without derating
                          • 2000...5000 m with derating
                            • Package 1 Weight

                              1.478 kg

                              Package 1 Height

                              16.5 cm

                              Package 1 width

                              11 cm

                              Package 1 Length

                              22 cm

                              WEEE

                              The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

                              PVC free

                              Yes

                              Halogen content performance

                              Halogen free plastic parts product
                              Show all specifications

                              Frequently Asked Questions

                              hide show

                              How many auxiliary contact modules can be installed on the GV3ME__ manual starter?

                              Issue:
                              GV2 and GV3 number of aux switches?

                              Product Line:
                              Manual Starters

                              Environment: 
                              GV2 GV3 manual motor starters, IEC

                              Resolution:
                              One right side mount instantaneous auxiliary module and one internal mount fault signaling auxiliary module.

                              What is the recommended circuit breaker for the ATV31CU22M2 IP54 rated drive?

                              Issue:
                              Recommended circuit breaker for the ATV31CU22M2 IP54 rated drive.

                              Product Line:
                              Altivar ATV31C

                              Environment:
                              All

                              Cause:
                              Wants to use a circuit breaker on the ATV31CU22M2 drive.

                              Resolution:
                              Recommended breakers for the ATV31C........ M2 units are

                              ATV31C018M2=  GV2L08
                              ATV31C037M2=  GV2L10
                              ATV31C055M2=  GV2L14
                              ATV31C075M2=  GV2L14
                              ATV31CU11M2=  GV2L16
                              ATV31CU15M2=  GV2L20
                              ATV31CU22M2=  GV2L22
                               

                              Are explosion proof enclosures available for GV manual motor starters.

                              Issue:
                              NEMA 7/9 rated enclosure for GV manual motor starters

                              Product Line:
                              Tesys GV Motor Starters and Protectors

                              Environment:
                              TeSys™ GV Manual Starters and Protectors

                              Resolution:
                              No hazardous duty enclosures are available for the GV product line.
                              For explosion proof applications consider the Class 2510 Type M or Type T offering.